Emerson 230V, 5000-10, 000-VA user manual Battery run time, minutes, all models

Page 44

Specifications

Table 11 Battery run time, minutes, all models

Number of

Load Percent

230VAC RT Models

 

 

 

Batteries/Cabinets

of Capacity

5kVA

6kVA

10kVA

 

10%

105

97

81

 

 

 

 

 

 

20%

52

47

39

 

 

 

 

 

 

30%

40

33

22

 

 

 

 

 

 

40%

27

22

15

 

 

 

 

 

Internal Battery

50%

21

17

11

 

 

 

 

60%

17

14

9

 

 

 

 

 

 

 

70%

14

11

7

 

 

 

 

 

 

80%

12

9

5

 

 

 

 

 

 

90%

10

8

4

 

 

 

 

 

 

100%

9

6

3

 

 

 

 

 

 

10%

187

158

149

 

 

 

 

 

 

20%

106

97

82

 

 

 

 

 

 

30%

78

65

50

 

 

 

 

 

 

40%

53

48

39

Internal Battery

 

 

 

 

50%

47

40

28

+ 1 External

 

 

 

 

60%

40

33

22

Battery Cabinet

 

70%

34

26

17

 

 

 

 

 

 

80%

28

22

15

 

 

 

 

 

 

90%

23

19

13

 

 

 

 

 

 

100%

21

17

11

 

 

 

 

 

 

10%

217

205

191

 

 

 

 

 

 

20%

146

123

128

 

 

 

 

 

 

30%

106

97

82

 

 

 

 

 

 

40%

91

74

60

Internal Battery

 

 

 

 

50%

71

53

47

+ 2 External

 

 

 

 

60%

53

48

39

Battery Cabinets

 

70%

49

43

32

 

 

 

 

 

 

80%

45

38

26

 

 

 

 

 

 

90%

41

33

22

 

 

 

 

 

 

100%

37

28

18

 

 

 

 

 

 

10%

360

223

224

 

 

 

 

 

 

20%

188

158

150

 

 

 

 

 

 

30%

132

110

112

 

 

 

 

 

 

40%

106

97

82

Internal Battery

 

 

 

 

50%

95

78

66

+ 3 External

 

 

 

 

60%

79

66

50

Battery Cabinets

 

70%

68

52

45

 

 

 

 

 

 

80%

53

48

40

 

 

 

 

 

 

90%

50

44

34

 

 

 

 

 

 

100%

47

41

28

 

 

 

 

 

Liebert® GXT3

38

Image 44
Contents Liebert GXT3 230V,5000-10,000VA Page Table of Contents Specifications MaintenanceTroubleshooting Figures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDynamic Bypass BatteryDC-to-DC Converter Main Frame and Electronics Major ComponentsC19 Output Power Liebert GXT3, 5,000 & 6000VA Terminal Block CommunicationInternal Battery Packs Removable Power Distribution BoxWHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchExternal Battery Cabinet Installation Slide into the bracket assemblies more easilyExternal battery cabinets connected to 10,000VA Liebert GXT3 Connect Input/Output Power Extract These Captive screws Maintenance Bypass BreakerElectrical specifications Distribution Box Electrical ConnectionsBranch circuit breaker ratings Unit Rating Maximum Breaker RatingOutput Input What You Will Need Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassRemove Screws IT Power System ConfigurationConnectors Any Mode Shutdown Communication Interface PortTerminal Block Communication CommunicationBattery Mode Shutdown On BatteryLow Battery Liebert IntelliSlot Communication CardsLiebert MultiLink Remote Emergency Power OffRepo switch connection diagram Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures 6000VA model shown5000 & 6000 VA models Battery ChargingPrecautions Checking UPS Status Checking UPS FunctionsUPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionTroubleshooting table Condition AlarmYour UPS has received a signal or command from Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications See TableBattery run time, minutes, all models Auto-Learning Battery Run Times Specifications Liebert GXT3 Page Ne t Is tTwor k Care