Page 75

5.2 With Line-of-Sight

When installing the Meter it is important to position your device in such a way to optimize the antenna location within what’s known as the "Fresnel Zone".

The Fresnel Zone can be thought of as a football-shaped invisible tunnel between two locations that provides a path for RF signals between the End Device and the Meter.

Figure 5.2 Fresnel Zone

In order to achieve maximum range, the football-shaped path in which radio

waves travel must be free of obstructions. Obstacles in the path (especially

metal) will decrease the communication range between the End Device and

Meter.

 

Also, if the antennas are mounted just barely off the ground or below the ceiling,

over half of the Fresnel zone ends up being obstructed resulting in significant

reduction in range.

 

Below is the calculated radius of the football-shaped tunnel for different distance

range:

 

Distance (feet)

Radius (feet)

100

3.2

200

4.5

300

5.5

It is recommended that within the tunnel of the above radius, at least 60% of space is free of obstruction.

Since signal reaches destination directly in a line-of-sight situation, it is important to adjust the antenna properly to achieve maximum performance. Antenna for the Meter and End Device should be perpendicular to the plane where the Meter and End Device is located.

69

Image 75
Contents User’sGuide Page Table of Contents List of Figures 19a List of Tables Part Introduction Safety ConsiderationsInspecting Your Shipment Customer ServiceBefore You Begin DescriptionDescription Rockwell Automation, and National Instruments, among others Front Panel Enunciators Physical Characteristics and Mounting 2.1.1 Front PanelRear Panel Connector Rear PanelNetwork Mounting Dimensions DimensionsPanel Mounting Assembly and Mounting 2.1.4.1 Panel Mounting InstructionAntenna Mounting Antenna Mounting InstructionAccessing the Main Board Assembly Disassembly InstructionUse copper conductors only for power connections Electrical Installation Power ConnectionsPulse and Analog Wiring OutputsOutputs Wiring Hookup Outputs Wiring HookupFast Blow Typical Applications10 Location of S1 Jumper Jumper Settings for Display Color SetupPosition Dip SwitchesPin Name Description Network Communication Interfaces 1 10Base-T RJ-45 PinoutEthernet MAC Address Network Protocols .1 Label DetailDhcp DNS 4 Position DIP SwitchIP Address Default IP AddressSection Changing TCP/IP Properties on Your ComputerPinging the Meter from MS-DOS Prompt Testing the ConnectionIConnect Software Assigning an IP Address using iConnectWireless Sensor Home Access Control Setting a New IP Address over the NetworkWireless System Home Page Menu Meter’s Configurations and OperationsPower Up Meter Login AdministratorLab Get Readings from the End DeviceGet Readings from the End Device ID End Device ID/address Java 1.5.x.x. Screen Shots Java Runtime Environment Setup10 Java 1.4.2.x Screen Shot Java Runtime Environment 1.4 Setup InstructionsAccessing Meter units over Peer-to-Peer network Accessing Meter units within your internal networkAccessing Meter units using the internet Diagnostics11 Java Policy Java Policy12 Java Policy Djava.security.policy=C\0JAVAPOLICY\javapolicy.txt13 Chart ChartChart 14 Controller Setup Controller SetupMiscellaneous SetupTransmission Power MonitorInput SetupSetpoints & On/Off Control Setpoints & On/Off Control Alarms 1 Setup Analog Output Retransmission Setup19a Display Menu Display19b Display Menu if Analog Output Option Example Display Color ExamplesAmber 20 ID Code Passcode IDTerminal Server Network SetupRemote Access Tunneling GeneralRemote Access GeneralTerminal Server 22 End Device Setup End Device SetupEnd Device Parameters Sensor2 Sensor1T75F T74F SensorUpdate CancelDisplay Access Control Telnet Setup List of Ascii / Telnet Commands 01 indicates End Device #1Command Description Response HTTPget Program HTTPget using PortHTTPget and ARP to Setup Device IP Address Connector/Transmitter TypesARP Protocol 27 ARP Commands and Responses28 iLog Software Logging Data for End Device #2, 6 ILog SoftwareNetworked Product Auto Full Wireless DevicesILog Software ILog Excel Applications Networked Product ILog File AlternateMail Notifier Software InstallationEmail Setup Email Address SetupMail Notifier Commands Device Setting and ConfigurationAlarm Editor General Deployment Guidelines Environment / Operating ConditionsOperation in Buildings Distance feet With Line-of-SightSee .1.4.2 and Figure Without Line-of-SightCasing and Closure Around the Antenna Material TypePart Specifications General Safety & Regulatory Compliance Input Factory Preset ValuesFactory Preset Values Setpoints & On/Off Control AlarmPasscode ID Misc Factory Preset Values Analog Output RetransmissionRemote Access Tunneling Access ControlEnd Device # 1 Factory Preset Values End Device SetupAppendix Aglossary Appendix BIP Address Address Class Mask Binary Value Mask Decimal Value Ascii Dec Hex Ctrl Key Ascii Control Codes Definition Appendix E ILog Error Messages Error # Description Maximum Power Levels and Antenna Gains WARRANTY/DISCLAIMER PH/CONDUCTIVITY Shop on line at omega.com