Omega WI8XX-U manual Display Color Examples

Page 52

4.3.7.5.1Display Color Examples

Example 1:

Output 1 & Output 2 = SSR

Alarm Setup: Absolute, Above, Alarm 2 HI Value "ALR.H" = 200, Alarm 1 HI Value "ALR.H" = 400

"Color Display" Setup: Normal Color “N.CLR” = Green,

Alarm 1 Color "1.CLR" = Amber, Alarm 2 Color "2.CLR" = Red

Display Colors change sequences:

•--

------------------------------GREEN

-----------------------------

 

RED

 

•------------------------------

AMBER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

AL2.H = 200

 

AL1.H = 400

 

 

 

 

Example 2:

 

 

 

= Pulse

 

 

 

 

 

 

 

 

 

Output 1 & Output 2

 

 

 

 

 

" = 300,

 

Alarm Setup: Absolute, Below, Alarm 2 Low Value "

ALR.L

 

 

 

 

: "

 

 

" = Green, "

 

" =

 

 

 

 

Alarm 1 Low Value "

ALR.L

" = 100

 

 

 

 

 

 

 

 

Color Display Setup

 

 

 

 

 

 

Amber, "

 

" = Red

 

 

 

 

N.CLR

 

 

1.CLR

2.CLR

Display Colors change

 

 

 

 

 

 

 

 

 

 

 

 

 

sequences:

 

 

 

 

 

 

 

 

--------------• AMBER •----------------------------------

RED

 

 

•-------------------------------------------

 

GREEN

 

 

--•

0

AL1.L = 100

 

 

 

 

 

 

AL2.L = 300

 

 

 

 

 

 

46

Image 52
Contents User’sGuide Page Table of Contents List of Figures 19a List of Tables Safety Considerations Part IntroductionCustomer Service Before You BeginDescription Inspecting Your ShipmentDescription Rockwell Automation, and National Instruments, among others Physical Characteristics and Mounting 2.1.1 Front Panel Front Panel EnunciatorsRear Panel Rear Panel ConnectorNetwork Dimensions Mounting DimensionsAssembly and Mounting 2.1.4.1 Panel Mounting Instruction Panel MountingAntenna Mounting Instruction Antenna MountingDisassembly Instruction Accessing the Main Board AssemblyElectrical Installation Power Connections Use copper conductors only for power connectionsWiring Outputs Outputs Wiring HookupOutputs Wiring Hookup Pulse and AnalogTypical Applications Fast BlowJumper Settings for Display Color Setup 10 Location of S1 JumperDip Switches PositionNetwork Communication Interfaces 1 10Base-T RJ-45 Pinout Pin Name DescriptionNetwork Protocols .1 Label Detail Ethernet MAC AddressDhcp 4 Position DIP Switch DNSDefault IP Address IP AddressChanging TCP/IP Properties on Your Computer SectionTesting the Connection Pinging the Meter from MS-DOS PromptAssigning an IP Address using iConnect IConnect SoftwareWireless Sensor Home Setting a New IP Address over the Network Access ControlMeter’s Configurations and Operations Wireless System Home Page MenuLogin Administrator Power Up MeterGet Readings from the End Device LabGet Readings from the End Device ID End Device ID/address Java Runtime Environment Setup Java 1.5.x.x. Screen ShotsJava Runtime Environment 1.4 Setup Instructions 10 Java 1.4.2.x Screen ShotAccessing Meter units within your internal network Accessing Meter units using the internetDiagnostics Accessing Meter units over Peer-to-Peer networkJava Policy 11 Java PolicyDjava.security.policy=C\0JAVAPOLICY\javapolicy.txt 12 Java PolicyChart 13 ChartChart Controller Setup 14 Controller SetupSetup Transmission PowerMonitor MiscellaneousSetup InputSetpoints & On/Off Control Setpoints & On/Off Control Alarms 1 Setup Setup Analog Output RetransmissionDisplay 19a Display Menu19b Display Menu if Analog Output Option Display Color Examples ExampleAmber Passcode ID 20 ID CodeNetwork Setup Remote Access TunnelingGeneral Terminal ServerGeneral Remote AccessTerminal Server End Device Setup 22 End Device SetupEnd Device Parameters Sensor1 Sensor2Sensor T75F T74FCancel UpdateDisplay Access Control List of Ascii / Telnet Commands 01 indicates End Device #1 Telnet SetupCommand Description Response HTTPget using Port HTTPget ProgramConnector/Transmitter Types HTTPget and ARP to Setup Device IP Address27 ARP Commands and Responses ARP ProtocolILog Software 28 iLog Software Logging Data for End Device #2, 6Wireless Devices ILog Software ILog Excel ApplicationsNetworked Product ILog File Alternate Networked Product Auto FullInstallation Mail Notifier SoftwareEmail Address Setup Email SetupDevice Setting and Configuration Mail Notifier CommandsAlarm Editor Environment / Operating Conditions General Deployment GuidelinesOperation in Buildings With Line-of-Sight Distance feetWithout Line-of-Sight Casing and Closure Around the AntennaMaterial Type See .1.4.2 and FigurePart Specifications General Safety & Regulatory Compliance Factory Preset Values InputAlarm Factory Preset Values Setpoints & On/Off ControlPasscode ID Factory Preset Values Analog Output Retransmission Remote Access TunnelingAccess Control MiscFactory Preset Values End Device Setup End Device # 1Appendix Aglossary Appendix BIP Address Address Class Mask Binary Value Mask Decimal Value Ascii Dec Hex Ctrl Key Ascii Control Codes Definition Appendix E ILog Error Messages Error # Description Maximum Power Levels and Antenna Gains WARRANTY/DISCLAIMER Shop on line at omega.com PH/CONDUCTIVITY