Optiquest iRIS 220 manual I/O Connector, Internal Battery iRIS 320 / iRIS 320V only

Page 16

iRIS 220 / iRIS 320, V1.19 User Guide - 14

3.4 I/O Connector

All I/O and power supply terminations are via 5mm (0.2”) screw terminals provided on a 16-way pluggable connector. The older (V1.1) PCB has a 12 way connector - see Appendix D – Legacy PCB (Rev 1.1) Details. The I/O connector is positioned on the right hand side of the iRIS 320 circuit board, directly above the white battery connector. On the iRIS 220, the connector protrudes through the top of the case.

The function of each I/O termination is shown in the diagram below.

TOP

 

 

AI4

Analog Input #4

 

 

AI3

Analog Input #3

 

AI2

Analog Input #2

 

AI1

Analog Input #1

 

AGND

Analog Common Ground

 

5VOP

5V Reference Output

 

DI2

Digital Input #2

 

DI1

Digital Input #1

 

DO2

Digital Output #2

 

DO1

Digital Output #1

 

SDI-12

SDI-12 Data Bus

 

DGND

Digital Common Ground

 

12V+

12Vdc Internal/External Battery Supply +

 

GND (-) 0Vdc Internal/External Battery Supply -

 

VIN+

15-30Vdc External Power Supply (Charger Input) +

 

GND (-)

0Vdc External Power Supply (Charger Input) -

BOTTOM

Figure 4 - I/O Connector

3.4.1 Internal Battery (iRIS 320 / iRIS 320V only)

The iRIS 320 / iRIS 320V are supplied with an internal rechargeable 12V 0.8A/Hr sealed lead-acid battery. Upon installation, you will need to connect this battery as it is shipped disconnected to preserve battery life. It should also be disconnected if the unit is not going to be used for some time.

NOTE: The iRIS 220 does not have an internal battery, so ignore all references to the internal battery for the iRIS 220 models.

For maximum flexibility, the iRIS I/O connector has two terminals provided for additional 12V power supply flexibility. These terminals (marked 12V+ and GND) can either be used to deliver 12V from the internal battery out to power an external sensor or other small load, or alternatively be connected to an external 12V battery (for greater battery capacity) or a 12V d.c battery charger type power supply. See the next two sections on using the 12V terminals and the external (charger) power supply feature.

WARNING! iRIS 320 / iRIS 320V INTERNAL BATTERY

The +12V and GND terminals of the I/O connector are effectively connected directly in parallel with the internal 12V battery. A resettable semiconductor fuse is fitted for short-circuit protection.

However, only connect 12V lead-acid batteries or a regulated d.c power supply that is designed for charging a 12V lead-acid battery, to these terminals.

Applying a voltage higher than 14.5V for a sustained period to these terminals will permanently damage the internal battery and may cause an acid leak and/or an explosion.

14

iQuest (NZ) Ltd - PO Box 15169, Hamilton, New Zealand Tel: +64 7 857-0810 Fax: +64 7 857-0811 Email: iquest@iquest.co.nz

