Emerson 230V, 000-VA UPS Symptoms, Troubleshooting, Indicators, Indicator Diagnosis/Audible alarm

Page 38

Troubleshooting

11.0TROUBLESHOOTING

This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.

11.1UPS Symptoms

The following symptoms indicate the Liebert GXT3 is malfunctioning:

The relative indicators illuminate, indicating the UPS has detected a problem.

An alarm buzzer sounds, alerting the user that the UPS requires attention.

11.1.1Indicators

In addition to the fault indicator being illuminated, one or more of LED segments of battery level indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 20. The descriptions are listed in Table 4.

Figure 20 Battery level indicator

 

 

 

 

 

 

 

 

 

 

 

 

A

B

C

D

E

 

Table 4

Indicator descriptions

 

 

 

 

 

 

 

 

 

 

 

 

Indicator

 

Diagnosis/Audible alarm

 

 

 

 

 

 

 

 

 

 

A - E

 

 

On bypass from output overload (half-second beep every half second)

 

 

 

 

 

 

A

 

 

On bypass due to overtemperature condition (1-second beep every 4 seconds)

 

 

 

 

 

 

B

 

 

On bypass due to DC bus overvoltage (1-second beep every 4 seconds)

 

 

 

 

 

 

C

 

 

On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)

 

 

 

 

 

 

 

D

 

 

PFC failure (1-second beep every 4 seconds).

 

 

 

 

 

 

 

 

 

E

 

 

On bypass due to inverter failure (1-second beep every 4 seconds)

 

 

 

 

 

 

A&C

 

 

UPS failed battery test (2-second beep every 60 seconds)

 

 

 

 

 

 

C&E

 

 

UPS shutdown by command from communication (USB port or Liebert IntelliSlot® port) (no

 

 

audible)

 

 

 

 

 

 

 

 

 

 

 

 

 

A&B

 

 

UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery

 

 

charger failure) and continuous alarm

 

 

 

 

 

 

 

 

 

Battery Indicator

 

Internal Battery source not available (continuous horn); check battery connection, power down

Flashing

 

 

and reboot UPS.

 

 

 

 

 

Bypass Indicator

 

Mains power voltage or frequency is out of tolerance; bypass is unavailable

Flashing

 

 

 

 

 

 

 

 

 

 

A - E indicators are shown in Figure 20

 

 

 

 

 

Liebert® GXT3

32

Image 38
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Specifications MaintenanceTroubleshooting Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionDynamic Bypass BatteryDC-to-DC Converter Main Frame and Electronics Major ComponentsC19 Output Power Liebert GXT3, 5,000 & 6000VA Terminal Block CommunicationInternal Battery Packs Removable Power Distribution BoxWHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchExternal Battery Cabinet Installation Slide into the bracket assemblies more easilyExternal battery cabinets connected to 10,000VA Liebert GXT3 Connect Input/Output Power Extract These Captive screws Maintenance Bypass BreakerBranch circuit breaker ratings Electrical specificationsDistribution Box Electrical Connections Unit Rating Maximum Breaker RatingOutput Input What You Will Need Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassRemove Screws IT Power System ConfigurationConnectors Terminal Block Communication Any Mode ShutdownCommunication Interface Port CommunicationLow Battery Battery Mode ShutdownOn Battery Liebert IntelliSlot Communication CardsLiebert MultiLink Remote Emergency Power OffRepo switch connection diagram Battery Replacement Procedures Replacing the Internal Battery PackMaintenance 6000VA model shown5000 & 6000 VA models Battery ChargingPrecautions Checking UPS Status Checking UPS FunctionsIndicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmTroubleshooting table Audible AlarmAudible alarm description Condition AlarmYour UPS has received a signal or command from Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications See TableBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Twor k Ne tIs t Care