SMC Networks EX500 manual ・EMC Directive 89 / 336 / EEC, Electromagnetic Emission, Specification

Page 8

EX500 Serial System

EX## - OME0008

3. Specification and Product numbers

3 -1. General specification of EX500 series

Item

Specification

 

 

Enclosure

IP65

Standard

UL,CSA,CE

Withstand voltage

1500V AC 1min. ( between PE - external terminal package )

Insulation resistance

2MΩor more

( 500VDC meg. between PE - external terminal package )

 

Momentary power failure

1m sec. or less

Ambient temperature

+5to +45

Ambient humidity

35% to 85%RH ( without condensation )

Preservation temperature

- 25to 70

 

10Hz to 57Hz 0.35mm ( constant amplitude )

Vibration proof

57Hz to 150Hz 5G ( constant speed )

 

2 hours per each direction of ±X,Y and Z

Shock resistance

Peak value : 15G

3 times per each direction of ±X,Y and Z

 

Applicable altitude

Less than 1000m above sea

EMC Directive ( 89 / 336 / EEC )

EN50081-2 / 1993, EN55011 / 1998 +A1 : 1999, EN50082-2 / 1995, EN61000-6-2 / 1999

Electromagnetic Emission

Item

Test Procedure

 

Specification

Criterion

Radiated Electric Field

EN55011 : 1998 +A1

 

30MHz to 230MHz, 230MHz to 1GHz

Group 1

Strength

: 1999

 

( Distance : 10m )

Class A

Electromagnetic Susceptibility ( Immunity )

 

 

Item

Test Procedure

 

Specification

Criterion

ESD

EN61000-4-2 : 1995 /

 

±4kV contact

B

A1 : 1998

 

±8kV air discharge

 

 

 

RS :

EN61000-4-3 : 1996 /

 

80MHz to 1000MHz

 

Radiated Susceptibility

 

A

A1 : 1998

 

10V / m ( 1kHz AM 80% )

( amplitude modulated)

 

 

 

 

 

 

RS :

 

 

900±5MHz

 

Radiated Susceptibility

ENV50204 : 1995

 

10V / m

A

( pulse modulated )

 

 

( 200Hz Pulse Mod. Duty 50% )

 

CS :

 

 

 

 

Conductive

EN61000-4-6 : 1996

 

0.15MHz to 80 MHz

A

Susceptibility

 

10V ( 1kHz AM 80% )

 

 

 

( amplitude modulated)

 

 

 

 

EFT / Burst,

EN61000-4-4 : 1995

 

±2kV

B

DC power lines

 

( 5 / 50ns, 5kHz )

 

 

 

EFT / Burst,

EN61000-4-4 : 1995

 

±2kV

B

control lines

 

( 5 / 50ns, 5kHz )

 

 

 

Surge,

EN61000-4-5 : 1995

 

±1kV ( Common )

B

interface lines

 

 

 

 

 

- 7 -

Image 8
Contents SMC Corporation ・Level of potential hazard ・Safety instructions for pneumatic equipment・Safety instructions for electric equipment ・Safety instructions for cables ! Caution・Safety instructions for power supply Index EX500 Serial System System Structure Outline Gateway GW UnitInput / Output Unit Specification Test Procedure Specification Criterion・EMC Directive 89 / 336 / EEC Electromagnetic EmissionGateway GW Unit specification How to Order 5 0 0 G D NDeviceNet communication specification EX500 GDN1 PROFIBUS-DP communication specification EX500 GPR1 PROFIBUS-DP EN50170Input Unit specification Input Unit Manifold1. Input Manifold 2. Input Unit3. Input Block Input Block specificationHow to Order 5 0 0 I E SI Unit specification SI UnitApplicable Manifold Valve series SI Unit for SV series Manifold ValveElectric specification Communication Connector Cable for DeviceNet EX500 GDN1Cable specification Option2. Branch Cable with M12 Connector How to Order 5 0 0 a C 0 3 0 S S P S5. Water Proof Cap 3. Power Supply Connector Cable4. Terminal Plug Parts description ・Representative PLCLED display Operation settingDisplay Content Setting Operation 1. Operation setting switch SW12. Operation setting switch SW2 3. Terminating resistance setting switch SW3 Layout of scanner I/OData Rate State of SW3・Cable specification How to operate EX500 GDN1 DeviceNet Connection style・Wiring length EDO Figure of setting switch I/O memory map 1. Address setting switch SW12. Data rate setting switch SW3 ・Terminating resistance How to operate EX500 GPR1 PROFIBUS-DP Communication wiring・Communication speed and Longest wiring length DIA 1. Address setting switch SW1, 2 2. Terminating resistance setting switch SW4・In case of corresponding with Word State of SW4・In case of corresponding with Double Word Power supply must be reset after fixing the short circuit Input Unit Manifold Parts descriptionCorrespondence of input number and Input Block Input Unit・Addition of the Input Block ・Parts list Parts name Parts numberExploded view / Input Unit Manifold Manifold Valve Parts description SV seriesVQC series SI Unit for SV series ManifoldCorrespondence of output number and Manifold Valve SI Unit for VQC series Manifold How to install the SI UnitSI Unit for SV series Manifold Wiring Source wiringIndividual power supply Single power supplyCommunication wiring 1. Communication wiring to PLC 2. Communication wiring to the SI Unit and the Input UnitRemote I/O EX500 GAB1 -X1 communication wiring DeviceNet EX500 GDN1 communication wiringStations Dimension 10 -1. Gateway GW Unit 10 -2. Input Unit Manifold・In case of M8 Input Block 10 -3. Manifold Valve ・In case of M12 Input Block・Remote I/O communication Remedies Trouble shooting・Whole system Remedies ・DeviceNet communication Remedies ・PROFIBUS-DP communication RemediesStatus of MS LED Status of NS LED