SMC Networks EX500 Terminating resistance setting switch SW3, Layout of scanner I/O, Data Rate

Page 21

EX500 Serial System

EX## - OME0008

4 -4 -3. Terminating resistance setting switch ( SW3 )

Set termination resistance.

Data Rate

57.6k bit / sec. : 150Ω

115.2 k bit / sec. : 150Ω

230.4 k bit / sec. : 82Ω

150Ω 82Ω No resistance

State of SW3

4 -5. Layout of scanner I/O

I/O mapping image at the Gateway (GW ) Unit communication port is shown in examples 1 and 2.

In this product, regardless of the quantity of the I/O equipment, continuous 4 Groups are automatically occupied. ( 1/2 RACK occupation ).

Each communication port occupies all of 16 points in corresponding Group.

Ex.1 ) RACK Address = 0

Starting Quarter = First

Bit Number( decimal ) 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1 0

 

RACK0 Group0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIO

RACK0 Group1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOGICAL

RACK0 Group2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0

RACK0 Group3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0 Group4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0 Group5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0 Group6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0 Group7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIO

RACK1 Group1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOGICAL

RACK1 Group2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1

RACK1 Group3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM A occupied COM B occupied COM C occupied COM D occupied

Ex.2 ) RACK Address = 1

Starting Quarter = Third

Bit Number( decimal ) 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1 0

 

RACK0 Group0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIO

RACK0 Group1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOGICAL

RACK0 Group2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0

RACK0 Group3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0 Group4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0 Group5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0 Group6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK0 Group7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIO

RACK1 Group1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOGICAL

RACK1 Group2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1

RACK1 Group3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RACK1 Group7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM A occupied COM B occupied COM C occupied COM D occupied

- 20 -

Image 21
Contents SMC Corporation ・Safety instructions for pneumatic equipment ・Safety instructions for electric equipment・Level of potential hazard ! Caution ・Safety instructions for cables・Safety instructions for power supply Index EX500 Serial System Outline Gateway GW Unit Input / Output UnitSystem Structure Test Procedure Specification Criterion Specification・EMC Directive 89 / 336 / EEC Electromagnetic EmissionHow to Order 5 0 0 G D N Gateway GW Unit specificationDeviceNet communication specification EX500 GDN1 PROFIBUS-DP EN50170 PROFIBUS-DP communication specification EX500 GPR1Input Unit Manifold Input Unit specification1. Input Manifold 2. Input UnitInput Block specification How to Order 5 0 0 I E3. Input Block SI Unit SI Unit specificationApplicable Manifold Valve series SI Unit for SV series Manifold ValveCommunication Connector Cable for DeviceNet EX500 GDN1 Electric specificationCable specification OptionHow to Order 5 0 0 a C 0 3 0 S S P S 2. Branch Cable with M12 Connector3. Power Supply Connector Cable 4. Terminal Plug5. Water Proof Cap ・Representative PLC Parts descriptionOperation setting Display ContentLED display 1. Operation setting switch SW1 2. Operation setting switch SW2Setting Operation Layout of scanner I/O 3. Terminating resistance setting switch SW3Data Rate State of SW3How to operate EX500 GDN1 DeviceNet Connection style ・Wiring length・Cable specification EDO Figure of setting switch 1. Address setting switch SW1 2. Data rate setting switch SW3I/O memory map How to operate EX500 GPR1 PROFIBUS-DP Communication wiring ・Communication speed and Longest wiring length・Terminating resistance DIA 2. Terminating resistance setting switch SW4 1. Address setting switch SW1, 2・In case of corresponding with Word State of SW4・In case of corresponding with Double Word Input Unit Manifold Parts description Power supply must be reset after fixing the short circuitCorrespondence of input number and Input Block Input Unit・Parts list Parts name Parts number Exploded view / Input Unit Manifold・Addition of the Input Block SV series Manifold Valve Parts descriptionVQC series SI Unit for SV series ManifoldCorrespondence of output number and Manifold Valve How to install the SI Unit SI Unit for SV series ManifoldSI Unit for VQC series Manifold Source wiring WiringIndividual power supply Single power supply2. Communication wiring to the SI Unit and the Input Unit Communication wiring 1. Communication wiring to PLCRemote I/O EX500 GAB1 -X1 communication wiring DeviceNet EX500 GDN1 communication wiringDimension 10 -1. Gateway GW Unit 10 -2. Input Unit Manifold ・In case of M8 Input BlockStations ・In case of M12 Input Block 10 -3. Manifold ValveTrouble shooting ・Whole system Remedies・Remote I/O communication Remedies ・PROFIBUS-DP communication Remedies ・DeviceNet communication RemediesStatus of MS LED Status of NS LED