5.3.1Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.

PD2-CE6HDWRMBS fits the 5000 and 6000VA models of the Liebert GXT3

PD2-CE10HDWRMBS fits the 10,000VA model of the Liebert GXT3

The installer must provide an upstream branch circuit breaker. The input circuit breaker on the distribution box and the output circuit breaker on the rear of the power distribution box disconnect all power between the main cabinet and the distribution box.

Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the input terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass breaker.

Table 1 Branch circuit breaker ratings

Unit Rating

Maximum Breaker Rating

5000VA

D Type 32A

6000VA

D Type 32A

10,000VA

D Type 63A

Figure 11 Distribution box electrical connections diagram

Mains Input

External

Branch CB

PD2-CE6HDWRMBS and

PD2-CE10HDWRMBS

MB CB

Output

 

Input

Output

 

CB

CB

 

 

 

UPS-PFC, Battery Inverter

Terminal Block Connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS

Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit. Emerson® recommends using strain relief when installing the wire.

Table 2 Electrical specifications

 

Recommended

Recommended Wire

Maximum Wire

Terminal

 

(Maximum) External

(Including ground wire)

Accepted by

Tightening

UPS Model

Overcurrent Protection

(75°C copper wire)

Terminal Block

Torque

GXT3-5000RT230

32A

4mm2 (10AWG)

6mm2 (8AWG)

2.26 Nm (20 in-lb)

GXT3-6000RT230

 

 

 

GXT3-10000RT230

63A

10mm2 (6AWG)

16mm2 (4AWG)

 

17

Liebert® GXT3

Image 23
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Specifications MaintenanceTroubleshooting Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDynamic Bypass BatteryDC-to-DC Converter Major Components Main Frame and ElectronicsLiebert GXT3, 5,000 & 6000VA Terminal Block Communication C19 Output PowerRemovable Power Distribution Box Internal Battery PacksWHAT’S Included Connectors Spacers Support Bases Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately Operation and Display Panel Rotated Clockwise 90 DegreesRetaining latch UPS or battery813mm DepthSlide into the bracket assemblies more easily External Battery Cabinet InstallationExternal battery cabinets connected to 10,000VA Liebert GXT3 Extract These Captive screws Maintenance Bypass Breaker Connect Input/Output PowerUnit Rating Maximum Breaker Rating Electrical specificationsDistribution Box Electrical Connections Branch circuit breaker ratingsOutput Input What You Will Need Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberUPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Put the Liebert GXT3 in Manual Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Maintenance BypassRemove Screws IT Power System ConfigurationConnectors Communication Any Mode ShutdownCommunication Interface Port Terminal Block CommunicationLiebert IntelliSlot Communication Cards Battery Mode ShutdownOn Battery Low BatteryLiebert MultiLink Remote Emergency Power OffRepo switch connection diagram 6000VA model shown Replacing the Internal Battery PackMaintenance Battery Replacement Procedures5000 & 6000 VA models Battery ChargingPrecautions Checking UPS Functions Checking UPS StatusIndicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsCondition Alarm Audible AlarmAudible alarm description Troubleshooting tableYour UPS has received a signal or command from UPS specifications SpecificationsPower distribution specifications Operating temperature parametersSee Table External battery cabinet specificationsBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Care Ne tIs t Twor k