![XP120 (10 Ton) Bottom Duct](/images/new-backgrounds/35089/35089149x1.webp)
XP120 (10 Ton) Bottom Duct
Air Flow |
|
|
|
|
|
| Available External Static Pressure - IWG1 |
|
|
|
|
|
|
| |||||||
0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 |
| 1.6 |
| 1.8 |
| 2.0 |
| ||||||||
(CFM) |
|
|
|
| |||||||||||||||||
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM BHP | RPM BHP | RPM BHP RPM BHP | |||||||
| |||||||||||||||||||||
| 2 HP & Field | Supplied Drive |
|
| Standard 2 | HP & Drive |
|
|
| Hi | Static 3 HP & Drive |
|
|
| |||||||
2600 | 693 | 0.75 | 748 | 0.90 | 801 | 1.04 | 852 | 1.18 | 901 | 1.31 | 949 | 1.44 | 996 | 1.56 | 1041 | 1.68 | 1085 | 1.80 | 1129 | 1.92 | |
2800 | 712 | 0.88 | 767 | 1.03 | 819 | 1.17 | 871 | 1.31 | 920 | 1.44 | 968 | 1.57 | 1014 | 1.69 | 1060 | 1.81 | 1104 | 1.94 | 1148 | 2.06 | |
3000 | 733 | 1.03 | 788 | 1.18 | 841 | 1.33 | 892 | 1.46 | 941 | 1.59 | 989 | 1.72 | 1036 | 1.84 | 1081 | 1.97 | 1125 | 2.09 | 1169 | 2.21 | |
3200 | 757 | 1.20 | 811 | 1.36 | 864 | 1.50 | 915 | 1.64 | 964 | 1.77 | 1012 | 1.89 | 1059 | 2.02 | 1104 | 2.14 | 1149 | 2.26 | 1192 | 2.38 | |
3400 | 782 | 1.40 | 837 | 1.55 | 890 | 1.69 | 941 | 1.83 | 990 | 1.96 | 1038 | 2.09 | 1085 | 2.21 | 1130 | 2.33 | 1174 | 2.45 | 1218 | 2.58 | |
3600 | 810 | 1.61 | 865 | 1.76 | 918 | 1.91 | 969 | 2.04 | 1018 | 2.18 | 1066 | 2.30 | 1113 | 2.43 | 1158 | 2.55 | 1203 | 2.67 | 1246 | 2.79 | |
3800 | 841 | 1.85 | 896 | 2.00 | 948 | 2.14 | 999 | 2.28 | 1049 | 2.41 | 1097 | 2.54 | 1143 | 2.66 | 1189 | 2.78 | 1233 | 2.91 | 1276 | 3.03 | |
4000 | 874 | 2.11 | 928 | 2.26 | 981 | 2.40 | 1032 | 2.54 | 1082 | 2.67 | 1130 | 2.80 | 1176 | 2.92 | 1222 | 3.04 | 1266 | 3.16 | 1309 | 3.28 | |
4200 | 909 | 2.38 | 963 | 2.53 | 1016 | 2.68 | 1067 | 2.81 | 1117 | 2.95 | 1164 | 3.07 | 1211 | 3.20 | 1256 | 3.32 | 1301 | 3.44 | - | - | |
4400 | 946 | 2.68 | 1000 | 2.83 | 1053 | 2.98 | 1104 | 3.11 | 1154 | 3.24 | 1202 | 3.37 | - | - | - | - | - | - | - | - | |
4600 | 985 | 3.00 | 1040 | 3.15 | 1092 | 3.29 | 1143 | 3.43 | - | - | - | - | - | - | - | - | - | - | - | - | |
4800 | 1026 | 3.33 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | |
|
|
|
|
|
|
|
|
|
| 3 HP & Field Supplied Drive |
|
|
|
|
|
|
|
1.Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3.kW = BHP x 0.932.