Image 16
Contents IRIS 220 iRIS Revision History Contents Diagnostic LEDs 13.1 13.213.3 13.4Introduction About this ManualHardware PCB Revision SupportOverview General Characteristics iRISIntroduction IRIS 320 / iRIS Feature Summary FeaturesTypical Applications Technical Specifications iRIS Technical Specifications iRIS 320 / iRIS Key Features Terminal ConfigurationWireless IP Connectivity GPRS/CDMA Alternative Wireless Connectivity CSD/SMSFull Power Save Partial Power SaveData Logging Alarm Processing Logged Data Array IdentificationReal Time Clock & Calendar SecurityInstallation Removing/Replacing the Electronic Assembly iRISOpening / Closing the Housing iRIS 320 / iRIS Removing / fitting the SIM card GSM models onlyI/O Connector Internal Battery iRIS 320 / iRIS 320V onlyExternal Charger Power Supply Internal / External 12V Battery SupplyAnalog Inputs Digital Inputs Digital Input CircuitDigital Outputs Digital Output 1 CircuitAntenna Connection Mounting iRISIRIS 320 / iRIS 320V Mounting Diagram Mounting iRIS 320 / iRISTerminal Connection ConfigurationComputer IRIS Terminal Cfg IRIS 220 / iRIS 320, V1.19 User Guide Terminal Menus Main Menu LevelSelect this option to display the Comms configuration menu Comms Cfg Level Option 9 SDI-12 Terminal iRIS 320 / iRIS 320V only GPRS/CDMA-1X Cfg Level Press Esc then Enter to enter an empty stringGprs Phone List Level IP Acceptance Cfg LevelGPRS/CDMA-1X Schedule Cfg Level Sensor Selection Level Sensor Cfg Level Internal Sensor Sources Log Multiplier 100 100Flag Value Description Mode Name DescriptionSupplementary Logging Flag Definitions Multiplier= Alarm Selection Level Alarm Cfg LevelOutput Selection Level Output Cfg LevelSource 0 1 2 3 4 Description Date/Time Cfg Level Typical Scheduled Output ExampleMiscellaneous Menu Level Voice Menu Level LED Indicators Diagnostic LEDsOperation Status LEDLCD & Keypad iRIS 320 only LCD OperationStatus Icons Keypad ButtonsDisplay Menu Structure Level Level6Log In Screen Level 0, when not logged Logging Control Screen Level 0, when loggedPrimary LCD Display Screens System Status 1 Screen LevelSensor Related Screens System Status 3 Screen LevelSystem Status 4 Screen Level Main Menu Screen LevelSensor Settings Screen 1/5 Process Level Sensor Settings Screen 2/5 Scaling LevelSensor Settings Screen 3/5 Logging Level Sensor Settings Screen 4/5 Alarm 1 LevelTotaliser Related Screens Comms Related Screens Comms Setting Screen 2/8 APN/Local IP Level Comms Setting Screen 3/8 Socket a LevelComms Setting Screen 4/8 Socket B Level Comms Setting Screen 5/8 Schedule 1 LevelComms Setting Screen 6/8 Schedule 2 Level Comms Setting Screen 7/8- CSD Settings LevelComms Setting Screen 8/8 RS232 Settings Level RS232 Port Mode Screen LevelSMS Communication Comms Enable Screen LevelComms Test Screen Level General Hints Iris I/O Connector Connecting a Flow Meter or Rain GaugeSensor Connection Examples Connecting a 0-5V Pressure Transducer 12V BatteryExternal RequiredRequired IRIS I/O Connector Connecting a 2-Wire Loop-Powered 4-20mA SensorSignal 4-20mA Sensor Isolated 12V 24V DC- DC Converter Connecting an Up/Down Water Level Instrument External 12V Battery OptionalConnecting Analogue Wind Instruments Connecting SDI-12 Instruments. iRIS 320 / iRIS 320V only Charging source Solar panelTOP AI4 AI3 AI2 AI1 Agnd 5VOP Analogue Input Scaling Example a 4-20mA Water Level SensorTroubleshooting User Notes Appendix a Radio Using the RS232 Interface Tait TM80xx Radio DB15 MiRIS 3xx / DS-4483 DB9 FIRIS 320 DB9 F DS-IRM Modem DB25 MAppendix B Voice Annunciation iRIS PartitionAppendix C SDI-12 iRIS 320 / 320V only What is SDI-12?Advantages of SDI-12 SDI-12 Electrical Interface Serial Data LineGround Line Volt-LineAppendix D Legacy PCB Rev 1.1 Details 13.1 I/O ConnectorDebounce Links Interface Wire Terminal SDI-12 Bus Function Diagnostic LEDsSDI-12 Interface Transistor Switch Purple Switched OutputSwitch Module REDSupply VoltageApproximate Mechanical Properties Appendix E iRIS 320 Enclosure Material SpecChemical Composition IQuest APN IQuest Global Data Network