ZH120 (10 Ton) Bottom Duct

246824-YTG-G-1208

ZH120 (10 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

0.6

0.8

 

1.0

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP RPM BHP

 

 

2 HP & Field

Supplied Drive

 

 

Standard 2

HP & Drive

 

 

 

Hi

Static 3 HP & Drive

 

 

 

2600

722

0.83

776

0.97

828

1.11

878

1.25

926

1.37

973

1.50

1018

1.62

1063

1.74

1106

1.86

1149

1.99

2800

744

0.97

798

1.12

850

1.26

900

1.39

949

1.52

995

1.64

1041

1.76

1085

1.88

1128

2.00

1171

2.13

3000

769

1.13

823

1.28

875

1.42

925

1.55

974

1.68

1020

1.80

1066

1.92

1110

2.05

1153

2.17

1196

2.29

3200

797

1.32

851

1.46

903

1.60

953

1.74

1001

1.86

1048

1.99

1093

2.11

1138

2.23

1181

2.35

1224

2.48

3400

828

1.52

882

1.67

934

1.81

983

1.94

1032

2.07

1078

2.19

1124

2.32

1168

2.44

1212

2.56

1254

2.68

3600

861

1.75

915

1.90

967

2.04

1017

2.17

1065

2.30

1112

2.42

1157

2.54

1201

2.67

1245

2.79

1287

2.91

3800

897

2.00

951

2.15

1002

2.29

1052

2.42

1101

2.55

1147

2.67

1193

2.80

1237

2.92

1280

3.04

1323

3.16

4000

935

2.27

989

2.42

1041

2.56

1091

2.69

1139

2.82

1186

2.95

1231

3.07

1275

3.19

1319

3.31

1362

3.43

4200

976

2.57

1030

2.72

1082

2.86

1132

2.99

1180

3.12

1227

3.24

1272

3.36

-

-

-

-

-

-

4400

1019

2.88

1073

3.03

1125

3.17

1175

3.30

1223

3.43

-

-

-

-

-

-

-

-

-

-

4600

1065

3.22

1119

3.36

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZH150 (12.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

 

1.8

2.0

(CFM)

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM

BHP

RPM

BHP

 

 

3 HP & Field

Supplied Drive

 

 

 

Standard 3 HP & Drive

 

 

 

 

Hi Static 5 HP & Drive

 

3200

797

1.32

851

1.46

903

1.60

953

1.74

1001

1.86

1048

1.99

1093

2.11

1138

2.23

1181

2.35

1224

2.48

3400

828

1.52

882

1.67

934

1.81

983

1.94

1032

2.07

1078

2.19

1124

2.32

1168

2.44

1212

2.56

1254

2.68

3600

861

1.75

915

1.90

967

2.04

1017

2.17

1065

2.30

1112

2.42

1157

2.54

1201

2.67

1245

2.79

1287

2.91

3800

897

2.00

951

2.15

1002

2.29

1052

2.42

1101

2.55

1147

2.67

1193

2.80

1237

2.92

1280

3.04

1323

3.16

4000

935

2.27

989

2.42

1041

2.56

1091

2.69

1139

2.82

1186

2.95

1231

3.07

1275

3.19

1319

3.31

1362

3.43

4200

976

2.57

1030

2.72

1082

2.86

1132

2.99

1180

3.12

1227

3.24

1272

3.36

1316

3.48

1360

3.60

1402

3.73

4400

1019

2.88

1073

3.03

1125

3.17

1175

3.30

1223

3.43

1270

3.55

1315

3.67

1360

3.80

1403

3.92

1446

4.04

4600

1065

3.22

1119

3.36

1171

3.50

1221

3.64

1269

3.76

1316

3.89

1361

4.01

1405

4.13

1449

4.25

1491

4.38

4800

1113

3.57

1167

3.72

1219

3.86

1269

3.99

1317

4.12

1364

4.24

1409

4.36

1453

4.48

1497

4.61

1540

4.73

5000

1163

3.94

1217

4.09

1269

4.23

1319

4.36

1367

4.49

1414

4.62

1459

4.74

1504

4.86

1547

4.98

1590

5.10

5200

1216

4.34

1270

4.48

1321

4.62

1371

4.76

1420

4.88

1466

5.01

1512

5.13

1556

5.25

1600

5.37

1642

5.50

5400

1270

4.75

1324

4.89

1376

5.03

1426

5.17

1474

5.29

1521

5.42

1566

5.54

1611

5.66

-

-

-

-

5600

1327

5.17

1381

5.32

1433

5.46

1483

5.59

1531

5.72

-

-

-

-

-

-

-

-

-

-

5800

1385

5.62

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

5 HP & Field Supplied Drive

 

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.