GAS PRESSURE REGULATOR
The gas pressure regulator is preset at 4.0 in. WC throughout for natural gas, and 10.5 in. WC. for propane gas. The pressure at the gas valve, taken with a manometer, should be about 4.0 in. WC natural gas (3.0 in. WC for Low NOx) and 10.5 in. WC propane gas. If an adjustment is needed, remove seal
and turn adjustment screw clockwise to increase
pressure or
NOTE: Low NOx gas valves are
MANOMETER
MANUAL
VALVE
GAS PRESSURE
TEST AT GAS VALVE
ELECTRONIC IGNITION GAS
Gas Pressure
Adjustment
Robertshaw 7200 | Robertshaw 7000 BDER |
(Heater Model 206) | (Heater Models |
Gas Pressure
Adjustment
Robertshaw 7000 DERHC
(Heater Model 406)
Gas Valve
GAS PRESSURE ADJUSTMENT LOCATIONS
MILLIVOLT GAS VALVES
Gas Pressure
Adjustment
Fig # 9263
Robertshaw 7000
(Heater Models
ELECTRONIC IGNITION GAS VALVES
Gas Pressure
Adjustment
Honeywell VR8304 (Heater Models 206- 406)
Fig # 9263
Robertshaw 7000 BDERF
(Heater Models
PIPE SIZING FOR GAS CONNECTIONS
Maximum Equivalent Pipe Length
Natural Gas 1000 BTU/FT3 0.60
Specific Gravity @ 0.5 in. WC Pressure Drop
Propane Gas 2500 BTU/FT3 1.53
Specific Gravity @ 0.5 in. WC Pressure Drop
Input | 3/4” | 1” |
Model (KBTU) N P N P N P N P
206/207 199.5 25 60 90 215 360
266/267 266.0 15 35 50 125 210 480 445
336/337 332.5 10 20 30 80 140 320 290
406/407 399.0 15 20 55 95 225 215 480
20