Emerson 5000-10, 000-VA, 230V user manual Battery Charging, Precautions, 5000 & 6000 VA models

Page 36

Maintenance

Figure 19 Pulling out the battery packs

5000 & 6000 VA models

10,000VA model

 

Internal

Internal

Battery

Battery

Pack

Pack

 

 

Battery

 

Battery

Handle

 

 

 

Handle

Each model has two

 

Pull Out with Battery Handle

 

battery packs

Pull Out with Battery Handle

 

 

6.Unpack a new internal battery pack. Take care not to destroy the packing.

Compare the new and old internal battery packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are different, stop and contact your local Emerson® representative or Emerson Channel Support.

7.Line up and slide in the new internal battery pack.

8.Repeat Steps 6 7 if replacing both battery packs. Each model has two battery packs

9.Reconnect the battery plugs and battery receptacles.

10.Gently push the battery wire into the UPS battery compartment.

11.Reattach the front battery door with the six screws.

12.Reattach the front plastic bezel cover to the UPS.

NOTE

The internal battery pack is hot-swappable. However, caution should be exercised because the load is unprotected from disturbances and power failures during this procedure. Do not replace the battery while the UPS is operating in Battery Mode. This will result in a loss of output power and will drop the connected load.

10.2Battery Charging

The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The Liebert GXT3 charges the batteries continuously when it is connected to the mains input power.

If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.

10.3Precautions

Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:

Turn Off and unplug the Liebert GXT3 before cleaning it.

Wear rubber gloves and boots.

Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.

Never block or insert any objects into the ventilation holes or other openings of the UPS.

Do not place the Liebert GXT3 power cord where it might be damaged.

Liebert® GXT3

30

Image 36
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Maintenance TroubleshootingSpecifications Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsC19 Output Power Liebert GXT3, 5,000 & 6000VA Terminal Block CommunicationInternal Battery Packs Removable Power Distribution BoxWHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchExternal Battery Cabinet Installation Slide into the bracket assemblies more easilyExternal battery cabinets connected to 10,000VA Liebert GXT3 Connect Input/Output Power Extract These Captive screws Maintenance Bypass BreakerElectrical specifications Distribution Box Electrical ConnectionsBranch circuit breaker ratings Unit Rating Maximum Breaker RatingOutput Input Configuration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassIT Power System Configuration ConnectorsRemove Screws Any Mode Shutdown Communication Interface PortTerminal Block Communication CommunicationBattery Mode Shutdown On BatteryLow Battery Liebert IntelliSlot Communication CardsRemote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures 6000VA model shownBattery Charging Precautions5000 & 6000 VA models Checking UPS Status Checking UPS FunctionsUPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionTroubleshooting table Condition AlarmYour UPS has received a signal or command from Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications See TableBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Ne t Is tTwor k Care