Raypak 407A, 406A, 206A, 337A Program Button, SETdef Default Settings, RESfl Reset Fault History

Page 34

Program Button

1)To access the program screen, press the Mode button until the display reads OFF. Remove the four screws holding the control cover on. Swing control panel down so the back side of the board is visible (see page 30). Locate the Program Mode button as shown in the figure on pg. 32. Press the program button (5-7 seconds) until SETdef appears on the digital display. Release the pro- gram button.

2)Press the Mode button sequentially until the desired program event is reached. There are 5 dif- ferent events that can be programmed. They appear in the sequence listed below:

set

Resets board to factory default settings.

 

Resets faults in the History File.

Change from Fahrenheit to Celsius.

SPA setpoint maximum adjustment.

POOL setpoint maximum adjustment.

SETdef – Default Settings

Refer to step one above to access the program screen. SETdef should appear on the screen. If not, press the Mode button until SETdef appears on the digital display. Press and hold both “UP” and “DOWN” buttons for 5-7 seconds until 3 dashes (---) appear. This operation resets the operating program to its fac- tory default values. Both the POOL and SPA setpoints will revert to 65°F (18.5°C) and both POOL and SPA maximum temperature settings will be 104°F (40.0°C). Once this is done, reassemble the control panel.

RESfl – Reset Fault History

Refer to step one above to access the program screen. Press the Mode button until RESfl appears on the digital display. Press and hold both “UP” and “DOWN” buttons for 5-7 seconds until 2 dashes (--) appear.This operation resets the Fault History file to “0” and clears all the stored faults. Once this is done, reassemble the control panel.

F/Cfff – Fahrenheit to Celsius

Refer to step one above to access the program screen. Press the Mode button until F/Cfff appears on the digital display. The digital display is capable of displaying Celsius as well as Fahrenheit temperatures. The “UP” or “DOWN” buttons will select “F” or “C” on the temperature display. Choose the desired tempera- ture scale. Once this is done, reassemble the control panel.

SETspa 104 – SPA Set Point Maximum Adjustment Refer to step one above to access the program screen. Press the Mode button until SETspa 104 appears on the digital display. Using the “UP” and “DOWN” buttons will change the Maximum Temperature Setting to your desired value. The con- trol can be set for a maximum of 107°F. Once this is done, reassemble the control panel.

SETpool 104 – POOL Set Point Maximum Adjustment Refer to step one above access into the program screen. Press the Mode button until SETpool 104 appears on the digital display. Using the “UP” and “DOWN” buttons will change the Maximum Temperature Setting to your desired value. The con- trol can be set for a maximum of 107°F. Once this is done, reassemble the control panel.

34

Image 34
Contents Installation and Operating Instructions What to do if YOU Smell GASWater Chemistry MaximumContents For Your Safety Read Before Operating START-UP ProceduresBefore START-UP Burners Water Millivolt System Electronic Ignition System Operating Instructions and SHUT-OFF ProceduresSHUT-OFF Procedures Automatically Lighted PilotAfter START-UP Water Pressure SwitchVisual Inspection Atmospheric Heaters If Heater will not Fire Maintenance and Care ProceduresSee plumbing diagram Pool & SPA Water ChemistryCold Weather Operation Important Freeze InformationWinterizing the Pool & SPA Heater Part TWO Installation and Service Instructions Receiving EquipmentImportant Notice General SpecificationsInstallation Instructions Code RequirementsClearances Outdoor InstallationOutdoor Heater Installation ALL Heaters10 ft Florida Building Code Wind Speed = 150 MPH, 3 Second Gust Exposure = CIndoor Heater Installation Outdoor Stack Indoor StackSpecifications and Dimensions Atmospheric UnitsLow NOx Units Model Square Inches Power Vent Kit Model Part NoCombustion and Ventilation AIR Indoor Units Only Vent PipingB149.1 and B149.2 GAS Supply ConnectionsGAS Pressure Regulator GAS Pressure Adjustment LocationsPipe Sizing for GAS Connections Flow Rates Plumbing for Water ConnectionsPolymer Headers Cast Iron Headers Asme INLET/OUTLET Header Asme INLET/OUTLET Header PolymerCast Iron Headers Asme Models Unitherm Governor OperationAuxiliary Bypass Valve Adjustment External Auxiliary Bypass ValveCast Iron Header Asme Models Heat Exchanger Reversal Procedure Standard Models Fig. #4Digital Models Electrical WiringMillivolt Models Atmospheric120V Atmospheric Heater Transformer Wiring VAC Wiring240V Atmospheric Heater Wiring Diagram Millivolt Mechanical Thermostat Wiring Diagram Digital Models Atmospheric Wiring Diagram Digital Models LOW NOx General Location of Controls Atmospheric Servicing InstructionsLOW NOx Control Adjustments Millivolt Models Control Adjustments Digital ModelsControl Panel Removal Digital Thermostat Controls Thermostat Control OperationProgram Button SETdef Default SettingsRESfl Reset Fault History Cfff Fahrenheit to CelsiusStatus Codes Program Modes Diagnostics Reading a FaultFault Codes Display DefinitionRemote Operation Remote Control Installation and OperationActivating the Remote Remote Control Wiring Wire Remote Control On-OffPilot Safety Digital Models Flame ROLL-OUT Safety SwitchPilot Safety Millivolt Models High LimitsGAS Valve Removal Pilot Removal and CleaningBurner Tray Removal Main Burner and Orifice RemovalImmersion Well Replacement Tube Cleaning ProcedureDesooting Procedure Unitherm Governor U.G. ReplacementOperation Blower AdjustmentLOW NOx Pool Heaters Visual InspectionPilot Removal Combustion Blower RemovalTroubleshooting MechanicalPage Electrical Electronic Ignition IID For qualified technicians onlyDigital Control Logic Flow Chart YESManufacturer Replacement PartsEastman Avenue OXNARD, CA Atmospheric Heaters LOW NOx Heaters IID LOW NOx Pilot Call OUT Description Call OUT Description Sheetmetal Call OUT Description 267A