Compaq MTEK6000 user manual Low Pressure Alarm, Low Supply Volts Alarms, Low Temperature Alarm

Page 30

MTEK6000 SERIES USER'S MANUAL

Low Pressure Alarm

If the gas pressure should fall below the Low Pressure Alarm Setpoint, a Low Pressure alarm will be initiated. The alarm will remain active until the pressure rises above the Low Pressure Reset parameter value. The setpoints are user configurable with default values of -100 and -80 respectively (see Appendix A for parameter addressing for your device).

Low Supply Volts Alarms

If the supply voltage to the unit falls below the Low Supply Volts Alarm Setpoint value, a Low Supply Volts alarm will be initiated. The alarm will remain active until the supply voltage is greater than the Low Supply Volts Alarm Reset parameter. The setpoints are user configurable with default values of 2.9 and 3.1 volts respectively for battery powered units (see Appendix A for parameter addressing for your device).

Low Temperature Alarm

If the gas flow temperature should fall below the Low Temperature Alarm Setpoint, a Low Temperature alarm will be initiated. The alarm will remain active until the temperature rises above the Low Temperature Reset parameter value. The setpoints are user configurable with default values of -100 and -80 respectively (see Appendix A for parameter addressing for your device).

Lost Differential Pressure Alarm (EFM)

A Lost Differential Pressure alarm is generated when the differential pressure circuitry is over-ranged. This can occur if the differential pressure transmitter is defective, or disconnected from the analog board causing differential pressure readings to be above or below the range of the transducer.

3-4

Lost Pressure Alarm

A Lost Pressure alarm is generated when the pressure circuitry is over-ranged. This can occur if the pressure transducer is defective, or disconnected from the analog board causing pressure readings to be above or below the range of the transducer.

Lost Temperature Alarm

A Lost Temperature alarm is generated when the temperature circuitry is over- ranged. This can occur if the thermal (temperature) probe is defective, or disconnected from the analog board causing temperature readings to be above or below the range of the probe.

LowVolt Shutdown

On battery powered units, if the battery voltage decreases to approximately 2.8 volts, an interrupt will be triggered and the unit will enter Low Voltage (Critical) Shutdown mode. Low batt will be displayed on the display. This is an indication that the supply voltage is absolutely too low to operate the unit properly. The battery must be changed at this point or adequate supply voltage applied. For units that are externally powered, this point will occur when the input voltage drops to approximately 6.0 volts. In this mode, all operations cease, and the unit operates in a protective mode. The on-board battery will continue to protect the unit's memory; therefore data prior to entering this mode will be maintained. The supply voltage is monitored constantly and the unit will reset itself should the supply voltage become greater than 6.0 volts. If the unit is left alone without applying adequate supply voltage, the battery will continue to drain and the outside display will eventually go blank.

When sufficient supply voltage is applied and the unit powers-up, a LowVolt Shutdown alarm will be recorded.

January 2002

Image 30
Contents MTEK6000 Series Table of Contents Optional Equipment List of Figures January January Overview Hazardous LocationsONE-YEAR Warranty ComplianceSecurity Options MTEK6000 exterior view MTEK6000 interior view Unpacking Initial Check OUTPower for the MTEK6000 Optional Power SuppliesMounting the Instrument on the Meter Setting UP the Index Assembly Output Shaft RotationUnit and Index Rotation Counter MaskingPulse Input to the MTEK6000 Wall and Pipe MountingWall Mounting Connecting the Pressure Tubing Transducers in the MTEK6000Typical Installation for MTEK6000 EFC Installing the Thermal Probe Pipe Size Insertion Thermowell Length Part NumberInstalling the Pulse Output Wiring Pulse Output WiringVolume and Alarm Pulse Specifications Uncorrected Pulse Output SpecificationsRS-232C Serial Direct Communications 9600 Baud Connecting the Telephone LineCommunications Modem Communications 2400 BaudActivity Indicator MTEK6000 Function RS232 cable connected January Grounding ReferencesJanuary SLEEP/WAKE-UP Mode Display ModeAlarm Mode Viewing and clearing alarms using the magnetHigh Flow Rate Alarm EFC & EFM Faulty Counter Alarm EFCFirst Time Power Alarm High Differential Pressure Alarm EFMLow Temperature Alarm Low Pressure AlarmLow Supply Volts Alarms Lost Temperature AlarmOpen Door Alarm optional Software Error AlarmMemory History Logging Configuration Mode Editing ParametersOptional Keypad and Display Wake-Up on Pulse Event Driven Assigning Function KeysAudit Trail Analog SamplingSpecial Key Combinations Calibration Mode Calibrating the Pressure TransducerCalibrating the Temperature Transducer Zero NEW?Calibrating the Differential Pressure Transmitter EFM Only Optional Equipment Analog Output AO OptionAnalog Output Option MTEK6000 Analog Output Specifications Zero x.xxx 04.000 +y.yyy mA Enclosure Maintenance Changing the BatteryCalibration PcGas Meter Utility Package PcGas Customer MonitorMtek Manager DC2000 January Alarms Alarm Code Label I.D Description AddressTable A-5 Standard alarms for MTEK6000 EFC w/ Aux Pressure Label Description Address Aux Pressure Table A-11 Standard alarms for MTEK6000 EFC2 w/2 Aux Press Table A-14 Standard alarms for MTEK6000 EFM w/ Aux Press MTEK6000 EPR MTEK6000 ETR MTEK6000 Eptr January AGA-7 Volume Calculations NX19 Supercompressibility ReportJanuary Audit Trail Logging Enable Alarm Pulse Output Enable/DisableAlarm Pulse Time ms Analog Sampling Rate secondsCalibration Password Base TemperatureCalibrate Mode Time-out Configuration PasswordFlow Rate Update Interval s Cubic Unit/Pulse In or Meter DriveDate Month, Day, Year High Pressure Alarm Reset High Flow Rate Alarm SetpointHigh Pressure Alarm Setpoint High Temperature Alarm ResetLow Supply Voltage Alarm Setpoint Low Pressure Alarm SetpointLow Supply Voltage Alarm Reset Low Temperature Alarm ResetWake Up Interval seconds Uncorrected VolumeTime Hhmmss Hours, Minutes, Seconds Wake Up On Pulse event driven EFCUnits of Measure Flow & VolumeTemperature Differential AccumulationsJanuary SBC Revision a Corrector Board OPT Revision a Option Board Description Jumper positionPulse Input #1 PLI Revision C Phone Line Interface Service Requirement Consumer Information and FCC RequirementsWarranty & Repair Service EL0001 Sheet 1 of 2 Class I Division 2 Installation EL0001 Sheet 2 of 2 Class I Division 2 Installation Warranty Information January Appendix G TII Station Protector January Appendix H Hazardous Area Installation Control Drawings October October