SMC Networks EX500 Trouble shooting, ・Whole system Remedies, ・Remote I/O communication Remedies

Page 39

EX500 Serial System

EX## - OME0008

11. Trouble shooting

Whole system

NO.

Item

Remedies

1

The solenoid valve does not work.

Check the power supply for the solenoid valve is supplying

 

 

24VDC. ( Refer to section 9 -1 )

 

 

Check the Branch Cable with M12 Connector is properly

 

 

connected with the SI Unit. ( Refer to section 8 -1 )

 

 

Check the Power LED and the Communication LED of

 

 

the SI Unit light up. ( Refer to section 8 -1 )

2

The solenoid valve does not work

Check the wiring specification of Manifold Block Ass'y.

 

as in the program.

( Refer to section 8 -2 )

3

The Power LED of the Input Unit

There is possibility that the input sensor has a short-circuit .

 

is flashing.

Check that the sensor is not bad.

 

 

Check the power supply for a possibility that the current in

 

 

power supply line is above the specification.

4

Connecting sensor does not start

Check the power supply to make sure that 24VDC is

 

signal.

supplied. ( Refer to section 9 -1 )

 

 

Check whether or not the Indicator LED of each block

 

 

lights up. ( Refer to section 7 -1 )

5

COM A - D does not light.

Check whether or not the Input Unit is connected with the

 

 

branch of the COM port which does not light up.

 

 

Check the Branch Cable with M12 Connector is properly

 

 

connected with the Input Unit. ( Refer to section 7 -1 )

 

 

Check that a Terminal Plug is connected with port C1 or C0

 

 

if Input Unit Manifold, is not connected.

 

 

( Refer to section 9 -2 -2 )

Remote I/O communication

 

NO.

Item

Remedies

1

RUN LED lights off.

Check the power supply is supplying 24VDC.

 

 

( Refer to section 9 -1 )

2

COM LED lights off.

Check the signal line from PLC is properly connected.

 

ERR LED lights.

( Refer to section 4 -2 )

 

 

Check wiring and pin out. ( Refer to section 3 -2 )

 

 

Check the RACK Address is correctly set.

 

 

( Refer to section 4 -4 -1 )

 

 

Check Starting Quarter is correctly set.

 

 

( Refer to section 4 -4 -1 )

 

 

Check Data Rate is correctly set.

 

 

( Refer to section 4 -4 -2 )

 

 

Check Last RACK is correctly set.

 

 

( Refer to section 4 -4 -2 )

 

 

Check the terminating resistance is correctly set.

 

 

( Refer to section 4 -4 -3 )

3

SOL LED lights off.

Check the power supply for 24VDC ( Refer to section 9 -1 )

 

 

Check the power supply for the solenoid valve is not less

 

 

than 20V.

- 38 -

Image 39
Contents SMC Corporation ・Safety instructions for pneumatic equipment ・Safety instructions for electric equipment・Level of potential hazard ! Caution ・Safety instructions for cables・Safety instructions for power supply Index EX500 Serial System Outline Gateway GW Unit Input / Output UnitSystem Structure Electromagnetic Emission SpecificationTest Procedure Specification Criterion ・EMC Directive 89 / 336 / EECHow to Order 5 0 0 G D N Gateway GW Unit specificationDeviceNet communication specification EX500 GDN1 PROFIBUS-DP EN50170 PROFIBUS-DP communication specification EX500 GPR12. Input Unit Input Unit specificationInput Unit Manifold 1. Input ManifoldInput Block specification How to Order 5 0 0 I E3. Input Block SI Unit for SV series Manifold Valve SI Unit specificationSI Unit Applicable Manifold Valve seriesOption Electric specificationCommunication Connector Cable for DeviceNet EX500 GDN1 Cable specificationHow to Order 5 0 0 a C 0 3 0 S S P S 2. Branch Cable with M12 Connector3. Power Supply Connector Cable 4. Terminal Plug5. Water Proof Cap ・Representative PLC Parts descriptionOperation setting Display ContentLED display 1. Operation setting switch SW1 2. Operation setting switch SW2Setting Operation State of SW3 3. Terminating resistance setting switch SW3Layout of scanner I/O Data RateHow to operate EX500 GDN1 DeviceNet Connection style ・Wiring length・Cable specification EDO Figure of setting switch 1. Address setting switch SW1 2. Data rate setting switch SW3I/O memory map How to operate EX500 GPR1 PROFIBUS-DP Communication wiring ・Communication speed and Longest wiring length・Terminating resistance DIA State of SW4 1. Address setting switch SW1, 22. Terminating resistance setting switch SW4 ・In case of corresponding with Word・In case of corresponding with Double Word Input Unit Power supply must be reset after fixing the short circuitInput Unit Manifold Parts description Correspondence of input number and Input Block・Parts list Parts name Parts number Exploded view / Input Unit Manifold・Addition of the Input Block SI Unit for SV series Manifold Manifold Valve Parts descriptionSV series VQC seriesCorrespondence of output number and Manifold Valve How to install the SI Unit SI Unit for SV series ManifoldSI Unit for VQC series Manifold Single power supply WiringSource wiring Individual power supplyDeviceNet EX500 GDN1 communication wiring Communication wiring 1. Communication wiring to PLC2. Communication wiring to the SI Unit and the Input Unit Remote I/O EX500 GAB1 -X1 communication wiringDimension 10 -1. Gateway GW Unit 10 -2. Input Unit Manifold ・In case of M8 Input BlockStations ・In case of M12 Input Block 10 -3. Manifold ValveTrouble shooting ・Whole system Remedies・Remote I/O communication Remedies Status of NS LED ・DeviceNet communication Remedies・PROFIBUS-DP communication Remedies Status of MS LED