Emerson 000-VA, 5000-10, 230V user manual Checking UPS Status, Checking UPS Functions

Page 37

Maintenance

10.4Checking UPS Status

Emerson® recommends checking the UPS operation status every six months.

Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an alarm?

Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or Emerson Channel Support.

Check whether the battery is discharging. When the mains input is normal, the battery should not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson representative or Emerson Channel Support.

10.5Checking UPS Functions

NOTE

UPS function check procedures may interrupt power supply to the connected load.

Emerson recommends checking the UPS functions once every six months.

Back up the load data before conducting the UPS functions check. Procedures are as follows:

1.Press the Standby/Manual Bypass button to check whether the buzzer and indicators are normal.

2.Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators are on and the UPS is operating normally.

3.Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode. The UPS should initiate a battery self-test. Check to determine whether the battery is operating normally. If not, stop and contact your local Emerson representative or Emerson Channel Support

31

Liebert® GXT3

Image 37
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Troubleshooting MaintenanceSpecifications Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionDC-to-DC Converter BatteryDynamic Bypass Major Components Main Frame and ElectronicsLiebert GXT3, 5,000 & 6000VA Terminal Block Communication C19 Output PowerRemovable Power Distribution Box Internal Battery PacksWHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Connectors Spacers Support BasesInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationOperation and Display Panel Rotated Clockwise 90 Degrees Quantity813mm UPS or batteryDepth Retaining latchSlide into the bracket assemblies more easily External Battery Cabinet InstallationExternal battery cabinets connected to 10,000VA Liebert GXT3 Extract These Captive screws Maintenance Bypass Breaker Connect Input/Output PowerDistribution Box Electrical Connections Electrical specificationsBranch circuit breaker ratings Unit Rating Maximum Breaker RatingOutput Input Configuration Program Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonStandby/Manual Bypass Button Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberUPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Disconnecting Input Power from the Liebert GXT3 Manual Battery TestMaintenance Bypass Put the Liebert GXT3 in Manual BypassConnectors IT Power System ConfigurationRemove Screws Communication Interface Port Any Mode ShutdownTerminal Block Communication CommunicationOn Battery Battery Mode ShutdownLow Battery Liebert IntelliSlot Communication CardsRepo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures 6000VA model shownPrecautions Battery Charging5000 & 6000 VA models Checking UPS Functions Checking UPS StatusTroubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmTroubleshooting table Condition AlarmYour UPS has received a signal or command from UPS specifications SpecificationsPower distribution specifications Operating temperature parametersSee Table External battery cabinet specificationsBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Is t Ne tTwor k Care