Chapter 3 Installing and Removing Server Switch Field Replaceable Units (FRUs)
Removing an InfiniBand Switch Module
Removing an InfiniBand Switch Module
To remove an InfiniBand switch module from the Cisco SFS 3012R Server Switch chassis, perform the following steps:
Step 1 Make sure the Cisco SFS 3012R Server Switch chassis is securely seated in the rack.
Step 2 If you are removing the InfiniBand module from slot 16 (the lower module), you must power down the chassis before removing the module.
Note The InfiniBand module in slot 16 is not
Step 3 Properly ground yourself to avoid potential electrostatic discharge and damage to the module.
Step 4 Facing the cable end of the Cisco SFS 3012R Server Switch chassis, unfasten both screws on the InfiniBand switch module.
Loosen the screws until you are sure the module is no longer attached to the chassis. Do not attempt to remove the screws from the module.
Step 5 Open both ejector levers simultaneously, and pull the switch module toward you.
Step 6 Either replace the module immediately or install a blanking panel over the empty chassis bay to ensure appropriate cooling.
Note The blanking panel is a flat sheet of metal with the same dimensions as the InfiniBand switch module faceplate.
Installing a Power Supply Module
Warning Hazardous voltage or energy is present on the backplane when the system is operating. Use caution when servicing. Statement 1034
Caution Never place your hand inside an empty module bay or anywhere inside the Cisco SFS 3012R Server Switch.
Caution Unused module bays should always have a switch filler panel over the bay to ensure proper safety, ventilation, and cooling.
Cisco SFS 3012R Multifabric Server Switch Hardware Installation Guide
|
| ||
|
|