Briggs & Stratton Liquid-Cooled Home Generator System system manual Engine Coolant System, Battery

Page 17

Engine Coolant System

With the engine cold, check the coolant level in the coolant reservoir, seen inside the Control Panel door. Maintenance instructions for engine coolant are found in the engine operator’s manual.

Battery

Charging the Battery

If it is necessary to charge the battery, proceed as follows:

1.Set generator’s system switch to OFF.

2.Remove 15 Amp fuse from control panel.

3.Disconnect negative battery cable to negative battery terminal (indicated by NEGATIVE, NEG, or (-).

notice

Failure to disconnect negative battery cable will result in equipment failure.

DO NOT attempt to jump start the battery.

Damage to equipment resulting from failure to follow this instruction will void warranty.

4.Charge battery with battery charger at 2 Amps until battery holds 12 Volts.

warning

Storage batteries give off explosive hydrogen gas during recharging.

Slightest spark will ignite hydrogen and cause explosion.

Battery electrolyte fluid contains acid and is extremely caustic.

Contact with battery contents will cause severe chemical burns.

A battery presents a risk of electrical shock and high short circuit current.

DO NOT dispose of battery in a fire.

DO NOT allow any open flame, spark, heat, or lit cigarette during and for several minutes after charging a battery.

DO NOT open or mutilate the battery.

Wear protective goggles, rubber apron, and rubber gloves.

Remove watches, rings, or other metal objects.

Use tools with insulated handles.

NOTE: With the battery installed and utility power available to the transfer switch, the battery receives a trickle charge whenever the engine is not running. It may take up to

72 hours to fully charge a discharged battery with the trickle charge. The trickle charge is not able to recharge a battery that is completely discharged.

5.Connect negative battery cable to negative battery terminal (indicated by NEGATIVE, NEG, or (-)).

6.Ensure hardware on both positive and negative battery terminals is secure.

7.Reinstall 15 Amp fuse in control panel.

caution

Installing the control panel’s 15A fuse could cause the engine to start.

DO NOT install this fuse until all plumbing and wiring has been completed and inspected.

8.Set generator’s system switch to AUTO.

9.Reset exercise timer. See Setting Exercise Timer.

Servicing the Battery

If it is necessary to service the battery, proceed as follows:

1.Set control board System switch to OFF.

2.Remove 15 Amp fuse from control panel.

3.Service or replace battery as required.

4.Connect red battery cable to battery positive terminal (indicated by POSITIVE, POS, or (+)).

5.Connect negative battery cable to negative battery terminal (indicated by NEGATIVE, NEG, or (-).

6.Ensure hardware on both positive and negative battery terminals is secure.

7.Reinstall 15 Amp fuse in control panel.

8.Set generator’s system switch to AUTO.

9.Reset exercise timer. See Setting Exercise Timer.

To Clean the Generator

notice

Improper treatment of generator can damage it and shorten its life.

DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.

DO NOT insert any objects through cooling slots.

Use a damp cloth to wipe exterior surfaces clean.

Use a soft, bristle brush to loosen caked on dirt, oil, etc.

Use a vacuum cleaner to pick up loose dirt and debris.

Use low pressure air (not to exceed 25 psi) to blow away dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.

17

Image 17
Contents Liquid-Cooled Home Generator System Where to Find Us Table of Contents Hazard Symbols and Meanings Safety RulesPage See Essential Circuits For the Installing Dealer/Contractor InstallationFor the Home Owner Owner OrientationEssential Circuits Generator LocationDelivery Inspection To be supplied by InstallerEssential Circuit Selection Home generator system is supplied withHome Generator Features and ControlsControl Panel Door opening Provides access to control panel System Control Panel To Close an Access Door Access DoorsTo Open an Access Door Automatic Operation OperationImportant Owner’s Considerations Setting Exercise Timer MaintenanceFault Detection System Servicing the SystemLow Battery Voltage FC1 No LED Discharged BatteryLow Oil Pressure FC2 Low Voltage Generator, FC3Engine Oil Generator MaintenanceEngine Maintenance Charging the Battery BatteryServicing the Battery To Clean the GeneratorStorage When Calling the FactoryProblem Cause Correction TroubleshootingDown when loads are connected AvailableWarranty terms continue on next Other Exclusions 30 kW 45 kW Product SpecificationsManual del Operario Dónde encontrarnos Instrucciones importantes de seguridad Instalación Problemas Garantía Especificaciones del productoControles y características Operación MantenimientoSímbolos de Peligro y Significados Conserve estas instruccionesAdvertencia Precaución Para el Propietario Doméstico InstalaciónOrientación para el propietario Factores Relacionados con el CombustibleDistancias Desde el Generador Ubicación del GeneradorCircuitos Fundamentales Selección de los Circuitos Fundamentales Dispositivo Vatiaje deEl Generador Doméstico incluye lo siguiente Inspección al Momento de la EntregaGenerador Doméstico Controles y característicasAjustes. Conserve este manual para referencias futuras Abertura de la Puerta de llenado de RefrigerantePanel de control del sistema Para cerrar una puerta de acceso Puertas de AccesoPara abrir una puerta de acceso Verificación de la Operación Automática OperaciónFuncionamiento Automático Mantenimiento Configuración del Temporizador de PrácticaParo del Sistema Sistema de Detección de FallasBaja Tensión de la Batería FC1 No se Enciende el LED Batería DescargadaBaja Presión de Aceite FC2 Baja Tensión FC3Aceite del Motor Mantenimiento del GeneradorMantenimiento del Motor Cargar la Batería Sistema refrigerante del motorBatería Almacenamiento Si Llama a la FábricaServicio la Batería Para Limpiar el GeneradorProblemas Causa Corrección ProblemasGarantía Limitada Garantía Limitada Español Especificaciones del producto Sistema generador domésticoGroupe électrogène Refroidissement par liquide Où nous trouver Fonctions et commandes Fonctionnement Directives de sécurité importantes InstallationEntreiten Dépannage Garantie Caractéristiques du produitVeuillez conserver ces instructions Symboles de Danger et MoyensDirectives de sécurité importantes SécuritéAvertissement Avis Facteurs Relatifs au Combustible Au Propriétaire RésidentielConseils au propriétaire Dégagement Autour de la Génératrice Emplacement de la GénératriceCircuits Essentiels Sélection des Circuits Essentiels Le Groupe électrogène est livré avec les éléments suivants Vérification de la LivraisonArticles non fournis Outils/équipements spécialisés nécessairesEntretien Dépannage Garantie Fonctions et commandesSécurité Instalación Tableau de commande de systèmeCommandes Fonctionnement Entretien Dépannage Garantie Pour fermer une porte d’accès Portes d’AccèsPour ouvrir une porte d’accès Vérification du Fonctionnement Automatique FonctionnementFonctionnement automatique Réglage de la Minuterie du Cycle d’Exercice EntreitenArrêt du Système Système de Détection des PannesFaible Tension de la Batterie FC1 Aucun DEL Batterie déchargéeFaible Pression d’Huile FC2 Basse Tension FC3’Huile Moteur Entretien du GénérateurEntretien du moteur Batterie Système de refroidissement du moteurPour Nettoyer le Générateur Rechargez la BatterieDépannage Problème Cause SolutionCommunications avec le Fabricant RemisageGarantie Limitée Sécurité Instalación CommandesFrançais Caractéristiques du produit Groupe électrogène