Briggs & Stratton Liquid-Cooled Home Generator System system manual Delivery Inspection

Page 9

Essential Circuit Selection

When selecting the essential circuits that will be switched to “Standby Power,” it is important that the sum of the combined circuit loads does not exceed the wattage/ amperage capacity of the generator. To help you with your selection of essential circuits, please consider the following:

Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the generator’s wattage capacity.

The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.

If the appliance, tool or motor nameplate does not list wattage, multiply volts times the ampere rating to determine watts (Volts x Amps = Watts).

Some electric motors (induction types) require about three times more watts of power for starting than for running. This surge lasts for only a few seconds. Be sure you allow for this high starting wattage when selecting electrical devices that will be energized by the home generator:

Figure the watts required to start the largest motor.

Add that to the total running watts of all other connected loads.

This Briggs & Stratton home generator complies with the following “stationary standby power rating”:

The standby power rating is applicable for supplying power for the duration of normal power interruption. No sustained overload capability is available for this rating.

This rating is applicable to installations served by a reliable normal utility source. This rating is only applicable to variable loads with an average load factor of 80% of the standby rating. The standby rating is only applicable for optional standby power where the generator set serves as the backup to the normal utility source.

Use the wattage reference table provided and mark those circuits you consider “critical” or “essential”. Make sure you and your installer consider the system’s altitude above sea level and the ambient temperature range when determining total generator load.

In a utility outage, you need to ‘manage’ power distribution by turning off non-essential loads. Some examples of non essential loads are as follows:

Pool pump

Hot tub

Electric hot tub and/or pool heaters

Central air conditioners

Electric hot water heaters

Electric range and/or oven

Arc welder

Non essential electric heaters

Delivery Inspection

Carefully inspect the home generator for any damage that may have occurred during shipment.

IMPORTANT: If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor’s memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier and your installer for claim procedures. Missing or damaged parts are not warranted.

The home generator system is supplied with:

Home generator

Fully-serviced coolant system

Fully-serviced oil/lubricating system

UL569/CSA8.3-listed flexible fuel hook-up

Installation and start-up manual

Operator’s manual

Engine operator’s manual

Installation checklist

Two access door keys

One spare 15A fuse

10 Pole control panel connector

Remote LED indicator kit (red LED/plate/screws)

To be supplied by Installer:

650 CCA 55 amp-hour starting battery

Connecting wire and conduit

Fuel supply valves/plumbing

Various specialty tools/equipment

Image 9
Contents Liquid-Cooled Home Generator System Where to Find Us Table of Contents Hazard Symbols and Meanings Safety RulesPage See Essential Circuits For the Installing Dealer/Contractor InstallationFor the Home Owner Owner OrientationEssential Circuits Generator LocationDelivery Inspection To be supplied by InstallerEssential Circuit Selection Home generator system is supplied withFeatures and Controls Control Panel Door opening Provides access to control panelHome Generator System Control Panel Access Doors To Open an Access DoorTo Close an Access Door Operation Important Owner’s ConsiderationsAutomatic Operation Setting Exercise Timer MaintenanceFault Detection System Servicing the SystemLow Battery Voltage FC1 No LED Discharged BatteryLow Oil Pressure FC2 Low Voltage Generator, FC3Generator Maintenance Engine MaintenanceEngine Oil Charging the Battery BatteryServicing the Battery To Clean the GeneratorStorage When Calling the FactoryProblem Cause Correction TroubleshootingDown when loads are connected AvailableWarranty terms continue on next Other Exclusions 30 kW 45 kW Product SpecificationsManual del Operario Dónde encontrarnos Instrucciones importantes de seguridad Instalación Problemas Garantía Especificaciones del productoControles y características Operación MantenimientoSímbolos de Peligro y Significados Conserve estas instruccionesAdvertencia Precaución Para el Propietario Doméstico InstalaciónOrientación para el propietario Factores Relacionados con el CombustibleUbicación del Generador Circuitos FundamentalesDistancias Desde el Generador Selección de los Circuitos Fundamentales Dispositivo Vatiaje deEl Generador Doméstico incluye lo siguiente Inspección al Momento de la EntregaGenerador Doméstico Controles y característicasAjustes. Conserve este manual para referencias futuras Abertura de la Puerta de llenado de RefrigerantePanel de control del sistema Puertas de Acceso Para abrir una puerta de accesoPara cerrar una puerta de acceso Operación Funcionamiento AutomáticoVerificación de la Operación Automática Mantenimiento Configuración del Temporizador de PrácticaParo del Sistema Sistema de Detección de FallasBaja Tensión de la Batería FC1 No se Enciende el LED Batería DescargadaBaja Presión de Aceite FC2 Baja Tensión FC3Mantenimiento del Generador Mantenimiento del MotorAceite del Motor Sistema refrigerante del motor BateríaCargar la Batería Almacenamiento Si Llama a la FábricaServicio la Batería Para Limpiar el GeneradorProblemas Causa Corrección ProblemasGarantía Limitada Garantía Limitada Español Especificaciones del producto Sistema generador domésticoGroupe électrogène Refroidissement par liquide Où nous trouver Fonctions et commandes Fonctionnement Directives de sécurité importantes InstallationEntreiten Dépannage Garantie Caractéristiques du produitVeuillez conserver ces instructions Symboles de Danger et MoyensDirectives de sécurité importantes SécuritéAvertissement Avis Au Propriétaire Résidentiel Conseils au propriétaireFacteurs Relatifs au Combustible Emplacement de la Génératrice Circuits EssentielsDégagement Autour de la Génératrice Sélection des Circuits Essentiels Le Groupe électrogène est livré avec les éléments suivants Vérification de la LivraisonArticles non fournis Outils/équipements spécialisés nécessairesEntretien Dépannage Garantie Fonctions et commandesTableau de commande de système Commandes Fonctionnement Entretien Dépannage GarantieSécurité Instalación Portes d’Accès Pour ouvrir une porte d’accèsPour fermer une porte d’accès Fonctionnement Fonctionnement automatiqueVérification du Fonctionnement Automatique Réglage de la Minuterie du Cycle d’Exercice EntreitenArrêt du Système Système de Détection des PannesFaible Tension de la Batterie FC1 Aucun DEL Batterie déchargéeFaible Pression d’Huile FC2 Basse Tension FC3Entretien du Générateur Entretien du moteur’Huile Moteur Batterie Système de refroidissement du moteurPour Nettoyer le Générateur Rechargez la BatterieDépannage Problème Cause SolutionCommunications avec le Fabricant RemisageGarantie Limitée Sécurité Instalación CommandesFrançais Caractéristiques du produit Groupe électrogène