XP078-150 Bottom Duct Application
XP078 (6.5 Ton) Bottom Duct
Air Flow |
|
|
|
|
|
| Available External Static Pressure - IWG1 |
|
|
|
|
|
|
| |||||||
0.2 | 0.4 | 0.6 |
| 0.8 | 1.0 |
| 1.2 |
| 1.4 |
| 1.6 |
| 1.8 |
| 2.0 |
| |||||
(CFM) |
|
|
|
|
|
|
| ||||||||||||||
RPM | BHP | RPM | BHP | RPM BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | |||||||||
| |||||||||||||||||||||
| 1.5 HP & Field | Supplied Drive |
| Standard 1.5 HP & Drive |
|
| Hi Static 2 HP & Drive |
|
|
|
|
| |||||||||
1800 | 775 | 0.32 | 849 | 0.54 | 923 | 0.72 | 997 | 0.89 | 1071 | 1.05 | 1147 | 1.20 | 1224 | 1.35 | 1303 | 1.51 | 1385 | 1.68 | 1469 | 1.88 | |
2000 | 805 | 0.46 | 879 | 0.68 | 953 | 0.86 | 1027 | 1.03 | 1101 | 1.19 | 1177 | 1.34 | 1254 | 1.49 | 1333 | 1.65 | 1414 | 1.82 | 1499 | 2.02 | |
2200 | 842 | 0.62 | 916 | 0.84 | 990 | 1.02 | 1064 | 1.19 | 1138 | 1.35 | 1214 | 1.50 | 1291 | 1.65 | 1370 | 1.81 | 1451 | 1.98 | 1536 | 2.18 | |
2400 | 885 | 0.81 | 959 | 1.02 | 1033 | 1.21 | 1107 | 1.38 | 1181 | 1.53 | 1257 | 1.68 | 1334 | 1.83 | 1413 | 1.99 | 1495 | 2.17 | - | - | |
2600 | 933 | 1.01 | 1007 | 1.23 | 1081 | 1.41 | 1155 | 1.58 | 1229 | 1.74 | 1305 | 1.89 | 1382 | 2.04 | 1461 | 2.20 | - | - | - | - | |
2800 | 985 | 1.24 | 1059 | 1.46 | 1132 | 1.64 | 1206 | 1.81 | 1281 | 1.97 | 1356 | 2.12 | 1433 | 2.27 | - | - | - | - | - | - | |
3000 | 1040 | 1.49 | 1114 | 1.71 | 1187 | 1.90 | 1261 | 2.06 | 1336 | 2.22 | - | - | - | - | - | - | - | - | - | - | |
3200 | 1097 | 1.77 | 1171 | 1.98 | 1245 | 2.17 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
3400 | 1157 | 2.06 | 1231 | 2.28 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
|
|
|
|
|
|
|
|
|
|
|
|
| 2 HP & Field Supplied Drive |
|
|
|
|
1.Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3.kW = BHP x 0.932.
XP090 (7.5 Ton) Bottom Duct
Air Flow |
|
|
|
|
|
| Available External Static Pressure - IWG1 |
|
|
|
|
|
|
| |||||||
0.2 | 0.4 | 0.6 |
| 0.8 | 1.0 |
| 1.2 |
| 1.4 |
| 1.6 |
| 1.8 |
| 2.0 |
| |||||
(CFM) |
|
|
|
|
|
|
| ||||||||||||||
RPM | BHP | RPM | BHP | RPM BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | |||||||||
| |||||||||||||||||||||
| 1.5 HP & Field | Supplied Drive |
| Standard 1.5 HP & Drive |
|
| Hi Static 3 HP & Drive |
|
|
|
|
| |||||||||
2000 | 805 | 0.46 | 879 | 0.68 | 953 | 0.86 | 1027 | 1.03 | 1101 | 1.19 | 1177 | 1.34 | 1254 | 1.49 | 1333 | 1.65 | 1414 | 1.82 | 1499 | 2.02 | |
2200 | 842 | 0.62 | 916 | 0.84 | 990 | 1.02 | 1064 | 1.19 | 1138 | 1.35 | 1214 | 1.50 | 1291 | 1.65 | 1370 | 1.81 | 1451 | 1.98 | 1536 | 2.18 | |
2400 | 885 | 0.81 | 959 | 1.02 | 1033 | 1.21 | 1107 | 1.38 | 1181 | 1.53 | 1257 | 1.68 | 1334 | 1.83 | 1413 | 1.99 | 1495 | 2.17 | 1579 | 2.36 | |
2600 | 933 | 1.01 | 1007 | 1.23 | 1081 | 1.41 | 1155 | 1.58 | 1229 | 1.74 | 1305 | 1.89 | 1382 | 2.04 | 1461 | 2.20 | 1542 | 2.37 | 1627 | 2.57 | |
2800 | 985 | 1.24 | 1059 | 1.46 | 1132 | 1.64 | 1206 | 1.81 | 1281 | 1.97 | 1356 | 2.12 | 1433 | 2.27 | 1512 | 2.43 | 1594 | 2.60 | 1679 | 2.80 | |
3000 | 1040 | 1.49 | 1114 | 1.71 | 1187 | 1.90 | 1261 | 2.06 | 1336 | 2.22 | 1411 | 2.37 | 1488 | 2.52 | 1567 | 2.68 | 1649 | 2.85 | 1734 | 3.05 | |
3200 | 1097 | 1.77 | 1171 | 1.98 | 1245 | 2.17 | 1319 | 2.34 | 1393 | 2.49 | 1469 | 2.64 | 1546 | 2.80 | 1625 | 2.96 | 1706 | 3.13 | 1791 | 3.33 | |
3400 | 1157 | 2.06 | 1231 | 2.28 | 1305 | 2.47 | 1379 | 2.63 | 1453 | 2.79 | 1529 | 2.94 | 1606 | 3.09 | 1685 | 3.25 | 1766 | 3.43 | - | - | |
3600 | 1219 | 2.38 | 1293 | 2.60 | 1367 | 2.78 | 1440 | 2.95 | 1515 | 3.11 | 1590 | 3.26 | 1667 | 3.41 | - | - | - | - | - | - | |
3800 | 1282 | 2.72 | 1356 | 2.93 | 1430 | 3.12 | 1504 | 3.29 | 1578 | 3.45 | - | - | - | - | - | - | - | - | - | - | |
|
|
|
|
|
|
|
|
|
|
| 3 HP & Field Supplied Drive |
|
|
|
|
|
|
1.Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3.kW = BHP x 0.932.
