Pentair PowerMax Outdoor Installation Powermax Venting Guidelines, The Vent Pipe, Diagram

Page 32
OUTDOOR INSTALLATION

P/N 471048

OUTDOOR INSTALLATION

POWERMAX VENTING GUIDELINES

G

Outdoor

Stack Kit

F

6 in. min.

 

A

D

1'

3'

C

4'

4'

B

4'

Property Line

E

A-6

Walkway

F Optional Horizontal Venting.

ECheck local building codes for setback requirements.

The Vent Pipe:

Must be the same diameter as the vent connector.

Must be suitable for use with Category III Appliances which have flue gas temperatures of less than 400 deg. F.

Vent Termination:

Must be not less than 7 ft. above public walkways.

AMust be at least 3 ft. above any forced air inlet located within a 10 ft. radius.

Must be located the following distances away from any door, window, or gravity air inlet:

B4 ft. below, or

C4 ft. horizontally, or

D1 ft. above

G

POWERMAX OUTDOOR STACK KITS

MODEL

STACK DIA.

KIT MODEL

 

PMX 150

3"

471395

 

PMX 200

3"

471395

 

PMX 250

4"

471396

 

PMX 300

4"

471396

 

PMX 350

4"

471396

 

PMX 400

4"

471396

Rev. G 1-22-04

(DIAGRAM 2)

Image 32
Contents MiniMax Plus and PowerMax OPERATION & INSTALLATION MANUALFor Your Safety FOR YOUR SAFETY - READ BEFORE OPERATINGTable of Contents Introduction Pool and Spa HeatersCODE REQUIREMENTS IMPORTANT NOTICESOperation WARRANTY INFORMATIONSAFETY RULES FOR YOUR SAFETY READ BEFORE LIGHTING OPERATING INSTRUCTIONSTO TURN OFF GAS TO APPLIANCE WHAT TO DO IF YOU SMELL GASSafety Lockout Gas control knobs shown in “OFF” position LIGHTING INSTRUCTIONSWHAT TO DO IF YOU SMELL GAS INDICATOR LIGHT DESCRIPTION OPERATING CONTROLSTHERMOSTAT ADJUSTMENT POWER THERMOSTAT SELECT SWITCHHEAT HEAT TROUBLESHOOTING CONTROLSSERVICE SERVICE IS IN THERMAL FUSE CIRCUIT TROUBLESHOOTING CONTROLS - ContinuedHEATER FIRING - NORMAL OPERATION Maintenance MAINTENANCE INSTRUCTIONSENERGY SAVING TIPS SPRING AND FALL OPERATIONCHEMICAL BALANCE pH ChartpH Control Chart POOL AND SPA WATERInstallation Instructions SPECIFICATIONSOutdoor installation - stackless Outdoor installation - with vent kitWATER CONNECTIONS PLUMBINGPLUMBING CONNECTIONS BELOW POOL INSTALLATIONQUICK-FLANGEINSTALLATION INSTRUCTIONS GAS CONNECTIONS GAS LINE INSTALLATIONSA manual main shut-offvalve must be installed externally to the heaterVENTILATION OUTDOOR INSTALLATION ONLYOUTDOOR VENT CAP INSTALLATION STACK TYPE OUTDOOR VENT KITFront Water Connection24 in RemainingAir supply requirements below apply to all MiniMax heaters, including PowerMax versionsSTACK TYPE INDOOR DRAFT HOOD KIT INDOOR DRAFT HOOD INSTALLATION Transformer Wiring InstructionELECTRICAL, IID ELECTRONIC UNITS Draft Hood Top Cover Adaptor Screw 2 PLCs HEATERMiniMax Plus Electronic Ignition Wiring DiagramMiniMax Plus WIRING DIAGRAM MiniMax Plus Millivolt Wiring Diagram REMOTE SWITCH DUAL THERM IID ONLY3 Wire Remote 2 Wire RemoteTroubleshooting - General MINIMAX PLUS HEATER - ALL MODELS INNER TOPSModel No 470024195/200 MiniMax Plus Only Parts ListDESCRIPTION MiniMax Plus Only Parts List, contd DESCRIPTION195/200 Not ShownPowerMax Pool & Spa Heater OPERATION & INSTALLATION MANUALINSTALLER AFFIX THESE INSTRUCTIONS APPENDIXPowerMax Pool and Spa HeaterMOUNTING ASSEMBLY PRESSURE SWITCH OPERATIONDESCRIPTION OF SYSTEM OPERATION SYSTEM OPERATIONVENTING Reduced Maximum Equivalent Vent Run feetINDOOR INSTALLATIONS POWERMAX VENTING GUIDELINES Vent for roof penetration installationsVent termination for side wall installations DIAGRAMVent Termination OUTDOOR INSTALLATION POWERMAX VENTING GUIDELINESThe Vent Pipe POWERMAX WIRING DIAGRAM INSTRUCTION FOR WIRING A POWERMAX INDUCED DRAFT ASSEMBLY TO A POOL HEATER WITH IID IGNITIONWIRING DIAGRAM FOR POWERMAX KIT A-10 POWERMAX HEATER - ALL MODELSOPTIONAL OUTDOOR VENT 195/200 PowerMax Heater Only Parts ListDESCRIPTION Not Shown PowerMax Heater Only Parts List, contdDESCRIPTION DESCRIPTION PowerMax Assembly Parts ListPowerMax Assembly SAVE THESE INSTRUCTIONS Pentair Pool Products, Inc