Page 20

MTEK6000 SERIES USER'S MANUAL

INSTALLING THE PULSE OUTPUT WIRING

The MTEK6000 comes standard with a board installed that provides two optically isolated pulse outputs. These outputs are configurable as either Form C or Form A type outputs. An alternative version of the board is available that provides four pulse outputs. Both versions of the board also provide terminal block positions to access the uncorrected mechanical volume switch output of the index. See Fig. 2-11 for pulse output wiring. The option boards optical coupling and physical arrangement of circuitry provide a minimum of 1,500 volts of isolation.

Wiring connections for the pulse outputs are made from terminals 19 to 17 for Pulse output #1, terminals 16 to 14 for Pulse output #2, terminals 13 to 11 for Pulse output #3 and terminals 10 to 8 for Pulse output #4. See Fig. 2-11 for pulse output wiring location and Form C vs. Form A jumpering. Note that proper operation of the Form C pulse output

configuration requires that a constant wetting current be available at both the normally open and normally closed terminals by the device attached to that pulse output.

The corrected volume pulse output generated can be scaled to any desired volume value. Typical values are 10, 100, 1,000, or 10,000 cubic feet per pulse, or the metric equivalents. The scaling factor is selected by the Pulse Out CF Per Pulse parameters. The pulse duration (width) is also configurable up to 5,000 ms. The Pulse Output On-Time and Off-Timeparameters determine the pulse time for corrected volume, uncorrected volume and pressure corrected volume pulses. The Alarm Pulse Time (ms) parameter determines the pulse time for alarm outputs. See Appendix C in this manual or Meter Reader Help screen for description of this parameter.

Figure 2- 9 Pulse Output Wiring

2-10

January 2002

Image 20
Contents MTEK6000 Series Table of Contents Optional Equipment List of Figures January January Overview Hazardous LocationsSecurity Options ONE-YEAR WarrantyCompliance MTEK6000 exterior view MTEK6000 interior view Unpacking Initial Check OUTMounting the Instrument on the Meter Power for the MTEK6000Optional Power Supplies Setting UP the Index Assembly Output Shaft RotationUnit and Index Rotation Counter MaskingPulse Input to the MTEK6000 Wall and Pipe MountingWall Mounting Connecting the Pressure Tubing Transducers in the MTEK6000Typical Installation for MTEK6000 EFC Installing the Thermal Probe Pipe Size Insertion Thermowell Length Part NumberInstalling the Pulse Output Wiring Pulse Output WiringVolume and Alarm Pulse Specifications Uncorrected Pulse Output SpecificationsConnecting the Telephone Line CommunicationsRS-232C Serial Direct Communications 9600 Baud Modem Communications 2400 BaudActivity Indicator MTEK6000 Function RS232 cable connected January Grounding ReferencesJanuary SLEEP/WAKE-UP Mode Display ModeAlarm Mode Viewing and clearing alarms using the magnetFaulty Counter Alarm EFC First Time Power AlarmHigh Flow Rate Alarm EFC & EFM High Differential Pressure Alarm EFMLow Pressure Alarm Low Supply Volts AlarmsLow Temperature Alarm Lost Temperature AlarmMemory History Logging Open Door Alarm optionalSoftware Error Alarm Configuration Mode Editing ParametersOptional Keypad and Display Assigning Function Keys Audit TrailWake-Up on Pulse Event Driven Analog SamplingSpecial Key Combinations Calibration Mode Calibrating the Pressure TransducerCalibrating the Temperature Transducer Zero NEW?Calibrating the Differential Pressure Transmitter EFM Only Optional Equipment Analog Output AO OptionAnalog Output Option MTEK6000 Analog Output Specifications Zero x.xxx 04.000 +y.yyy mA Calibration Enclosure MaintenanceChanging the Battery Mtek Manager PcGas Meter Utility PackagePcGas Customer Monitor DC2000 January Alarms Alarm Code Label I.D Description AddressTable A-5 Standard alarms for MTEK6000 EFC w/ Aux Pressure Label Description Address Aux Pressure Table A-11 Standard alarms for MTEK6000 EFC2 w/2 Aux Press Table A-14 Standard alarms for MTEK6000 EFM w/ Aux Press MTEK6000 EPR MTEK6000 ETR MTEK6000 Eptr January AGA-7 Volume Calculations NX19 Supercompressibility ReportJanuary Alarm Pulse Output Enable/Disable Alarm Pulse Time msAudit Trail Logging Enable Analog Sampling Rate secondsBase Temperature Calibrate Mode Time-outCalibration Password Configuration PasswordDate Month, Day, Year Flow Rate Update Interval sCubic Unit/Pulse In or Meter Drive High Flow Rate Alarm Setpoint High Pressure Alarm SetpointHigh Pressure Alarm Reset High Temperature Alarm ResetLow Pressure Alarm Setpoint Low Supply Voltage Alarm ResetLow Supply Voltage Alarm Setpoint Low Temperature Alarm ResetUncorrected Volume Time Hhmmss Hours, Minutes, SecondsWake Up Interval seconds Wake Up On Pulse event driven EFCFlow & Volume Temperature DifferentialUnits of Measure AccumulationsJanuary SBC Revision a Corrector Board OPT Revision a Option Board Description Jumper positionPulse Input #1 PLI Revision C Phone Line Interface Service Requirement Consumer Information and FCC RequirementsWarranty & Repair Service EL0001 Sheet 1 of 2 Class I Division 2 Installation EL0001 Sheet 2 of 2 Class I Division 2 Installation Warranty Information January Appendix G TII Station Protector January Appendix H Hazardous Area Installation Control Drawings October October