Delta Electronics DVPCOPM-SL manual Status = 01Hex

Page 26

CANopen Communication Module DVPCOPM-SL

Required settings in DVPCOPM-SL:

Parameter

Setting

 

Explanation

Node address

01

 

Set the node address of DVPCOPM-SL to “01”.

 

 

 

 

Baud rate

1 Mbps

 

Set the communication speed between DVPCOPM-SL and

 

bus to “1 Mbps”.

 

 

 

Required settings in IFD9503:

 

 

 

 

 

 

Parameter

Setting

 

Explanation

Node address

02

 

Set the node address of IFD9503 to “02”.

 

 

 

 

Baud rate

1 Mbps

 

Set the communication speed between IFD9503 and bus to

 

“1 Mbps”.

 

 

 

Required settings in VFD-B AC motor drive:

Parameter

 

 

Setting

 

 

 

 

 

 

 

 

Explanation

 

 

 

 

 

 

 

 

 

02-00

 

 

04

 

The main frequency is operated by RS-485 interface.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02-01

 

 

03

 

The running command is operated by communication

 

 

 

 

 

 

 

interface. Operation by keys is valid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09-00

 

 

01

 

Communication address of VFD-B: 01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09-01

 

 

03

 

Baud rate: 38,400 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09-04

 

 

03

 

Modbus RTU mode, format <8, N, 2>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Devices in PLC:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLC device

 

Content

 

 

 

 

 

 

 

 

Explanation

 

 

 

 

 

 

 

 

 

 

 

15

14

13

12

11

10

 

9

8

7

 

6

 

5

4

3

2

 

1

0

 

 

 

 

 

 

 

 

 

 

 

 

 

D6250

 

0101Hex

 

 

 

ReqID = 01Hex

 

 

 

 

 

Command = 01Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SDO request

D6251

 

0004Hex

 

 

 

 

Reserved

 

 

 

 

 

 

Size = 04Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

message

D6252

 

0102Hex

 

 

 

Type = 01Hex

 

 

 

 

 

 

MAC ID = 02Hex

 

 

editing area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6253

 

2021Hex

 

High byte of index = 20Hex

 

Low byte of index = 21Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6254

 

0004Hex

 

 

 

 

Reserved

 

 

 

 

 

Sub index = 04Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6000

 

0101Hex

 

 

 

ReqID = 01Hex

 

 

 

 

 

 

Status = 01Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6001

 

0006Hex

 

 

 

 

Reserved

 

 

 

 

 

 

Size = 06Hex

 

 

 

SDO response

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6002

 

4B02Hex

 

 

 

Type = 4BHex

 

 

 

 

 

 

MAC ID = 02Hex

 

 

message

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6003

 

2021Hex

 

High byte of index = 20Hex

 

Low byte of index = 21Hex

 

editing area

 

 

 

 

 

D6004

 

0004Hex

 

 

 

 

Reserved

 

 

 

 

 

Sub index = 04Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6005

 

0100Hex

 

 

 

Datum 1= 01Hex

 

 

 

 

Datum 0 = 00Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0100Hex in D6005 refers to the actual output frequency of the AC motor drive is 2.56Hz.

zPLC program

M1002

ZRST D6000 D6031

ZRST D6250 D6281

Reset response message editing area and request message editing area.

24

DVP-PLC Application Manual

Image 26
Contents DVPCOPM-SL Page Table of Contents LED Indicator & TROUBLE-SHOOTING Features IntroductionFunctions Can 500VDCProduct Profiles DimensionProduct Profile & Outline CANopen Connection Port Address SwitchFunction Switch Installing DVPCOPM-SL and DVP-SV MPU on DIN Rail Digital IndicatorConnecting DVPCOPM-SL to DVP-SV MPU Basic OperationConstructing CANopen Network Connecting to CANopen Connection PortHow to Construct a CANopen Network CANopen Data Mapping in CANopen Network How to Configure Network by Delta CANopenBuilder Software DVP-SV CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL CANopen Communication Module DVPCOPM-SL Saving the Configuration Data CANopen Network ControlStructure of SDO Request Message Sending SDO, NMT and Reading Emergency by Ladder DiagramPrinciple Structure of NMT Service Message MAC IDStructure of Emergency Request Message Application Examples Status = 01Hex MOV MAC ID = 02Hex LED Indicator & Trouble-shooting Power LED Codes in Digital DisplayCANopen Communication Module DVPCOPM-SL Memo