CHAPTER6 COUNTERMEASURE FOR ABNORMALITY

6.1 Trip display

When the inverter is in a tripped state, the inverter displays an error code (See table below). The trip history monitor (d081 to d086) also displays the same error code as the inverter.

Trip

6.2 Protection function list

The table below describes an error code for protecting the inverter and the motor.

No.

Function

Error

Action

 

 

Display

 

1

Network option’s

E70

This error is displayed, disconnection occurs when timeout is

 

communication error

 

occurred, while the inverter is operating with CANopen. (Trip

 

 

 

is caused by P045 setting)

2

External trip

E12

This error is displayed, when Halt is set to 1 toward control

 

 

 

word(Index:6040h) in BIT8(Halt).

With regard to the other errors except table above, refer to Inverter instruction manual chapter 4 Explanation of function.

6.3 Countermeasure for a trip state

The table below only corresponds to additional trip codes, with regard to the other countermeasures refer to Inverter instruction manual chapter 4 Explanation of function.

Trip code

Name of trip

Cause

Conformation

Countermeasure

E70

CANopen

Baud

 

rate

is

Check Baud

Install correct Baud rate and

 

Communication

different.

 

 

rate

then reset the power supply.

 

error

Wiring distance does

Check the wiring

Adjust the setting to the

 

 

 

 

not match with Baud

distance

matching Baud rate.

 

 

rate

 

 

 

 

Adjust Wiring distance.

 

 

Defective

connector

Check the area of

Improve the connection and

 

 

for

signal

cable

connection.

then reset the power supply.

 

 

causes

connection

 

 

 

 

fail.

 

 

 

 

 

 

 

Terminating resistor

Check the

Connect the terminating

 

 

is not connected.

Connection

Resistor and then reset the

 

 

 

 

 

 

 

power supply

 

 

 

 

 

 

 

E12

External

Control

 

 

Check as mentioned

Set Halt to 0 toward Control

 

Trip

word(Index:6040h)

left.

word(Index:6040h)Bit8(Halt).

 

 

Bit8:Halt

 

 

 

 

 

 

 

 

 

 

 

 

21

Image 25
Contents Hitachi Inverter Revision History Table Safty Precautions Otherwise, there is a danger of electric shock and/or injury Request upon inquiring Warranty of the productAppearance of SJ2-CO Appearance and Names of PartsCANopen Support Version Specifications LabelLED display Mounting method of option Installation of SJ2-CO SJ200-2 + SJ2-COSJ2-MF SJ2-CCV Communication cable for CANopen Connection for CANopen connectorPLC Wiring noteSetting method of CANopen Baud rate Setting methods of Baud rate and Node IDSetting method of CANopen Node Power Supply LED check Parameter setting of the InverterCanopen Communication Function PDOProcess Data Object Object Dictionary for Standardized Device Profile Area Device ControlAbortconnectionoptioncode Index 6007h Control word Index 6040h Status word Index 6041h State Machine PowerRFG Using RFGRamp Function GeneratorVlvelocitydemand Index 6043h Vltargetvelocity Index 6042hVlvelocityeffort Index 6044h Vlvelocityminmaxamount Index 6046hVlvelocitydeceleration Index 6049h Vlvelocityacceleration Index 6048hKeypad displayOPTIONAL OPERATOROPE-SRMINI Modesofoperation Index 6060h/6061hProtection function list Trip displayCountermeasure for a trip state LED LED display and CountermeasureDevice Profile Area Communication ObjectsIndex Profile Manufacyure Objects d,F groupProfile Manufacture Objects A,b,C,H,P group Parameter Communication Objects Lists Communication Objects Lists Saving Parameters to Eeprom Dimension Contact Information