Air supply requirements below apply to all

Installation (contd.)

19

 

 

 

 

NOTE

The heater requires two uninterrupted air supply openings; one for ventilation and one to supply oxygen for proper gas combustion. The air supply openings should be sized according to Tables 10. and 11.

Air supply requirements below apply to all

b)Construct a non-combustible base from masonry blocks as illustrated, see Figure 23.

MiniMax heaters, including PowerMax versions.

 

All Air From Inside

 

 

 

Model

Air for Combustion

Air Ventilation

Sq. In.

Sq. In.

 

 

 

 

150

150

150

 

 

 

195/200

200

200

 

 

 

250

250

250

 

 

 

300

300

300

 

 

 

350

350

350

 

 

 

400

400

400

BASE FOR USE ON COMBUSTIBLE FLOORS

SHEET METAL

BLOCKS

T

O

H

. MiniMax heaters, including PowerMax versions. Min 6" STACK TYPE INDOOR DRAFT HOOD KIT

. Manual background Min 6"

Manual background HOLLOW MASONARY BLOCKS, NOT LESS THAN 4" THICK (LAID WITH ENDS UNSEALED AND JOINTS MATCHED FOR AIR CIRCULATION). COVER BLOCKS WITH

24 GA. (MIN.) GALVANIZED SHEET METAL.

Table 10.

Figure 23.

 

All Air From Outside

 

 

 

Model

Air for Combustion

Air Ventilation

Sq. In.

Sq. In.

 

 

 

 

150

37

37

 

 

 

195/200

50

50

 

 

 

250

63

63

 

 

 

300

77

77

 

 

 

350

90

90

 

 

 

400

100

100

 

 

 

Manual backgroundCAUTION

Chemicals should not be stored near the heater installation. Combustion air can be contaminated by corrosive chemical fumes which can void the warranty.

Table 11.

INSTALLATION ON FLOORS CONSTRUCTED OF COMBUSTIBLE MATERIALS

The heater may be placed on a “combustible floor” using either of the two methods listed below:

a)Use Listed Factory Non-combustible Base Kit for use on combustible floors.

Model

Non-Combustible Base Kit

 

 

150

471389

 

 

195/200

471390

 

 

250

471391

 

 

300

471392

 

 

350

471393

 

 

400

471394

 

 

Table 12.

Rev. G 1-22-04

STACK TYPE INDOOR DRAFT HOOD KIT

The proper draft hood and adapter must be installed on the heater as shown below and on page 20:

Model

Draft Hood

Product No.

Vent Dia.

 

 

 

 

150

DH15

460227

6 in.

 

 

 

 

195/200

DH20

460228

7 in.

 

 

 

 

250

DH25

460230

7 in.

 

 

 

 

300

DH30

460231

8 in.

 

 

 

 

350

DH35

460233

9 in.

 

 

 

 

400

DH40

460234

10 in.

 

 

 

 

Table 13.

P/N 471048

Image 19
Contents FOR YOUR SAFETY - READ BEFORE OPERATING MiniMax Plus and PowerMaxOPERATION & INSTALLATION MANUAL For Your SafetyTable of Contents IMPORTANT NOTICES IntroductionPool and Spa Heaters CODE REQUIREMENTSSAFETY RULES WARRANTY INFORMATIONOperation WHAT TO DO IF YOU SMELL GAS FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCESafety Lockout WHAT TO DO IF YOU SMELL GAS LIGHTING INSTRUCTIONSGas control knobs shown in “OFF” position POWER THERMOSTAT SELECT SWITCH INDICATOR LIGHT DESCRIPTIONOPERATING CONTROLS THERMOSTAT ADJUSTMENTSERVICE SERVICE TROUBLESHOOTING CONTROLSHEAT HEAT HEATER FIRING - NORMAL OPERATION TROUBLESHOOTING CONTROLS - ContinuedIS IN THERMAL FUSE CIRCUIT SPRING AND FALL OPERATION MaintenanceMAINTENANCE INSTRUCTIONS ENERGY SAVING TIPSPOOL AND SPA WATER CHEMICAL BALANCEpH Chart pH Control ChartOutdoor installation - with vent kit Installation InstructionsSPECIFICATIONS Outdoor installation - stacklessBELOW POOL INSTALLATION WATER CONNECTIONSPLUMBING PLUMBING CONNECTIONSQUICK-FLANGEINSTALLATION INSTRUCTIONS externally to the heater GAS CONNECTIONSGAS LINE INSTALLATIONS A manual main shut-offvalve must be installedSTACK TYPE OUTDOOR VENT KIT VENTILATIONOUTDOOR INSTALLATION ONLY OUTDOOR VENT CAP INSTALLATIONRemaining FrontWater Connection 24 inSTACK TYPE INDOOR DRAFT HOOD KIT MiniMax heaters, including PowerMax versionsAir supply requirements below apply to all Draft Hood Top Cover Adaptor Screw 2 PLCs HEATER INDOOR DRAFT HOOD INSTALLATIONTransformer Wiring Instruction ELECTRICAL, IID ELECTRONIC UNITSMiniMax Plus WIRING DIAGRAM Ignition Wiring DiagramMiniMax Plus Electronic 2 Wire Remote MiniMax Plus Millivolt Wiring DiagramREMOTE SWITCH DUAL THERM IID ONLY 3 Wire RemoteTroubleshooting - General 470024 MINIMAX PLUS HEATER - ALL MODELSINNER TOPS Model NoDESCRIPTION MiniMax Plus Only Parts List195/200 Not Shown MiniMax Plus Only Parts List, contdDESCRIPTION 195/200APPENDIX PowerMax Pool & Spa HeaterOPERATION & INSTALLATION MANUAL INSTALLER AFFIX THESE INSTRUCTIONSPool and Spa Heater PowerMaxSYSTEM OPERATION MOUNTING ASSEMBLYPRESSURE SWITCH OPERATION DESCRIPTION OF SYSTEM OPERATIONReduced Maximum Equivalent Vent Run feet VENTINGDIAGRAM INDOOR INSTALLATIONS POWERMAX VENTING GUIDELINESVent for roof penetration installations Vent termination for side wall installationsThe Vent Pipe OUTDOOR INSTALLATION POWERMAX VENTING GUIDELINESVent Termination POWERMAX WIRING DIAGRAM ASSEMBLY TO A POOL HEATER WITH IID IGNITION INSTRUCTION FOR WIRING A POWERMAX INDUCED DRAFTWIRING DIAGRAM FOR POWERMAX KIT OPTIONAL OUTDOOR VENT POWERMAX HEATER - ALL MODELSA-10 DESCRIPTION PowerMax Heater Only Parts List195/200 DESCRIPTION PowerMax Heater Only Parts List, contdNot Shown PowerMax Assembly PowerMax Assembly Parts ListDESCRIPTION Pentair Pool Products, Inc SAVE THESE INSTRUCTIONS