ZR120 (10 Ton) Reheat (Continued)

246824-YTG-G-1208

ZR120 (10 Ton) Reheat (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

 

85

 

80

75

70

 

65

85

 

80

75

70

 

65

 

 

 

 

 

75°F

 

 

 

 

 

 

85°F

 

 

 

 

 

 

72

59.1

8.4

0.6

 

0.7

0.9

-

 

-

52.8

8.9

3.0

 

3.8

4.5

-

 

-

2500

 

67

53.8

8.0

-0.9

 

-0.7

-0.5

-0.4

 

-

49.1

8.4

-6.0

 

-5.2

-4.4

-3.6

 

-

 

 

62

49.1

7.6

-2.2

 

-2.0

-1.9

-1.7

 

-1.5

42.8

8.0

-

 

-

-

-

 

-

 

 

72

62.5

8.1

-4.4

 

-5.1

-5.8

-

 

-

56.8

8.6

-4.1

 

-4.4

-4.7

-

 

-

3000

 

67

56.9

7.7

5.5

 

4.8

4.1

3.4

 

-

52.7

8.1

2.3

 

2.0

1.7

1.4

 

-

 

62

52.0

7.4

14.7

 

14.0

13.3

12.6

 

11.9

46.1

7.8

2.8

 

2.4

2.1

1.8

 

1.5

 

 

 

 

 

 

 

 

57

50.9

7.3

17.4

 

16.8

16.1

15.4

 

14.7

45.6

7.7

2.5

 

2.1

1.8

1.5

 

1.2

 

 

72

65.9

7.9

-9.4

 

-11.0

-12.5

-

 

-

60.7

8.4

-11.1

 

-12.5

-

-

 

-

3500

 

67

60.0

7.5

11.8

 

10.2

8.7

7.1

 

-

56.4

7.9

10.6

 

9.2

7.8

6.4

 

-

 

62

54.8

7.1

31.5

 

30.0

28.4

26.9

 

25.3

49.3

7.5

24.2

 

22.8

21.4

19.9

 

18.5

 

 

 

 

 

 

 

 

57

53.7

7.0

37.0

 

35.9

34.4

32.8

 

31.3

48.8

7.5

27.2

 

26.4

25.0

23.6

 

22.1

 

 

72

69.4

7.6

-

 

-

-

-

 

-

64.7

8.1

-

 

-

-

-

 

-

4000

 

67

63.1

7.2

18.1

 

15.7

13.3

10.9

 

-

60.0

7.6

18.9

 

16.4

13.9

11.4

 

-

 

62

57.7

6.9

48.4

 

46.0

43.5

41.1

 

38.7

52.6

7.3

45.6

 

43.1

40.6

38.1

 

35.6

 

 

 

 

 

 

 

 

57

56.5

6.8

56.5

 

55.1

52.7

50.3

 

47.9

52.0

7.2

52.0

 

50.6

48.1

45.6

 

43.1

 

 

72

70.6

7.6

-

 

-

-

-

 

-

64.7

8.1

-

 

-

-

-

 

-

4500

 

67

64.3

7.2

21.9

 

19.0

16.0

13.0

 

-

60.0

7.6

20.9

 

18.1

15.2

12.3

 

-

 

62

58.7

6.9

54.0

 

52.8

49.9

46.9

 

43.9

52.5

7.3

49.1

 

47.8

44.9

42.1

 

39.2

 

 

 

 

 

 

 

 

57

57.5

6.8

57.5

 

56.8

53.8

50.9

 

47.9

52.0

7.2

52.0

 

51.3

48.4

45.6

 

42.7

 

 

72

71.9

7.6

-

 

-

-

-

 

-

64.7

8.1

-

 

-

-

-

 

-

5000

 

67

65.4

7.2

25.8

 

22.2

18.7

15.2

 

-

60.1

7.6

23.0

 

19.8

16.5

13.3

 

-

 

62

59.7

6.9

59.7

 

59.7

56.2

52.7

 

49.2

52.5

7.3

52.5

 

52.5

49.2

46.0

 

42.8

 

 

 

 

 

 

 

 

57

58.5

6.8

58.5

 

58.5

55.0

51.5

 

47.9

52.0

7.2

52.0

 

52.0

48.7

45.5

 

42.3

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.