EX500 Serial SystemEX## - OME0008
・DeviceNet communication
NO. | Item | Remedies | |
1 | The status of MS LED | ・Check the signal line from PLC is properly connected. | |
| Operating in a normal condition | ( Refer to section 5 | |
| Recoverable fault | : Green lights | ・Check Wiring and pin out. |
|
| ( Refer to section 3 | |
| ( Memory is abnormal ) : Red lights | ・Check communication speed and Address setting switch | |
|
|
| are correctly set. |
|
|
| ( Refer to section 5 |
2 | The status of NS LED | ・Check the signal line from PLC is properly connected. | |
| Not online | : Lights off | ( Refer to section 5 |
| Online , Not Allocated | ・Check wiring and pin out. | |
|
| : Green flashing | ( Refer to section 3 |
| Online , Allocated | : Green lights | ・Check communication speed and Address setting switch |
| Connection Time - Out | are correctly. ( Refer to section 5 | |
|
| : Red flashing | |
|
|
| |
| Critical Link Failure : Red lights |
| |
3 | SOL LED lights off. |
| ・Check power supply to make sure that 24VDC is supplied |
|
|
| to solenoid valve. ( Refer to section 9 |
|
|
| ・Check power supply to solenoid valves is not less |
|
|
| than 20VDC. |
|
| ||
NO. | Item | Remedies | |
1 | RUN LED lights off. |
| ・Check the power supply is supplying 24V DC. |
|
|
| ( Refer to section 9 |
2 | BF LED lights. |
| ・Check the signal line from PLC is properly connected. |
|
|
| ( Refer to section 6 |
|
|
| ・Check wiring and pin out. |
|
|
| ( Refer to section 3 |
|
|
| ・Check Address setting switch is correctly set. |
|
|
| ( Refer to section 6 |
|
|
| ・Check the terminating resistance is correctly set. |
|
|
| ( Refer to section 6 |
3 | DIA LED lights. |
| ・Check the power supply for the solenoid valve is supplying. |
|
|
| ( Refer to section 9 |
|
|
| ・Check the power supply for the solenoid valve is not less |
|
|
| than 20VDC. |
4 | SOL LED lights off. |
| ・Check the power supply for the solenoid valve is supplying. |
|
|
| ( Refer to section 9 |
|
|
| ・Check the power supply for the solenoid valve is not less |
|
|
| than 20VDC. |
This technical instruction manual is the day of March, 2001 present one.
Specifications are subjected to change without any notice. Manufacture does not assume any liability arising out of application of any product specified in this manual.
- 39 -