XP150 (12.5 Ton) Bottom Duct
Air Flow |
|
|
|
|
|
| Available External Static Pressure - IWG1 |
|
|
|
|
|
| ||||||||
0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 | 1.6 |
| 1.8 | 2.0 | |||||||||||
(CFM) |
| ||||||||||||||||||||
RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM BHP | RPM | BHP | RPM | BHP | |||
| |||||||||||||||||||||
|
| 3 HP & Field Supplied Drive |
|
|
|
| Standard 3 HP & Drive |
|
|
| Hi Static 5 HP & Drive | ||||||||||
3200 | 757 | 1.20 | 811 | 1.36 | 864 | 1.50 | 915 | 1.64 | 964 | 1.77 | 1012 | 1.89 | 1059 | 2.02 | 1104 | 2.14 | 1149 | 2.26 | 1192 | 2.38 | |
3400 | 782 | 1.40 | 837 | 1.55 | 890 | 1.69 | 941 | 1.83 | 990 | 1.96 | 1038 | 2.09 | 1085 | 2.21 | 1130 | 2.33 | 1174 | 2.45 | 1218 | 2.58 | |
3600 | 810 | 1.61 | 865 | 1.76 | 918 | 1.91 | 969 | 2.04 | 1018 | 2.18 | 1066 | 2.30 | 1113 | 2.43 | 1158 | 2.55 | 1203 | 2.67 | 1246 | 2.79 | |
3800 | 841 | 1.85 | 896 | 2.00 | 948 | 2.14 | 999 | 2.28 | 1049 | 2.41 | 1097 | 2.54 | 1143 | 2.66 | 1189 | 2.78 | 1233 | 2.91 | 1276 | 3.03 | |
4000 | 874 | 2.11 | 928 | 2.26 | 981 | 2.40 | 1032 | 2.54 | 1082 | 2.67 | 1130 | 2.80 | 1176 | 2.92 | 1222 | 3.04 | 1266 | 3.16 | 1309 | 3.28 | |
4200 | 909 | 2.38 | 963 | 2.53 | 1016 | 2.68 | 1067 | 2.81 | 1117 | 2.95 | 1164 | 3.07 | 1211 | 3.20 | 1256 | 3.32 | 1301 | 3.44 | 1344 | 3.56 | |
4400 | 946 | 2.68 | 1000 | 2.83 | 1053 | 2.98 | 1104 | 3.11 | 1154 | 3.24 | 1202 | 3.37 | 1248 | 3.49 | 1294 | 3.62 | 1338 | 3.74 | 1381 | 3.86 | |
4600 | 985 | 3.00 | 1040 | 3.15 | 1092 | 3.29 | 1143 | 3.43 | 1193 | 3.56 | 1241 | 3.69 | 1287 | 3.81 | 1333 | 3.93 | 1377 | 4.05 | 1420 | 4.18 | |
4800 | 1026 | 3.33 | 1081 | 3.48 | 1133 | 3.63 | 1184 | 3.76 | 1234 | 3.90 | 1282 | 4.02 | 1328 | 4.15 | 1374 | 4.27 | 1418 | 4.39 | 1461 | 4.51 | |
5000 | 1069 | 3.69 | 1124 | 3.84 | 1177 | 3.98 | 1228 | 4.12 | 1277 | 4.25 | 1325 | 4.38 | 1372 | 4.50 | 1417 | 4.62 | 1461 | 4.74 | 1505 | 4.87 | |
5200 | 1114 | 4.06 | 1169 | 4.21 | 1222 | 4.35 | 1273 | 4.49 | 1322 | 4.62 | 1370 | 4.75 | 1417 | 4.87 | 1462 | 5.00 | 1506 | 5.12 | 1550 | 5.24 | |
5400 | 1161 | 4.45 | 1216 | 4.60 | 1268 | 4.74 | 1319 | 4.88 | 1369 | 5.01 | 1417 | 5.14 | 1463 | 5.26 | 1509 | 5.38 | 1553 | 5.51 | 1596 | 5.63 | |
5600 | 1210 | 4.86 | 1264 | 5.01 | 1317 | 5.15 | 1368 | 5.29 | 1418 | 5.42 | 1465 | 5.55 | 1512 | 5.67 | - | - | - | - | - | - | |
5800 | 1260 | 5.28 | 1315 | 5.43 | 1367 | 5.57 | 1418 | 5.71 | - | - | - | - | - | - | - | - | - | - | - | - | |
|
|
|
|
|
|
|
|
|
| 5 HP & Field Supplied Drive |
|
|
|
|
|
|
|
1.Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3.kW = BHP x 0.932.
Johnson Controls Unitary Products | 75 |