Troubleshooting
Problem |
| Cause |
| Correction | |
|
|
|
|
| |
Engine is running, but no AC output is | 1. | Circuit breaker open or defective. | 1. | Reset or replace circuit breaker. | |
2. | Fault in generator control panel. | 2. | Contact local service facility. | ||
available. | 3. | Poor wiring connections or | 3. | Check and repair. | |
|
| defective transfer switch. |
|
| |
|
|
|
|
| |
| 1. | Short circuit in a connected load. | 1. | Disconnect shorted electrical load. | |
Engine runs good at | 2. | Generator is overloaded. | 2. | See Essential Circuits. | |
3. | Shorted generator circuit. | 3. | Contact local service facility. | ||
down” when loads are connected. | 4. | Fuel pressure or mixture is | 4. | See Gaseous Fuel System in the | |
|
| incorrect. |
| Installation Manual. | |
| 5. | Kinked fuel line. | 5. | Remove kink. Replace if necessary. | |
|
|
|
|
| |
| 1. | 15 Amp fuse missing or blown. | 1. | Install (new) 15 Amp fuse. See | |
|
|
|
| System Control Panel. | |
Engine will not start; or starts and runs | 2. | Fuel supply turned off or depleted. | 2. | Open fuel valve(s); check propane | |
rough. |
|
|
| tank. | |
3. | Failed battery. | 3. | Replace battery. | ||
| |||||
| 4. | Fuel pressure is incorrect | 4. | See Gaseous Fuel System in the | |
|
|
|
| Installation Manual. | |
Engine shuts down during operation. | 1. | Fuel supply turned off or depleted. | 1. | Check fuel valves, fill propane tank. | |
2. | Fault indicator blinking. | 2. | Count blinks and refer to Fault | ||
|
|
|
| Detection System. | |
|
|
|
|
| |
Loss of power on essential circuits. | 1. | Generator circuit breaker is open. | 1. | Reset circuit breaker. | |
2. | Transfer switch problems. | 2. | See the transfer switch manual. | ||
| |||||
|
|
|
|
|
19