Installation and Configuration

Figure 12 Terminal block connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS

PD2-CE6HDWRMBS

PD2-CE10HDWRMBS

L N

L N

OUTPUT

INPUT

NOTE

L N

L N

INPUT

OUTPUT

The installer must provide circuit breaker protection according to local codes. The mains disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.

The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.

Liebert® GXT3

18

Image 24
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Maintenance TroubleshootingSpecifications Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsC19 Output Power Liebert GXT3, 5,000 & 6000VA Terminal Block CommunicationInternal Battery Packs Removable Power Distribution BoxWHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchExternal Battery Cabinet Installation Slide into the bracket assemblies more easilyExternal battery cabinets connected to 10,000VA Liebert GXT3 Connect Input/Output Power Extract These Captive screws Maintenance Bypass BreakerElectrical specifications Distribution Box Electrical ConnectionsBranch circuit breaker ratings Unit Rating Maximum Breaker RatingOutput Input Configuration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassIT Power System Configuration ConnectorsRemove Screws Any Mode Shutdown Communication Interface PortTerminal Block Communication CommunicationBattery Mode Shutdown On BatteryLow Battery Liebert IntelliSlot Communication CardsRemote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures 6000VA model shownBattery Charging Precautions5000 & 6000 VA models Checking UPS Status Checking UPS FunctionsUPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionTroubleshooting table Condition AlarmYour UPS has received a signal or command from Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications See TableBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Ne t Is tTwor k Care