Emerson 5000-10, 230V Liebert IntelliSlot Communication Cards, Battery Mode Shutdown, On Battery

Page 33

Communication

9.2.2Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.

Battery Mode Shutdown can be performed locally or remotely:

Local Battery Mode shutdown can be performed by shorting the pins in Set 4.

Remote Battery Mode Shutdown can be performed using a switch connected to the pins in Set 4 and mounted at remote location.

Activation of the Battery Mode Shutdown will be logged as an event in the event history log.

NOTE

Remote Power Off will be performed by NO contact.

The current limited source for this optocoupler (+12VDC, 50mA) will be available from UPS. The connection to the Liebert GXT3 for remote connection will be via terminal block connector.

Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

This signal must last for 1.5 seconds or longer.

A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the utility power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.

9.2.3On Battery

On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.

9.2.4Low Battery

Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.

NOTE

The rated values for the dry contacts for the On Battery and Low Battery signals are:

Rated Voltage: 30V (AC or DC)

Rated Current: 300mA

9.3Liebert IntelliSlot® Communication Cards

The Liebert IntelliSlot port on the UPS accepts three optional cards:

Liebert IntelliSlot SNMP Card

Liebert IntelliSlot Relay Card

Liebert IntelliSlot 485 Card.

The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network.

The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.

The Liebert IntelliSlot 485 Card is used to connect the UPS and a BMS.

Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at multilink.liebert.com

27

Liebert® GXT3

Image 33
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Maintenance TroubleshootingSpecifications Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Major Components Main Frame and ElectronicsLiebert GXT3, 5,000 & 6000VA Terminal Block Communication C19 Output PowerRemovable Power Distribution Box Internal Battery PacksWHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Connectors Spacers Support BasesInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationOperation and Display Panel Rotated Clockwise 90 Degrees Quantity813mm UPS or batteryDepth Retaining latchSlide into the bracket assemblies more easily External Battery Cabinet InstallationExternal battery cabinets connected to 10,000VA Liebert GXT3 Extract These Captive screws Maintenance Bypass Breaker Connect Input/Output PowerDistribution Box Electrical Connections Electrical specificationsBranch circuit breaker ratings Unit Rating Maximum Breaker RatingOutput Input Configuration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberUPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Disconnecting Input Power from the Liebert GXT3 Manual Battery TestMaintenance Bypass Put the Liebert GXT3 in Manual BypassIT Power System Configuration ConnectorsRemove Screws Communication Interface Port Any Mode ShutdownTerminal Block Communication CommunicationOn Battery Battery Mode ShutdownLow Battery Liebert IntelliSlot Communication CardsRemote Emergency Power Off Repo switch connection diagramLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures 6000VA model shownBattery Charging Precautions5000 & 6000 VA models Checking UPS Functions Checking UPS StatusTroubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmTroubleshooting table Condition AlarmYour UPS has received a signal or command from UPS specifications SpecificationsPower distribution specifications Operating temperature parametersSee Table External battery cabinet specificationsBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Is t Ne tTwor k Care