PART 6 |
|
SPECIFICATIONS |
|
ON/OFF CONTROL OUTPUT 1 & 2 | |
Relay: | 250 Vac or 30 Vdc @ 3 A (Resistive Load), SPDT |
Solid State Relay (SSR): | 20 to 265 Vac @ 0.05 to 0.5 A (Resistive Load); |
DC Pulse: | continuous |
Analog Output (Output 1 only) | |
Operation: | max |
Direct (cool), reverse (heat); deadband; single | |
Configuration | sensing input |
Output 1 and 2 can be configured as Alarm 1 | |
| and 2, respectively. Analog Output for Output 1 |
| can be configured as retransmission. |
ALARM 1 & 2 (PROGRAMMABLE) | |
Type: | SPDT Relay, SSR, and DC Pulse |
Operation: | High/low, above/below, band, latch/unlatch, |
| normally open/normally closed and |
| process/deviation; front panel configurations; |
| single/multiple sensing input(s) |
ANALOG RETRANSMISSION OUTPUT (PROGRAMMABLE) | |
Type: | |
Operation: | 0 to 20 mA, 500 Ω max (Output 1 only). |
Single sensing input; accuracy is + 1% of FS | |
| when following conditions are satisfied: |
1) Input is not scaled below 1% of Input FS.
2) Analog Output is not scaled below 3% of Output FS.
2300 Vac per 1 min. test
1500 Vac per 1 min. test
(Low Voltage/Power Option)
2300 Vac per 1 min. test
2300 Vac per 1 min. test
Programmable
71