Specifications
Table 11 Battery run time, minutes, all models
Number of | Load Percent | 230VAC RT Models | |||
|
|
| |||
Batteries/Cabinets | of Capacity | 5kVA | 6kVA | 10kVA | |
| 10% | 460 | 360 | 316 | |
|
|
|
|
| |
| 20% | 205 | 191 | 163 | |
|
|
|
|
| |
| 30% | 159 | 138 | 137 | |
|
|
|
|
| |
| 40% | 124 | 108 | 107 | |
Internal Battery |
|
|
|
| |
50% | 106 | 97 | 82 | ||
+ 4 External |
|
|
|
| |
60% | 98 | 81 | 69 | ||
Battery Cabinets | |||||
| 70% | 83 | 71 | 52 | |
|
|
|
|
| |
| 80% | 75 | 61 | 48 | |
|
|
|
|
| |
| 90% | 66 | 51 | 44 | |
|
|
|
|
| |
| 100% | 53 | 48 | 40 | |
|
|
|
|
|
Using the configuration program, the user may specify the number of
Table 11 shows the estimated run times at different loads.
12.1Auto-Learning Battery Run Times
As batteries age, the estimated run times may become less accurate. The Liebert GXT3 is programmed to “learn” from a full battery discharge and modify the estimated runtime for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
•The UPS must have a steady load that is greater than 20%.
•The UPS must be at 100% charge at the start of a battery discharge.
•The battery discharge must continue uninterrupted until the batteries reach their
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the battery above table will be restored. This will override any value that is