Emerson 230V Startup Checklist for the Liebert GXT3, Initial Startup and Electrical Checks

Page 29

Operation

8.0OPERATION

This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting the mains power from the UPS.

NOTE

The Liebert GXT3’s battery has been fully charged before delivery, but some charge will be lost during storage and shipping. To ensure that the battery has adequate reserve power to protect the connected load, charge the battery for three hours before putting the UPS into service.

8.1Startup Checklist for the Liebert GXT3

Before starting the UPS, perform these checks:

___ 1. Check that the input plugs and loads are connected properly and reliably.

___ 2. Check that the battery cable is connected properly.

___ 3. Check that the communication cables are connected properly.

8.2Initial Startup and Electrical Checks

1.Verify that the Input Output circuit breakers are off.

2.During initial system checks, disconnect all loads (open load disconnects).

3.Inspect all wiring, cables and connection.

4.If external battery cabinets are used, verify that the battery interconnect cables are fully inserted in the sockets.

5.Place the manual bypass breaker in BYPASS position.

6.Turn on the branch circuit disconnect to apply voltage to the input terminal block.

7.Using a voltmeter, verify the expected L1-N voltage.

Verify that the same voltages appear at the Output terminals. The Bypass lamp by the switch will light.

8.After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power, close all access panels to the distribution box and reapply input power.

9.Close the Input circuit breaker located on the distribution box. The green AC INPUT lamp should illuminate on the front panel.

10.Press the ON button for four seconds. After several seconds, the UPS ON lamp will turn on continuously. If the batteries are determined to be charged above 80%, an automatic battery test will run for about 15 seconds.

11.Close the Output circuit breaker on the rear of the power distribution box. The light by the input breaker will illuminate.

12.Return the manual breaker to the Inverter position. The output terminal block will be powered at this time.

13.Connect all loads for normal operation.

23

Liebert® GXT3

Image 29
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Specifications MaintenanceTroubleshooting Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionDynamic Bypass BatteryDC-to-DC Converter Major Components Main Frame and ElectronicsLiebert GXT3, 5,000 & 6000VA Terminal Block Communication C19 Output PowerRemovable Power Distribution Box Internal Battery PacksWHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Connectors Spacers Support BasesInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationOperation and Display Panel Rotated Clockwise 90 Degrees Quantity813mm UPS or batteryDepth Retaining latchSlide into the bracket assemblies more easily External Battery Cabinet InstallationExternal battery cabinets connected to 10,000VA Liebert GXT3 Extract These Captive screws Maintenance Bypass Breaker Connect Input/Output PowerDistribution Box Electrical Connections Electrical specificationsBranch circuit breaker ratings Unit Rating Maximum Breaker RatingOutput Input What You Will Need Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberUPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Disconnecting Input Power from the Liebert GXT3 Manual Battery TestMaintenance Bypass Put the Liebert GXT3 in Manual BypassRemove Screws IT Power System ConfigurationConnectors Communication Interface Port Any Mode ShutdownTerminal Block Communication CommunicationOn Battery Battery Mode ShutdownLow Battery Liebert IntelliSlot Communication CardsLiebert MultiLink Remote Emergency Power OffRepo switch connection diagram Maintenance Replacing the Internal Battery PackBattery Replacement Procedures 6000VA model shown5000 & 6000 VA models Battery ChargingPrecautions Checking UPS Functions Checking UPS StatusTroubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmTroubleshooting table Condition AlarmYour UPS has received a signal or command from UPS specifications SpecificationsPower distribution specifications Operating temperature parametersSee Table External battery cabinet specificationsBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Is t Ne tTwor k Care