CANopen Communication Module
3. | POWER, RUN, ERR indicators | 8. | Function switch |
4. | DIN rail clip | 9. | CANopen connection port |
5.Digital display
2.3CANopen Connection Port
The connector is used on the connection to CANopen network. Wire by using the connector enclosed with
PIN | Signal | Content |
1 | GND | 0 VDC |
|
|
|
2 | CAN_L | Signal- |
|
|
|
3 | SHLD | Shielded |
|
|
|
4 | CAN_H | Signal+ |
|
|
|
5 | - | Reserved |
|
|
|
CAN+
SHLD
CAN-
GND
5
4
3
2
1
2.4Address Switch
The switch is used on setting up the node address of
88 ~ FF are forbidden).
Switch setting | Content |
|
|
1 ~ 7F | Valid CANopen node address |
|
|
0, 80 ~ FF | Invalid CANopen node address |
|
|
NODE ADDRESS
x161
0
x16
Example: If you need to set the node address of
Note:
zUse slotted screwdriver to rotate the switch carefully in case you scratch the switch.
zPlease set up the node address when the power is switched off. After the setup is completed,
2.5Function Switch
The switch is used on setting up the baud rate between
DR2 | DR1 | DR0 | Baud rate (bps) | Max. communication distance (m) |
OFF | OFF | OFF | 10k | 5,000 |
|
|
|
|
|
OFF | OFF | ON | 20k | 2,500 |
|
|
|
|
|
OFF | ON | OFF | 50k | 1,000 |
|
|
|
|
|
OFF | ON | ON | 125k | 500 |
|
|
|
|
|
ON | OFF | OFF | 250k | 250 |
|
|
|
|
|
ON | OFF | ON | 500k | 100 |
|
|
|
|
|
ON | ON | OFF | 800k | 50 |
|
|
|
|
|
ON | ON | ON | 1M | 25 |
|
|
|
|
|
|