York R-410A manual YTG-G-1208, ZR102 8.5 Ton Reheat Continued, Johnson Controls Unitary Products

Models: R-410A

1 128
Download 128 pages 30.42 Kb
Page 43
Image 43
ZR102 (8.5 Ton) Reheat (Continued)

246824-YTG-G-1208

ZR102 (8.5 Ton) Reheat (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

 

85

 

80

75

70

 

65

85

 

80

75

70

 

65

 

 

 

 

 

75°F

 

 

 

 

 

 

85°F

 

 

 

 

 

 

72

42.8

6.3

-0.9

 

-1.0

-1.1

-

 

-

37.6

6.4

-0.6

 

-0.4

-0.1

-

 

-

2125

 

67

35.4

6.5

1.6

 

1.5

1.4

1.2

 

-

28.6

6.8

-1.2

 

-1.0

-0.8

-0.6

 

-

 

 

62

31.9

6.2

4.4

 

4.3

4.2

4.1

 

4.0

24.7

6.5

-0.7

 

-0.5

-0.3

0.0

 

0.2

 

 

72

50.9

6.2

-2.8

 

-3.6

-4.4

-

 

-

48.3

6.4

-3.2

 

-3.6

-4.1

-

 

-

2550

 

67

42.1

6.4

6.2

 

5.4

4.7

3.9

 

-

37.3

6.8

3.3

 

2.9

2.5

2.0

 

-

 

62

38.0

6.1

16.6

 

15.8

15.0

14.3

 

13.5

32.5

6.5

13.0

 

12.5

12.1

11.6

 

11.2

 

 

 

 

 

 

 

 

57

29.4

6.1

16.6

 

15.8

15.0

14.3

 

13.5

22.5

6.4

10.6

 

10.1

9.7

9.3

 

8.8

 

 

72

59.1

6.2

-4.8

 

-6.2

-7.7

-

 

-

58.9

6.3

-5.8

 

-6.9

-8.0

-

 

-

2975

 

67

48.9

6.4

10.8

 

9.4

8.0

6.6

 

-

46.0

6.7

7.9

 

6.8

5.7

4.6

 

-

 

62

44.0

6.1

28.7

 

27.3

25.9

24.5

 

23.1

40.2

6.4

26.6

 

25.5

24.4

23.3

 

22.2

 

 

 

 

 

 

 

 

57

34.1

6.0

27.7

 

27.3

25.9

24.5

 

23.1

28.4

6.4

22.4

 

22.2

21.1

20.0

 

19.0

 

 

72

67.2

6.2

-6.8

 

-8.9

-10.9

-

 

-

69.6

6.3

-8.4

 

-10.1

-

-

 

-

3400

 

67

55.6

6.3

15.4

 

13.3

11.3

9.2

 

-

54.7

6.7

12.5

 

10.7

9.0

7.3

 

-

 

62

50.1

6.0

40.9

 

38.8

36.8

34.7

 

32.6

48.0

6.4

40.2

 

38.5

36.7

35.0

 

33.3

 

 

 

 

 

 

 

 

57

38.8

6.0

38.8

 

38.8

36.8

34.7

 

32.6

34.3

6.3

34.3

 

34.3

32.6

30.8

 

29.1

 

 

72

68.6

6.1

-

 

-

-

-

 

-

69.7

6.2

-

 

-

-

-

 

-

3825

 

67

56.7

6.3

19.7

 

17.0

14.4

11.7

 

-

54.6

6.6

17.2

 

14.9

12.5

10.2

 

-

 

62

51.1

6.0

46.5

 

45.5

42.8

40.1

 

37.5

47.9

6.3

45.3

 

45.4

43.1

40.7

 

38.3

 

 

 

 

 

 

 

 

57

39.6

5.9

39.6

 

39.6

36.9

34.3

 

31.6

34.0

6.3

34.0

 

34.0

31.6

29.3

 

26.9

 

 

72

69.9

6.1

-

 

-

-

-

 

-

69.8

6.2

-

 

-

-

-

 

-

4250

 

67

57.8

6.3

24.0

 

20.8

17.5

14.2

 

-

54.5

6.6

22.0

 

19.0

16.0

13.1

 

-

 

62

52.1

5.9

52.1

 

52.1

48.8

45.6

 

42.3

47.7

6.3

47.7

 

47.7

47.7

46.4

 

43.4

 

 

 

 

 

 

 

 

57

40.4

5.9

40.4

 

40.4

37.1

33.9

 

30.6

33.7

6.2

33.7

 

33.7

30.7

27.8

 

24.8

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

43

Page 43
Image 43
York R-410A manual YTG-G-1208, ZR102 8.5 Ton Reheat Continued, Johnson Controls Unitary Products