LOW NOx POOL HEATERS
The Low NOx pool heaters are certified and tested under the ANSI Z21.56/CSA 4.7 Standard for Gas- Fired Pool Heaters.
The heater should be installed to meet all local codes, and the latest editions of the National Fuel Gas Code Z223.1 and the National Electrical Code, ANSI/NFPA 70.
OPERATION
On call for heat, the ignition system, consisting of an electronic spark module, gas valve and pilot system, is energized. Providing the pilot is proven, the blower will start running, the main gas valve will open and the heater will operate. When the operating control is sat- isfied the heater will shut down.
1.Turn on power to the heater with gas supply off.
2.Turn on gas supply.
3.Set controller to call for heat.
4.System should start as follows:
a.Spark will turn on, pilot gas valve will open, and the blower will begin running.
b.Once the blower provides pressure, the main gas valve will open.
c.Heater will operate until call for heat is satisfied.
NOTE: Door must be in place for proper operation.
BLOWER ADJUSTMENT
This Low NOx pool heater is equipped with a combus- tion air plate (baffle) mounted on the air intake to the combustion air blower. The baffle has a hole that is uti- lized to control the air inlet to the blower.
When the combustion air setting is proper, there will be some lifting of the flames on some areas of the burner deck under
VISUAL INSPECTION
Flames can be observed through the slot opening above the plenum. Flame color is blue and evenly spread on the top surface of the burner. At least every three months a visual inspection should be made of the burners.
ELECTRICAL
Be sure that electrical service to the heater has prop- er overload fuse or circuit breaker protection, wire size and connections which comply with all applicable codes.
FLAME ROLL-OUT SAFETY SWITCH
Low NOx heaters are equipped with (2) thermal
Manual Reset | Auto Reset |
Switch | Switch |
Fig.# 9412 | Fig.# 9439 |