Delta Electronics manual CANopen Communication Module DVPCOPM-SL

Page 31

CANopen Communication Module DVPCOPM-SL

Code

Indication

How to correct

F9

Low voltage is deteced.

Check and make sure the power of

DVPCOPM-SL works normally.

 

 

FA

The firmware of DVPCOPM-SL is

Re-power DVPCOPM-SL.

in error status.

 

 

FB

The sending buffer in

Make sure the bus works normally and re-power

DVPCOPM-SL is full.

DVPCOPM-SL.

 

FC

The receiving buffer in

Make sure the bus works normally and re-power

DVPCOPM-SL is full.

DVPCOPM-SL.

 

E0

DVPCOPM-SL receives

Read relevant information through PLC MPU or

Emergency message sent by the

Delta CANopenBuilder software.

 

slave.

 

 

 

 

 

E1

PDO data length returned from the

Reset the PDO data length in the slave and

slave is not consistent with the

download the new setting to DVPCOPM-SL.

 

length set in the node list.

 

 

 

 

 

E2

PDO message from the slave has

Check and make sure the setting is correct.

not been received.

 

 

E3

Auto SDO download failed.

Check and make sure auto SDO is correct.

 

 

 

E4

PDO parameter setting has failed.

Make sure the PDO parameter setting is legal.

 

 

 

E5

Error in key parameter setting.

Make sure all the slaves connected are

consistentwith the slaves set.

 

 

E6

The slave does not exist in the

 

network.

Make sure the power of the slave and the

 

E7

The slave's error control is

network connection work normally.

timed-out.

 

 

 

E8

Master/slave node address is

Reset the node address and make sure the new

repeated.

address is not a repeated one.

 

zDVPCOPM-SL as slave:

Code

Indication

How to correct

0 ~ 7F

The node address of DVPCOPM-SL

--

 

when in normal operation.

 

A0

The parameters in DVPCOPM-SL is

--

 

being initialized.

 

A1

DVPCOPM-SL is in pre-operational

--

status.

 

 

A3

The data are being downloaded to

--

DVPCOPM-SL.

 

 

B0

Heartbeat timed-out

Re-connect DVPCOPM-SL to the network.

 

 

 

B1

PDO data length returned from the

Reset the PDO data length in the slave and

slave is not consistent with the

download the new setting to DVPCOPM-SL.

 

length set in the node list.

 

 

 

 

 

F4

Bus-off is detected

Make sure the communication cable is in normal

operation, and all the nodes on the network work

 

 

in the same baud rate. Re-power DVPCOPM-SL.

FB

The sending buffer in

Make sure the bus works normally and re-power

DVPCOPM-SL is full.

DVPCOPM-SL.

 

FC

The receiving buffer in

Make sure the bus works normally and re-power

DVPCOPM-SL is full.

DVPCOPM-SL.

 

DVP-PLC Application Manual

29

Image 31
Contents DVPCOPM-SL Page Table of Contents LED Indicator & TROUBLE-SHOOTING Introduction FeaturesCan 500VDC FunctionsProduct Profile & Outline DimensionProduct Profiles Function Switch Address SwitchCANopen Connection Port Basic Operation Digital IndicatorConnecting DVPCOPM-SL to DVP-SV MPU Installing DVPCOPM-SL and DVP-SV MPU on DIN RailHow to Construct a CANopen Network Connecting to CANopen Connection PortConstructing CANopen Network CANopen Data Mapping in CANopen Network How to Configure Network by Delta CANopenBuilder Software DVP-SV CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Network Control Saving the Configuration DataPrinciple Sending SDO, NMT and Reading Emergency by Ladder DiagramStructure of SDO Request Message MAC ID Structure of NMT Service MessageStructure of Emergency Request Message Application Examples Status = 01Hex MOV MAC ID = 02Hex LED Indicator & Trouble-shooting Codes in Digital Display Power LEDCANopen Communication Module DVPCOPM-SL Memo