Operation

8.3Manual Battery Test

To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while operating from mains power with no alarm conditions present.

If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries for 24 hours.

Retest the batteries after 24 hours of charging.

After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact your local Emerson® representative or Emerson Network Power Channel Support.

If none of the five Battery LEDs illuminate during a manual battery test, check the battery connection and allow the UPS to recharge the batteries for 1 hour, then initiate a manual battery test again.

If none of the five Battery LEDs illuminate during the second manual battery test, replace batteries and contact your local Emerson representative or Emerson Channel Support.

8.4Put the Liebert GXT3 in Manual Bypass

Press the Standby/Manual Bypass button and hold it for about 2 seconds while the UPS is in Mains (AC) Mode. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of mains power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indicators are illuminated, refer to 11.0 - Troubleshooting.)

8.5Shut Down the Liebert GXT3

1.Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding it for about 2 seconds.

If manual bypass is not available, disregard the first step.

2.Press the Standby/Manual Bypass button twice within four seconds, each time holding it for about two seconds.

Power to the connected loads is now Off.

8.6Disconnecting Input Power from the Liebert GXT3

1.After the UPS has been shut down as detailed in 8.5 - Shut Down the Liebert GXT3, turn off the Output Circuit Breaker.

2.Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete.

3.Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.

After powering off the UPS, the UPS ceases output and the load is powered Off.

8.7Maintenance Bypass

Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in Maintenance Bypass:

1.Place the UPS on internal bypass. This may be done by either of the following methods:

a.Press the Off button on the front panel one time.

b.Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires loosening the captive screw and sliding the bracket up and away from the Manual Bypass Breaker.

2.Move the Manual Bypass Breaker on the rear of the UPS to the bypass position. This requires loosening the captive screw and sliding the bracket up and away from the manual bypass breaker.

Liebert® GXT3

24

Image 30
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Maintenance TroubleshootingSpecifications Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsC19 Output Power Liebert GXT3, 5,000 & 6000VA Terminal Block CommunicationInternal Battery Packs Removable Power Distribution BoxWHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchExternal Battery Cabinet Installation Slide into the bracket assemblies more easilyExternal battery cabinets connected to 10,000VA Liebert GXT3 Connect Input/Output Power Extract These Captive screws Maintenance Bypass BreakerBranch circuit breaker ratings Electrical specificationsDistribution Box Electrical Connections Unit Rating Maximum Breaker RatingOutput Input Configuration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassIT Power System Configuration ConnectorsRemove Screws Terminal Block Communication Any Mode ShutdownCommunication Interface Port CommunicationLow Battery Battery Mode ShutdownOn Battery Liebert IntelliSlot Communication CardsRemote Emergency Power Off Repo switch connection diagramLiebert MultiLink Battery Replacement Procedures Replacing the Internal Battery PackMaintenance 6000VA model shownBattery Charging Precautions5000 & 6000 VA models Checking UPS Status Checking UPS FunctionsIndicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmTroubleshooting table Audible AlarmAudible alarm description Condition AlarmYour UPS has received a signal or command from Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications See TableBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Twor k Ne tIs t Care