Delta Electronics DVPCOPM-SL manual CANopen Connection Port, Address Switch, Function Switch

Page 8

CANopen Communication Module DVPCOPM-SL

3.

POWER, RUN, ERR indicators

8.

Function switch

4.

DIN rail clip

9.

CANopen connection port

5.Digital display

2.3CANopen Connection Port

The connector is used on the connection to CANopen network. Wire by using the connector enclosed with

DVPCOPM-SL.

PIN

Signal

Content

1

GND

0 VDC

 

 

 

2

CAN_L

Signal-

 

 

 

3

SHLD

Shielded

 

 

 

4

CAN_H

Signal+

 

 

 

5

-

Reserved

 

 

 

CAN+

SHLD

CAN-

GND

5

4

3

2

1

2.4Address Switch

The switch is used on setting up the node address of DVPCOPM-SL on CANopen network. Range: 1 ~ 7F (0,

88 ~ FF are forbidden).

Switch setting

Content

 

 

1 ~ 7F

Valid CANopen node address

 

 

0, 80 ~ FF

Invalid CANopen node address

 

 

NODE ADDRESS

x161

0

x16

Example: If you need to set the node address of DVPCOPM-SL to 26 (1AH), simply switch the corresponding switch of x161 to 1 and the corresponding switch of x160 to A.

Note:

zUse slotted screwdriver to rotate the switch carefully in case you scratch the switch.

zPlease set up the node address when the power is switched off. After the setup is completed, re-poser

DVPCOPM-SL.

2.5Function Switch

The switch is used on setting up the baud rate between DVPCOPM-SL and CANopen network (DR0 ~ DR2). See the table below for the baud rate and its maximum communication distance.

DR2

DR1

DR0

Baud rate (bps)

Max. communication distance (m)

OFF

OFF

OFF

10k

5,000

 

 

 

 

 

OFF

OFF

ON

20k

2,500

 

 

 

 

 

OFF

ON

OFF

50k

1,000

 

 

 

 

 

OFF

ON

ON

125k

500

 

 

 

 

 

ON

OFF

OFF

250k

250

 

 

 

 

 

ON

OFF

ON

500k

100

 

 

 

 

 

ON

ON

OFF

800k

50

 

 

 

 

 

ON

ON

ON

1M

25

 

 

 

 

 

 

 

IN0

 

Reserved

 

 

 

 

 

6

DVP-PLC Application Manual

Image 8
Contents DVPCOPM-SL Page Table of Contents LED Indicator & TROUBLE-SHOOTING Features IntroductionFunctions Can 500VDCProduct Profiles DimensionProduct Profile & Outline CANopen Connection Port Address SwitchFunction Switch Digital Indicator Connecting DVPCOPM-SL to DVP-SV MPUInstalling DVPCOPM-SL and DVP-SV MPU on DIN Rail Basic OperationConstructing CANopen Network Connecting to CANopen Connection PortHow to Construct a CANopen Network CANopen Data Mapping in CANopen Network How to Configure Network by Delta CANopenBuilder Software DVP-SV CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL Saving the Configuration Data CANopen Network ControlStructure of SDO Request Message Sending SDO, NMT and Reading Emergency by Ladder DiagramPrinciple Structure of NMT Service Message MAC IDStructure of Emergency Request Message Application Examples Status = 01Hex MOV MAC ID = 02Hex LED Indicator & Trouble-shooting Power LED Codes in Digital DisplayCANopen Communication Module DVPCOPM-SL Memo