Specifications
12.0SPECIFICATIONS
Table 7 | UPS specifications |
|
|
| ||
|
|
|
|
|
| |
| Model # |
| ||||
Rating |
| 5000VA/4000W |
| 6000VA/4800W | 10000VA/9000W | |
Dimensions, mm (in) |
|
|
|
| ||
| Unit, W x D x H | 430 x 574 x 217 (16.9 x 22.4 x 8.5) | 430 x 581 x 261 (16.9 x 22.9 x 10.3) | |||
|
|
|
| |||
| Shipping, W x D x H | 516 x 745 x 530 (20.3 x 29.3 x 20.9) | 530 x 745 x 563 (20.9 x 29.3 x 22.2) | |||
|
|
|
|
| ||
Weight, kg (lb) |
|
|
|
| ||
| Unit | 60 (132.2) | 70 (154.3) | |||
| Shipping | 71 (156.5) | 92 (202.8) | |||
|
|
|
|
| ||
Input AC Parameters |
|
|
|
| ||
Operating Frequency, Nom |
|
| 50 or 60Hz (Factory Default = 50) | |||
| Factory Default VAC |
|
| 230VAC |
| |
|
|
|
|
|
| |
|
| 220/230/240VAC |
| |||
(May be modified using included configuration program) | ||||||
|
| |||||
Operating Voltage Range |
|
| 176 - 280VAC |
| ||
Without Battery Operation |
|
|
| |||
|
|
|
| |||
Maximum Allowable VAC |
|
| 280VAC |
| ||
Input Frequency Without |
|
| 40 - 70Hz |
| ||
| Battery Operation |
|
|
| ||
|
|
|
|
| ||
|
| |||||
Input Power Connection | (See 3.3 - Removable Power | |||||
(See 3.3 - Removable Power Distribution Box) | ||||||
|
| Distribution Box) | ||||
|
|
|
|
| ||
Output AC Parameters |
|
|
|
| ||
|
|
| 92% |
| ||
| Factory Default VAC |
|
| 230VAC |
| |
|
|
|
|
|
| |
|
| |||||
| Output Connections | (See 3.3 - Removable Power | ||||
| (See 3.3 - Removable Power Distribution Box) | |||||
|
| Distribution Box) | ||||
|
|
|
|
| ||
| Frequency |
|
| 50Hz or 60Hz, Nominal | ||
|
|
|
|
|
| |
| Waveform |
|
| Sinewave |
| |
| Main Mode Overload | >200% for 5 cycles; 151 - 200% for 1 seconds; | ||||
Internal Battery Charger |
|
|
|
| ||
| Charger Current |
| 1.3 | 2.6 | ||
|
|
|
|
| ||
Battery Parameters |
|
|
|
| ||
| Type |
| ||||
| Quantity x V |
|
| 20 x 12V |
| |
|
|
|
|
|
| |
| Battery Mfr. / Part # | 5AH battery, CSB HR1221W or YUASA | 9AH battery, CSB HR1234W | |||
| or Panasonic | |||||
|
|
|
|
| ||
| Backup Time | See Table 11 - Battery run time, minutes, all models | ||||
Recharge Time (Internal | 3 hr. to 90% capacity after full discharge into 100% load | |||||
| Batteries) | |||||
|
|
|
|
| ||
Bypass Protection Limits |
|
|
|
| ||
Disable Bypass Operation | If input voltage exceeds ±15% of the nominal voltage | |||||
|
|
|
|
|
| |
| If input voltage returns to within ±10% of nominal output voltage | |||||
| Operation | |||||
|
|
|
|
| ||
Disable Bypass operation | When the input frequency prevents synchronous operation | |||||
|
|
|
|
| ||
Environmental |
|
|
|
| ||
Operating Temperature, | 0 to 40 (32 to 104) see Table 8 - Operating temperature parameters | |||||
| °C (°F) | |||||
|
|
|
|
| ||
Storage Temperature, |
|
|
| |||
| °C (°F) |
|
|
| ||
|
|
|
|
|
35 | Liebert® GXT3™ |