Section 2 – Installation
◆2.6.6 SENSING HARNESS
A sensing harness has been provided with the gener- ator to connect to the inverter (Figure 2.22). It is 12 feet long, however, it is also available in a 24 foot length: Model #
DO NOT in any way cut or shorten the
!sensing harness. If the harness is too long, simply tie the excess up neatly with standard cable ties.
2.7BATTERY INSTALLATION
◆2.7.1 RECOMMENDED BATTERY
Install a battery that meets the following require- ments:
•Battery must be a 12 volt, automotive type storage battery.
•For prevailing ambient temperatures above 32°F (0°C), use a battery rated 70
•For prevailing ambient temperatures below 32°F (0°C), use a battery rated 95
IMPORTANT: IF THE BATTERY IS TO BE USED TO POWER OTHER VEHICLE ACCESSORIES, AS WELL AS START THE GENERATOR, A BATTERY WITH A LARGER CAPACITY MAY BE NEEDED.
◆2.7.2 BATTERY CABLES
Using battery cables that are too long or too small in diameter may cause a drop in voltage which causes starting problems. For best cold weather starting, the voltage drop between battery terminals and the gen- erator connection point should not exceed 0.12 volts per 100 amperes of cranking current.
Select battery cables based on (a) cable length, and
(b)prevailing ambient temperatures. Generally, the longer the cable and the colder the weather, the larg- er the cable size must be as shown in the following chart.
Figure 2.22 — Generator to Inverter Connection
RED
BLACK
BLUE
GREEN
TO INVERTER INPUT
Generac® Power Systems, Inc. 31