Configuring I/O Links
In the application program, use Move and Block Move instructions to configure the I/O Links in the system by placing the required data in the appropriate %P program references.
Configuration Logic, Example
Use Move instructions to supply the number of I/O Link Interface Modules (1), and the rack location (0), and slot location (5) of that module.
+±±±±±+ | +±±±±±+ | +±±±±±+ | ||||
+±±±±±±±±+MOVE_+±±±±±±±±±±±±±±±±±+MOVE_+±±±±±±±±±±±±±±±±±+MOVE_+± | ||||||
INT | INT | INT | ||||
NUMLINK | L1RACK | L1SLOT | ||||
CONST ±+IN | Q+±%P00001 | CONST ±+IN | Q+±%P00002 | CONST ±+IN | Q+±%P00003 | |
+00001 LEN | +00000 LEN | +00005 LEN | ||||
00001 | 00001 | 00001 | ||||
+±±±±±+ | +±±±±±+ | +±±±±±+ | ||||
|
|
|
|
|
|
Block Move instructions can supply the data lengths and beginning %I and %Q addresses for six slaves on the link, which is link 1 in this example.
+±±±±±+ |
| +±±±±±+ |
| +±±±±±+ | ||||
+±±±±±±±±+BLKMV+±±±±±±±±±±±±±±±±±+BLKMV+±±±±±±±±±±±±±±±±±+BLKMV+± | ||||||||
INT |
| INT |
| INT | ||||
L1DEV0 |
| L1DEV2 |
| L1DEV4 | ||||
CONST ±+IN1 Q+±%P00006 | CONST ±+IN1 Q+±%P00012 | CONST ±+IN1 Q+±%P00018 | ||||||
+00032 LEN | +00032 | LEN | +00032 | LEN | ||||
00001 |
| 00001 |
| 00001 | ||||
|
| |||||||
CONST ±+IN2 | CONST ±+IN2 | CONST ±+IN2 | ||||||
+00001 | +00097 | +00151 | ||||||
|
| |||||||
CONST ±+IN3 | CONST ±+IN3 | CONST ±+IN3 | ||||||
+00001 | +00097 | +00151 | ||||||
|
| |||||||
CONST ±+IN4 | CONST ±+IN4 | CONST ±+IN4 | ||||||
+00064 | +00032 | +00064 | ||||||
|
| |||||||
CONST ±+IN5 | CONST ±+IN5 | CONST ±+IN5 | ||||||
+00033 | +00129 | +00215 | ||||||
|
| |||||||
CONST ±+IN6 | CONST ±+IN6 | CONST ±+IN6 | ||||||
+00033 | +00129 | +00215 | ||||||
|
| |||||||
CONST ±+IN7 | CONST ±+IN7 | CONST ±+IN7 | ||||||
+00000 | +00000 | +00000 | ||||||
+±±±±±+ |
| +±±±±±+ |
| +±±±±±+ | ||||
|
|
|
|
|
|
|
|
|
The first Block Move configures the length and beginning %I and %Q addresses of devices 0 and 1. The second Block Move configures devices 2 and 3. The third Block Move configures devices 4 and 5. To simplify programming, IN7 in these Block Moves is not used. If there were more I/O Links, or more devices on link 1, they would be configured in the same manner.