Faults on the I/O Link

A.The Series 90±30 PLC, Series 90±70 PLC, and Power Mate CNC without a separate encoder port handle faults as described below. The following information applies only if there are no other types of devices on the link.

If one of the following faults occurs, communications stop at the fault location. If there are prior devices on the link, they are still able to transfer data with the master. If there are subsequent devices on the link, however, they cannot.

H Power is removed from any device.

H There is a fault in the I/O Link cable such as an open or shorted wire.

H A module fault, software fault, or hardware fault occurs in the master or slave.

MASTER

SLAVE

1

POWER

REMOVED

HERE

SLAVE

2

SLAVE

3

DATA

If the master is a Series 90±70 PLC and one of the following faults occurs, communications continue on the rest of the link.

HA slave has been set up for the wrong amount of data.

HA Series 90±30 slave is in Stop mode.

HThe sequence of slaves on the link is not the same as the sequence expected by the master.

MASTER

SLAVE

1

PLACED IN STOP MODE

SLAVE

2

a45011

SLAVE

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B. If the link is connected to any other type of device, including a Power Mate CNC

 

 

that has a separate encoder port, a fault on any device causes the entire link to shut

 

down as a safety precaution. If that happens, follow this procedure to restore link

 

 

operation.

 

 

1.

Correct the condition that caused the fault.

 

 

2.

With the master inactive on the link, clear system errors by power cycling each

 

 

 

CNC slave (turn power off, then on again).

 

 

3.

Cycle power to each Series 90±30 I/O Link module, to clear the Logicmaster

 

 

 

fault table.

 

 

4.

Reset the I/O link from the master.

 

12

Series 90t-70 I/O Link Interface Module User's Manual ± February 1993

GFK-0644A

Image 16
Contents GE Fanuc Automation GFL±002 Related Publications Content of this ManualWe Welcome Your Comments and Suggestions Contents Chapter Introduction System OverviewMaster or Slave Operation Application Software Module Description LEDsReset Pushbutton Module SpecificationsSerial Ports Cable Types for the I/O Link CatalogNumberCable Lengths on the I/O Link Optical Adapter Operation of the I/O Link Input and Output DataData Sent by the Master Data Returned by SlavesInputs and Outputs Hold Last State Faults on the I/O Link Diagnostics Link ControlGetting Started Install the module and complete the I/O LinkComplete the program logic for the I/O Link Module Chapter Installation Installing the I/O Link Interface Module in the RackRemoving the I/O Link Interface Module from the Rack LED Name LED Status IndicationPorts on the I/O Link Module Connecting the I/O Link Interface Module to Other DevicesLink Module Used as a Master Link Module Used as a Slave Serial Port Pin AssignmentsOrder of the Devices on the Link Cable Diagram, No Optical Adapter Cable Diagram, Electrical Cable to Optical Adapter Optical Adapter InstallationCable Connections Chapter Logicmaster 90-70 Configuration Configuration StepsGFK-0644A Chapter Programming Guide OverviewSelecting a Program Block Adding the Program Block Logic to an Application ProgramCalling the Program Block Using Multiple Calls to the Program BlockExample Call Instruction Program %P References for the I/O Link Program Blocks 3rdModule 4thModuleUsing Nicknames for the %P References Global %G References for the I/O Link Program BlocksConfiguring I/O Links Configuration Logic, ExampleConfiguration Guidelines Specify the Number of I/O Link ModulesSet Master or Slave Mode bit Reset or Stop bitControlling the I/O Link Module Start/Restart bitDisable or Enable the Input Update bit Disable or Enable the Output Update bitMonitor the Module bit Monitoring Link OperationMonitor Communications Status bit Monitor for an Invalid Configuration or Link Fault bit Monitor for Link Failure bitError Codes Troubleshooting Error Description RecommendedAction CodeConfiguration Error Codes Index GFK-0644A Index