Raypak 206A LOW NOx Pool Heaters, Operation, Blower Adjustment, Visual Inspection, Electrical

Page 41

LOW NOx POOL HEATERS

The Low NOx pool heaters are certified and tested under the ANSI Z21.56/CSA 4.7 Standard for Gas- Fired Pool Heaters.

The heater should be installed to meet all local codes, and the latest editions of the National Fuel Gas Code Z223.1 and the National Electrical Code, ANSI/NFPA 70.

OPERATION

On call for heat, the ignition system, consisting of an electronic spark module, gas valve and pilot system, is energized. Providing the pilot is proven, the blower will start running, the main gas valve will open and the heater will operate. When the operating control is sat- isfied the heater will shut down.

START-UP PROCEDURES

1.Turn on power to the heater with gas supply off.

2.Turn on gas supply.

3.Set controller to call for heat.

4.System should start as follows:

a.Spark will turn on, pilot gas valve will open, and the blower will begin running.

b.Once the blower provides pressure, the main gas valve will open.

c.Heater will operate until call for heat is satisfied.

NOTE: Door must be in place for proper operation.

BLOWER ADJUSTMENT

This Low NOx pool heater is equipped with a combus- tion air plate (baffle) mounted on the air intake to the combustion air blower. The baffle has a hole that is uti- lized to control the air inlet to the blower.

When the combustion air setting is proper, there will be some lifting of the flames on some areas of the burner deck under cold-start conditions. After about five min- utes of operation, the flames should settle down and blue tips should become visible. Lifting of flames beyond five minutes would indicate too much combus- tion air.

VISUAL INSPECTION

Flames can be observed through the slot opening above the plenum. Flame color is blue and evenly spread on the top surface of the burner. At least every three months a visual inspection should be made of the burners.

ELECTRICAL

Be sure that electrical service to the heater has prop- er overload fuse or circuit breaker protection, wire size and connections which comply with all applicable codes.

FLAME ROLL-OUT SAFETY SWITCH

Low NOx heaters are equipped with (2) thermal cut-off devices to prevent flame roll-out in the event the heat exchanger becomes blocked. One is a "manual reset" type roll-out switch that must be reset by a service technician after any over-temperature conditions have been fixed. The second is an “auto reset” type roll-out switch that resets itself after a few minutes. Excessive restriction in the heat exchanger flue passage may cause any of the two switchs to disable the heater.

Manual Reset

Auto Reset

Switch

Switch

Fig.# 9412

Fig.# 9439

41

Image 41
Contents What to do if YOU Smell GAS Installation and Operating InstructionsMaximum Water ChemistryContents Before START-UP Burners Water START-UP ProceduresFor Your Safety Read Before Operating Millivolt System SHUT-OFF Procedures Operating Instructions and SHUT-OFF ProceduresElectronic Ignition System Automatically Lighted PilotVisual Inspection Atmospheric Heaters Water Pressure SwitchAfter START-UP See plumbing diagram Maintenance and Care ProceduresIf Heater will not Fire Pool & SPA Water ChemistryWinterizing the Pool & SPA Heater Important Freeze InformationCold Weather Operation Receiving Equipment Part TWO Installation and Service InstructionsInstallation Instructions General SpecificationsImportant Notice Code RequirementsOutdoor Heater Installation Outdoor InstallationClearances ALL Heaters10 ft Wind Speed = 150 MPH, 3 Second Gust Exposure = C Florida Building CodeOutdoor Stack Indoor Stack Indoor Heater InstallationAtmospheric Units Specifications and DimensionsLow NOx Units Combustion and Ventilation AIR Indoor Units Only Power Vent Kit Model Part NoModel Square Inches Vent PipingGAS Supply Connections B149.1 and B149.2Pipe Sizing for GAS Connections GAS Pressure Adjustment LocationsGAS Pressure Regulator Polymer Headers Cast Iron Headers Asme Plumbing for Water ConnectionsFlow Rates Cast Iron Headers Asme Models INLET/OUTLET Header PolymerINLET/OUTLET Header Asme Unitherm Governor OperationExternal Auxiliary Bypass Valve Auxiliary Bypass Valve AdjustmentCast Iron Header Asme Models Fig. #4 Heat Exchanger Reversal Procedure Standard ModelsMillivolt Models Electrical WiringDigital Models Atmospheric240V Atmospheric Heater Transformer Wiring VAC Wiring120V Atmospheric Heater Wiring Diagram Millivolt Mechanical Thermostat Wiring Diagram Digital Models Atmospheric Wiring Diagram Digital Models LOW NOx LOW NOx Servicing InstructionsGeneral Location of Controls Atmospheric Control Panel Removal Control Adjustments Digital ModelsControl Adjustments Millivolt Models Thermostat Control Operation Digital Thermostat ControlsRESfl Reset Fault History SETdef Default SettingsProgram Button Cfff Fahrenheit to CelsiusFault Codes Diagnostics Reading a FaultStatus Codes Program Modes Display DefinitionActivating the Remote Remote Control Installation and OperationRemote Operation Wire Remote Control On-Off Remote Control WiringPilot Safety Millivolt Models Flame ROLL-OUT Safety SwitchPilot Safety Digital Models High LimitsBurner Tray Removal Pilot Removal and CleaningGAS Valve Removal Main Burner and Orifice RemovalDesooting Procedure Tube Cleaning ProcedureImmersion Well Replacement Unitherm Governor U.G. ReplacementLOW NOx Pool Heaters Blower AdjustmentOperation Visual InspectionCombustion Blower Removal Pilot RemovalMechanical TroubleshootingPage For qualified technicians only Electrical Electronic Ignition IIDYES Digital Control Logic Flow ChartEastman Avenue OXNARD, CA Replacement PartsManufacturer Atmospheric Heaters LOW NOx Heaters IID LOW NOx Pilot Call OUT Description Call OUT Description Sheetmetal Call OUT Description 267A