Page 24

2

Optical Adapter Installation

The Optical Adapter is an optional component used to interface the electrical cable to optical cable.

An Optical Adapter must be installed in a sealed enclosure. Avoid contact with other electrical components or wiring, which could short the unit. Use the adapter's casing screws to make earth ground connection. The electrical potential of the earth ground used for the adapter must be the same as that of the I/O Link to which it is connected.

Cable Connections

Connection between two optical adapters is made using optical fiber cable A66L±6001±009. Lengths of 10 to 100 meters are available. Connect the optical fiber cable to COP1 on the adapter unit.

UNIT

JD1A

ELECTRICAL

CABLE

OPTICAL I/O LINK ADAPTOR

JD1 COP1

OPTICAL CABLE

OPTICAL I/O LINK ADAPTOR

COP1 JD1

a45014

UNIT

ELECTRICAL

CABLE

JD1B

Connection between a master or slave device and an Optical Adapter is made using electrical cable A03B±0807±K803, which is a one±meter cable with connectors on both ends. Connect this cable to JD1 on the adapter. A connection diagram is shown below.

Cable Diagram, Electrical Cable to Optical Adapter

Cable A03B±0807±K803 provides the +5±volt signal required by the Optical Adapter. Do not use this cable to directly connect master or slave devices; use it only with an Optical Adapter.

 

 

 

 

 

UNIT SIDE

 

 

 

 

 

JD1A, JD1B

 

 

 

 

 

 

 

01

SIN

11

0V

 

SIN

(01)

02

SIN *

12

0V

 

*SIN

(02)

 

SOUT

(03)

03

SOUT

13

0V

 

 

*SOUT

(04)

04

SOUT *

14

0V

 

+%V

(09)

 

 

 

 

 

+5V

(18)

05

 

15

0V

 

 

 

+5V

(20)

06

 

16

0V

 

 

 

0V

(11)

07

 

17

 

 

0V

(12)

 

 

 

 

 

0V

(13)

08

 

18

+5V

 

 

 

0V

(14)

09

+5V

19

 

 

 

 

0V

(15)

10

 

20

+5V

 

0V

(16)

 

 

 

 

 

 

 

a45020

ADAPTER SIDE

JD1

(03) SOUT

(04) SOUT*

(01) SIN

(02) SIN*

(09) +5V

(18) +5V

(20) +5V

(11)0V

(12)0V

(13)0V

(14)0V

(15)0V

(16)0V

Note

The +5±volt output on the Series 90±70 I/O Link Module is fused with a 0.5 Amp fuse. The fuse is not field replaceable.

20

Series 90t-70 I/O Link Interface Module User's Manual ± February 1993

GFK-0644A

Image 24
Contents GE Fanuc Automation GFL±002 Content of this Manual Related PublicationsWe Welcome Your Comments and Suggestions Contents Chapter Introduction System OverviewMaster or Slave Operation Application Software Module Description LEDsModule Specifications Reset PushbuttonSerial Ports Cable Types for the I/O Link CatalogNumberCable Lengths on the I/O Link Optical Adapter Operation of the I/O Link Input and Output DataData Sent by the Master Data Returned by SlavesInputs and Outputs Hold Last State Faults on the I/O Link Diagnostics Link ControlInstall the module and complete the I/O Link Getting StartedComplete the program logic for the I/O Link Module Chapter Installation Installing the I/O Link Interface Module in the RackRemoving the I/O Link Interface Module from the Rack LED Name LED Status IndicationConnecting the I/O Link Interface Module to Other Devices Ports on the I/O Link ModuleLink Module Used as a Master Serial Port Pin Assignments Link Module Used as a SlaveOrder of the Devices on the Link Cable Diagram, No Optical Adapter Optical Adapter Installation Cable Diagram, Electrical Cable to Optical AdapterCable Connections Chapter Logicmaster 90-70 Configuration Configuration StepsGFK-0644A Chapter Programming Guide OverviewSelecting a Program Block Adding the Program Block Logic to an Application ProgramUsing Multiple Calls to the Program Block Calling the Program BlockExample Call Instruction Program %P References for the I/O Link Program Blocks 3rdModule 4thModuleUsing Nicknames for the %P References Global %G References for the I/O Link Program BlocksConfiguring I/O Links Configuration Logic, ExampleConfiguration Guidelines Specify the Number of I/O Link ModulesSet Master or Slave Mode bit Reset or Stop bitControlling the I/O Link Module Start/Restart bitDisable or Enable the Input Update bit Disable or Enable the Output Update bitMonitoring Link Operation Monitor the Module bitMonitor Communications Status bit Monitor for an Invalid Configuration or Link Fault bit Monitor for Link Failure bitError Codes Troubleshooting Error Description RecommendedAction CodeConfiguration Error Codes Index GFK-0644A Index