York R-410A manual YTG-G-1208, ZR090 7.5 Ton Reheat Continued, Johnson Controls Unitary Products

Models: R-410A

1 128
Download 128 pages 30.42 Kb
Page 39
Image 39
ZR090 (7.5 Ton) Reheat (Continued)

246824-YTG-G-1208

ZR090 (7.5 Ton) Reheat (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

 

85

 

80

75

70

 

65

85

 

80

75

70

 

65

 

 

 

 

 

75°F

 

 

 

 

 

 

85°F

 

 

 

 

 

 

72

41.4

6.3

-2.1

 

-2.3

-2.5

-

 

-

39.2

6.7

-0.5

 

-0.5

-0.5

-

 

-

1875

 

67

40.3

6.0

1.8

 

1.7

1.5

1.3

 

-

38.0

6.3

0.1

 

0.1

0.1

0.1

 

-

 

 

62

37.7

5.8

5.8

 

5.6

5.4

5.2

 

5.0

34.9

6.0

-0.1

 

0.0

0.0

0.0

 

0.0

 

 

72

41.9

6.3

-5.5

 

-6.1

-6.6

-

 

-

40.1

6.6

-4.7

 

-5.2

-5.7

-

 

-

2250

 

67

40.9

6.0

4.9

 

4.3

3.7

3.2

 

-

38.9

6.3

3.8

 

3.3

2.8

2.4

 

-

 

62

38.2

5.7

15.1

 

14.5

13.9

13.4

 

12.8

35.7

6.0

11.3

 

10.8

10.3

9.9

 

9.4

 

 

 

 

 

 

 

 

57

37.3

5.7

17.7

 

17.2

16.6

16.0

 

15.5

35.3

6.0

12.2

 

11.7

11.3

10.8

 

10.3

 

 

72

42.5

6.2

-8.8

 

-9.8

-

-

 

-

41.0

6.6

-8.9

 

-9.9

-

-

 

-

2625

 

67

41.4

5.9

7.9

 

6.9

6.0

5.0

 

-

39.8

6.2

7.5

 

6.5

5.6

4.6

 

-

 

62

38.8

5.7

24.4

 

23.4

22.5

21.5

 

20.6

36.5

6.0

22.6

 

21.6

20.7

19.7

 

18.8

 

 

 

 

 

 

 

 

57

37.8

5.7

28.0

 

27.7

26.8

25.8

 

24.9

36.1

6.0

24.6

 

24.3

23.4

22.4

 

21.5

 

 

72

43.1

6.2

-

 

-

-

-

 

-

41.9

6.6

-

 

-

-

-

 

-

3000

 

67

42.0

5.9

10.9

 

9.6

8.2

6.9

 

-

40.7

6.2

11.2

 

9.8

8.3

6.9

 

-

 

62

39.3

5.6

33.7

 

32.4

31.0

29.7

 

28.4

37.3

5.9

33.9

 

32.5

31.0

29.6

 

28.2

 

 

 

 

 

 

 

 

57

38.3

5.6

38.3

 

38.3

37.0

35.6

 

34.3

36.9

5.9

36.9

 

36.9

35.5

34.1

 

32.6

 

 

72

43.6

6.2

-

 

-

-

-

 

-

42.5

6.5

-

 

-

-

-

 

-

3375

 

67

42.5

5.9

13.5

 

11.9

10.3

8.7

 

-

41.2

6.2

14.0

 

12.3

10.6

8.9

 

-

 

62

39.7

5.6

37.0

 

36.3

34.7

33.1

 

31.5

37.9

5.9

36.1

 

35.4

33.7

32.0

 

30.3

 

 

 

 

 

 

 

 

57

38.8

5.6

38.8

 

38.8

37.2

35.6

 

34.0

37.4

5.9

37.4

 

37.4

35.7

34.0

 

32.3

 

 

72

44.1

6.1

-

 

-

-

-

 

-

43.1

6.5

-

 

-

-

-

 

-

3750

 

67

43.0

5.8

16.1

 

14.3

12.4

10.6

 

-

41.8

6.2

16.8

 

14.8

12.8

10.8

 

-

 

62

40.2

5.6

40.2

 

40.2

38.4

36.5

 

34.7

38.4

5.9

38.4

 

38.4

36.4

34.4

 

32.4

 

 

 

 

 

 

 

 

57

39.2

5.6

39.2

 

39.2

37.4

35.5

 

33.7

37.9

5.9

37.9

 

37.9

36.0

34.0

 

32.0

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.