Emerson 000-VA Remote Emergency Power Off, Liebert MultiLink, Repo switch connection diagram

Page 34

Communication

9.3.1Liebert MultiLink®

Liebert MultiLink continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.

Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot® SNMP/Web card is installed in the UPS. Additionally, Liebert MultiLink can be configured to coordinate shutdown across the network with other computers running Liebert MultiLink when you purchase a Liebert MultiLink License Kit. For more information about the Liebert IntelliSlot SNMP/Web Card and Liebert MultiLink License Kits, visit our Web site (www.liebert.com) or contact your local dealer or Emerson® representative.

Several option cards are available for use in the Liebert IntelliSlot® port of the Liebert GXT3. The Liebert IntelliSlot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.

The Liebert IntelliSlot MultiPort 4 Card allows installing Liebert MultiLink software on four computers and coordinate shutdown in the event of a power failure.

The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support for built-in shutdown for AS/400 systems.

! CAUTION

To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be shielded and run separate from all other power cables, where applicable.

9.4Remote Emergency Power Off

The UPS is equipped with a Remote Emergency Power Off (REPO) connector.

The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.

REPO switch connection diagram

UPS ships with REPO jumper installed allowing the UPS to operate

1

2

Opening the REPO connection will disable the UPS. Manual restart using the front panel is required after the REPO connection is closed again.

1

2

 

 

Normally closed switch system (fail-safe)

! CAUTION

To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be shielded and run separately from power cables.

Liebert® GXT3

28

Image 34
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Troubleshooting MaintenanceSpecifications Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionDC-to-DC Converter BatteryDynamic Bypass Main Frame and Electronics Major ComponentsC19 Output Power Liebert GXT3, 5,000 & 6000VA Terminal Block CommunicationInternal Battery Packs Removable Power Distribution BoxWHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchExternal Battery Cabinet Installation Slide into the bracket assemblies more easilyExternal battery cabinets connected to 10,000VA Liebert GXT3 Connect Input/Output Power Extract These Captive screws Maintenance Bypass BreakerBranch circuit breaker ratings Electrical specificationsDistribution Box Electrical Connections Unit Rating Maximum Breaker RatingOutput Input Configuration Program Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassConnectors IT Power System ConfigurationRemove Screws Terminal Block Communication Any Mode ShutdownCommunication Interface Port CommunicationLow Battery Battery Mode ShutdownOn Battery Liebert IntelliSlot Communication CardsRepo switch connection diagram Remote Emergency Power OffLiebert MultiLink Battery Replacement Procedures Replacing the Internal Battery PackMaintenance 6000VA model shownPrecautions Battery Charging5000 & 6000 VA models Checking UPS Status Checking UPS FunctionsIndicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmTroubleshooting table Audible AlarmAudible alarm description Condition AlarmYour UPS has received a signal or command from Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications See TableBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Twor k Ne tIs t Care