WATER PRESSURE SWITCH
The water pressure switch, or heater actuator, ensures that the heater operates only when the filter pump is in operation. It is located on the inlet/outlet header. It is factory set at 1.75 PSI for
WATER PRESSURE SWITCH ADJUSTMENT
FLAME ROLL-OUT SAFETY SWITCH
Atmospheric heaters are equipped with a thermal cut- off device to prevent flame
Fig.# 9438
PRESSURE SWITCH ADJUSTMENT RANGE
1.With pump and heater on, turn adjustment knob clockwise until a click is heard from the gas valve.
2.Turn adjustment knob
3.Turn pump off and on several times. Heater should shut off immedi- ately. If it does not, repeat the above steps.
MAY REQUIRE ADJUSTMENT
FOR LOWER PRESSURE
Fig.# 9440
HIGH LIMITS
The heater is equipped with two automatic high limits. Both are located in the inlet/outlet header. Both are set to open at 135°F.
NOTE: An erratic high limit is often characteristic of an internal heat exchanger problem, e.g. scale
HIGH LIMIT REMOVAL
5 FT.
MAY REQUIRE ADJUSTMENTMAX FOR HIGHER PRESSURE
5 FT. |
|
MAX | POOL OR SPA |
Fig.# 8152.3
NOTE: If heater is installed outside of the limits shown, a higher pressure rated (11 psi) switch may be used. A flow switch, mounted and wired adjacent to the heater, may be used in place of the
TWO-SPEED PUMPS
In some cases, the flow on the
CAUTION: Do not operate the heater without the function of a properly adjusted water pressure switch or flow switch.
1.Shut off main elec- trical power switch to heater.
2.Remove inlet/outlet inspection panel.
3.Remove defective high limit and replace with a new high limit.
4. Replace inspection | Fig.# 9439 |
| |
panel. |
|
PILOT SAFETY - Millivolt Models
Heaters equipped with the standing pilot (millivolt sys- tem) have pilot generators which act as a safety device to shut off the flow of gas to the main burners and the pilot burner in case the pilot flame is extin- guished. The pilot burner must be manually
PILOT SAFETY - Digital Models
The heater employs a pilot safety which closes the main gas valve within 8/10ths of a second whenever the pilot flame is interrupted. The pilot flame is auto- matically lit when the device is powered. The heater performs its own safety check and opens the main valve only after the pilot is proven to be lit.