Compaq MTEK6000 Faulty Counter Alarm EFC, First Time Power Alarm, High Flow Rate Alarm EFC & EFM

Page 29

MTEK6000 SERIES USER'S MANUAL

For transport or interruptible customers, this parameter can be used to alarm when an account has exceeded a predetermined daily volume allocation.

Faulty Counter Alarm (EFC)

This alarm is only valid for EFC units with a Form C switch. If any of the dual-reed switches in the index assembly fail, pulses to the unit would automatically switch to a working counter input. When this happens, the unit generates a Faulty Counter alarm (see the section on Pulse Input to the MTEK6000 in chapter 2 for more details).

First Time Power Alarm

First Time Power alarm is defined as the re- application of power after interruption of the power source. For example, whenever the battery is disconnected and then subsequently reconnected, the unit records the First Time Power event.

High Flow Rate Alarm (EFC & EFM)

If the flow rate should exceed the High Flow Rate Alarm Setpoint, a High Flow Rate alarm will be initiated. The alarm will remain active until the flow rate falls below the High Flow Rate Reset parameter value. The setpoints are user configurable with default values of 100000 and 99990 respectively (see Appendix A for parameter addressing for your device).

High Differential Pressure Alarm (EFM)

If the differential pressure should exceed the High Differential Pressure Alarm Setpoint, a High Differential Pressure alarm will be initiated. The alarm will remain active until the differential pressure falls below the High Differential Pressure Reset parameter value. The setpoints are user configurable with default values of 1500 and 1480 respectively (see Appendix A for parameter addressing for your device).

January 2002

High Pressure Alarm

If the gas pressure should exceed the High Pressure Alarm Setpoint, a High Pressure alarm will be initiated. The alarm will remain active until the pressure falls below the High Pressure Reset parameter value. The setpoints are user configurable with default values of 1500 and 1480 respectively (see Appendix A for parameter addressing for your device).

High Temperature Alarm

If the gas flow temperature should exceed the High Temperature Alarm Setpoint, a High Temperature alarm will be initiated. The alarm will remain active until the temperature falls below the High Temperature Reset parameter value. The setpoints are user configurable with default values of 200 and 180 respectively (see Appendix A for parameter addressing for your device).

Low Differential Pressure Alarm (EFM) If the differential pressure should fall below the Low Differential Pressure Alarm Setpoint, a Low Differential Pressure alarm will be initiated. The alarm will remain active until the differential pressure rises above the Low Differential Pressure Reset parameter value. The setpoints are user configurable with default values of - 100 and -80 respectively (see Appendix A for parameter addressing for your device).

Low Flow Rate Alarm (EFC & EFM)

If the flow rate should fall below the Low Flow Rate Alarm Setpoint, a Low Flow Rate alarm will be initiated. The alarm will remain active until the flow rate rises above the Low Flow Rate Reset parameter value. The setpoints are user configurable with default values of -100 and -80 respectively (see Appendix A for parameter addressing for your device).

3 -3

Image 29
Contents MTEK6000 Series Table of Contents Optional Equipment List of Figures January January Hazardous Locations OverviewSecurity Options ONE-YEAR WarrantyCompliance MTEK6000 exterior view MTEK6000 interior view Initial Check OUT UnpackingMounting the Instrument on the Meter Power for the MTEK6000Optional Power Supplies Output Shaft Rotation Setting UP the Index AssemblyCounter Masking Unit and Index RotationWall and Pipe Mounting Pulse Input to the MTEK6000Wall Mounting Transducers in the MTEK6000 Connecting the Pressure TubingTypical Installation for MTEK6000 EFC Pipe Size Insertion Thermowell Length Part Number Installing the Thermal ProbePulse Output Wiring Installing the Pulse Output WiringUncorrected Pulse Output Specifications Volume and Alarm Pulse SpecificationsCommunications Connecting the Telephone LineRS-232C Serial Direct Communications 9600 Baud Modem Communications 2400 BaudActivity Indicator MTEK6000 Function RS232 cable connected January References Grounding January Display Mode SLEEP/WAKE-UP ModeViewing and clearing alarms using the magnet Alarm ModeFirst Time Power Alarm Faulty Counter Alarm EFCHigh Flow Rate Alarm EFC & EFM High Differential Pressure Alarm EFMLow Supply Volts Alarms Low Pressure AlarmLow Temperature Alarm Lost Temperature AlarmMemory History Logging Open Door Alarm optionalSoftware Error Alarm Editing Parameters Configuration ModeOptional Keypad and Display Audit Trail Assigning Function KeysWake-Up on Pulse Event Driven Analog SamplingSpecial Key Combinations Calibrating the Pressure Transducer Calibration ModeZero NEW? Calibrating the Temperature TransducerCalibrating the Differential Pressure Transmitter EFM Only Analog Output AO Option Optional EquipmentAnalog Output Option MTEK6000 Analog Output Specifications Zero x.xxx 04.000 +y.yyy mA Calibration Enclosure MaintenanceChanging the Battery Mtek Manager PcGas Meter Utility PackagePcGas Customer Monitor DC2000 January Label I.D Description Address Alarms Alarm CodeTable A-5 Standard alarms for MTEK6000 EFC w/ Aux Pressure Label Description Address Aux Pressure Table A-11 Standard alarms for MTEK6000 EFC2 w/2 Aux Press Table A-14 Standard alarms for MTEK6000 EFM w/ Aux Press MTEK6000 EPR MTEK6000 ETR MTEK6000 Eptr January NX19 Supercompressibility Report AGA-7 Volume CalculationsJanuary Alarm Pulse Time ms Alarm Pulse Output Enable/DisableAudit Trail Logging Enable Analog Sampling Rate secondsCalibrate Mode Time-out Base TemperatureCalibration Password Configuration PasswordDate Month, Day, Year Flow Rate Update Interval sCubic Unit/Pulse In or Meter Drive High Pressure Alarm Setpoint High Flow Rate Alarm SetpointHigh Pressure Alarm Reset High Temperature Alarm ResetLow Supply Voltage Alarm Reset Low Pressure Alarm SetpointLow Supply Voltage Alarm Setpoint Low Temperature Alarm ResetTime Hhmmss Hours, Minutes, Seconds Uncorrected VolumeWake Up Interval seconds Wake Up On Pulse event driven EFCTemperature Differential Flow & VolumeUnits of Measure AccumulationsJanuary SBC Revision a Corrector Board Description Jumper position OPT Revision a Option BoardPulse Input #1 PLI Revision C Phone Line Interface Consumer Information and FCC Requirements Service RequirementWarranty & Repair Service EL0001 Sheet 1 of 2 Class I Division 2 Installation EL0001 Sheet 2 of 2 Class I Division 2 Installation Warranty Information January Appendix G TII Station Protector January Appendix H Hazardous Area Installation Control Drawings October October