XP102 (8.5 Ton) Bottom Duct
Air Flow |
|
|
|
|
|
| Available External Static Pressure - IWG1 |
|
|
|
|
|
|
| |||||||
0.2 | 0.4 | 0.6 | 0.8 | 1.0 |
| 1.2 |
| 1.4 |
| 1.6 |
| 1.8 |
| 2.0 |
| ||||||
(CFM) |
|
|
|
|
|
| |||||||||||||||
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | ||||||||
| |||||||||||||||||||||
| 2 HP & Field | Supplied Drive |
|
| Standard 2 | HP & Drive |
|
|
|
| Hi Static 3 | HP & Drive |
|
| |||||||
2200 | 662 | 0.53 | 717 | 0.68 | 770 | 0.83 | 821 | 0.96 | 870 | 1.09 | 918 | 1.22 | 965 | 1.35 | 1010 | 1.47 | 1055 | 1.59 | 1098 | 1.71 | |
2400 | 677 | 0.63 | 732 | 0.78 | 784 | 0.93 | 835 | 1.06 | 885 | 1.19 | 933 | 1.32 | 979 | 1.44 | 1025 | 1.57 | 1069 | 1.69 | 1112 | 1.81 | |
2600 | 693 | 0.75 | 748 | 0.90 | 801 | 1.04 | 852 | 1.18 | 901 | 1.31 | 949 | 1.44 | 996 | 1.56 | 1041 | 1.68 | 1085 | 1.80 | 1129 | 1.92 | |
2800 | 712 | 0.88 | 767 | 1.03 | 819 | 1.17 | 871 | 1.31 | 920 | 1.44 | 968 | 1.57 | 1014 | 1.69 | 1060 | 1.81 | 1104 | 1.94 | 1148 | 2.06 | |
3000 | 733 | 1.03 | 788 | 1.18 | 841 | 1.33 | 892 | 1.46 | 941 | 1.59 | 989 | 1.72 | 1036 | 1.84 | 1081 | 1.97 | 1125 | 2.09 | 1169 | 2.21 | |
3200 | 757 | 1.20 | 811 | 1.36 | 864 | 1.50 | 915 | 1.64 | 964 | 1.77 | 1012 | 1.89 | 1059 | 2.02 | 1104 | 2.14 | 1149 | 2.26 | 1192 | 2.38 | |
3400 | 782 | 1.40 | 837 | 1.55 | 890 | 1.69 | 941 | 1.83 | 990 | 1.96 | 1038 | 2.09 | 1085 | 2.21 | 1130 | 2.33 | 1174 | 2.45 | 1218 | 2.58 | |
3600 | 810 | 1.61 | 865 | 1.76 | 918 | 1.91 | 969 | 2.04 | 1018 | 2.18 | 1066 | 2.30 | 1113 | 2.43 | 1158 | 2.55 | 1203 | 2.67 | 1246 | 2.79 | |
3800 | 841 | 1.85 | 896 | 2.00 | 948 | 2.14 | 999 | 2.28 | 1049 | 2.41 | 1097 | 2.54 | 1143 | 2.66 | 1189 | 2.78 | 1233 | 2.91 | 1276 | 3.03 | |
4000 | 874 | 2.11 | 928 | 2.26 | 981 | 2.40 | 1032 | 2.54 | 1082 | 2.67 | 1130 | 2.80 | 1176 | 2.92 | 1222 | 3.04 | 1266 | 3.16 | 1309 | 3.28 | |
4200 | 909 | 2.38 | 963 | 2.53 | 1016 | 2.68 | 1067 | 2.81 | 1117 | 2.95 | 1164 | 3.07 | 1211 | 3.20 | 1256 | 3.32 | 1301 | 3.44 | - | - | |
|
|
|
|
|
|
|
|
|
|
|
|
| 3 HP & Field Supplied Drive |
|
|
|
|
1.Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3.kW = BHP x 0.932.
74 | Johnson Controls Unitary Products |