Hitachi SJ2-CO instruction manual Status word Index 6041h

Page 19

CHAPTER5 CANOPEN COMMUNICATION FUNCTION

5.1.7 Status word (Index: 6041h)

The status word indicates the current state of the inverter.

 

 

 

 

 

Bit

Description

 

 

 

 

 

 

 

Note

 

0

Ready to switch on

 

 

 

 

 

 

Mandatory

 

1

Switched on

 

 

 

 

 

 

 

Mandatory

 

2

Operation enabled

 

 

 

 

 

 

Mandatory

 

3

Fault

 

 

 

 

 

 

 

Mandatory

 

4

Voltage enabled

 

 

(~V1.04) Voltage disable -> enabled

 

Mandatory

 

5

Quick stop

 

 

 

 

 

 

 

Mandatory

 

6

Switch on disabled

 

 

 

 

 

 

Mandatory

 

7

Warning

 

 

 

 

 

 

 

Unsupported

 

8

Manufacturer Specific

 

 

 

 

 

 

Unsupported

 

9

Remote

 

 

 

 

 

 

 

Mandatory

 

10

Target reached

 

 

 

 

 

 

 

Mandatory

 

11

Internal Limit Active

 

“Index 6046” influences this bit.

 

Mandatory

 

12

(reserved)

 

 

(reserved)

 

 

 

Mode Specific

 

13

(reserved)

 

 

(reserved)

 

 

 

Mode Specific

 

14

Moving forwards

 

 

 

 

 

 

 

 

 

 

15

Moving backwards

 

 

 

 

 

 

 

 

Bitmapping of Status word

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 6

 

Bit 5

 

Bit 3

Bit 2

Bit 1

 

Bit 0

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch On

 

Quick

 

Fault

Operation

Switch On

 

Ready to

 

 

 

 

 

 

 

 

 

 

 

Disable

 

Stop

 

Enable

 

Switch On

 

 

 

 

 

 

 

 

 

 

Not Ready to

 

0

 

X

 

0

0

0

 

0

 

Switch On

 

 

 

 

 

 

 

 

 

 

 

 

Switch On

 

1

 

X

 

0

0

0

 

0

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

Ready to

 

0

 

1

 

 

0

0

0

 

1

 

Switch On

 

 

 

 

 

 

 

 

 

 

 

 

Switched On

 

0

 

1

 

 

0

0

1

 

1

 

Operation Enabled

 

0

 

1

 

 

0

1

1

 

1

 

Fault

 

0

 

X

 

1

1

1

 

1

 

Fault Reaction

 

0

 

X

 

1

1

1

 

1

 

Active

 

 

 

 

 

 

 

 

 

 

 

 

Quick Stop

 

0

 

0

 

 

0

1

1

 

1

 

‘X’ means that any value is allowed.

15

Image 19
Contents Hitachi Inverter Revision History Table Safty Precautions Otherwise, there is a danger of electric shock and/or injury Request upon inquiring Warranty of the productAppearance of SJ2-CO Appearance and Names of PartsCANopen Support Version Specifications LabelLED display Mounting method of option Installation of SJ2-CO SJ200-2 + SJ2-COSJ2-MF SJ2-CCV Communication cable for CANopen Connection for CANopen connectorPLC Wiring noteSetting method of CANopen Baud rate Setting methods of Baud rate and Node IDSetting method of CANopen Node Power Supply LED check Parameter setting of the InverterCanopen Communication Function PDOProcess Data Object Object Dictionary for Standardized Device Profile Area Device ControlAbortconnectionoptioncode Index 6007h Control word Index 6040h Status word Index 6041h State Machine PowerRFG Using RFGRamp Function GeneratorVlvelocityminmaxamount Index 6046h Vltargetvelocity Index 6042hVlvelocitydemand Index 6043h Vlvelocityeffort Index 6044hVlvelocitydeceleration Index 6049h Vlvelocityacceleration Index 6048hKeypad displayOPTIONAL OPERATOROPE-SRMINI Modesofoperation Index 6060h/6061hProtection function list Trip displayCountermeasure for a trip state LED LED display and CountermeasureDevice Profile Area Communication ObjectsIndex Profile Manufacyure Objects d,F groupProfile Manufacture Objects A,b,C,H,P group Parameter Communication Objects Lists Communication Objects Lists Saving Parameters to Eeprom Dimension Contact Information