Error Codes: Troubleshooting

The less significant byte of an I/O Link status register contains an error code supplied by the Program Block. Error codes are listed below and on the next page.

Error

Description of

RecommendedAction

Code

Error

 

 

 

 

0

No error

None

 

 

 

1

I/OLinkmodule

Reset the module by pressing the pushbutton or cycling power. If the

 

hardware fault

problem persists, replace the module.

 

 

 

2

ExternalI/Olink

This fault can be caused by pressing the Reset pushbutton while the link is

 

failure

operating. If that is not the cause, inspect all cabling and examinecarefully

 

 

each link device. Reset the link. If the problem persists, remove devices

 

 

from the link one at a time to isolate the defective unit. This error code may

 

 

also be caused by a hardware problem on the I/O Link Interface Module.

 

 

 

3

Configuration error

Try to reinitialize the link interface. If the problem persists, contact the GE

 

 

Fanuc PLC service hotline (phone number: 1±800±978±5747).

 

 

 

4

Link interface is not

Check that the I/O Link Interface Module is installed in the rack and slot

 

responding

location specified in the %P configuration data. Also determine if the

 

 

module is inserted completely in the backplane, and the VME bus is

 

 

operating to other modules in that rack. Make sure that the Logicmaster

 

 

configuration has been correctly completed for the module as described in

 

 

chapter 4. Reset the module by cycling power on the rack. If the problem

 

 

persists, replace the link module.

 

 

 

6

Link Reset

This code indicates that a reset has occurred, or that the application program

 

 

has reset the link by writing a 1 to control bit 13. The fault bit (status bit 12)

 

 

is not set. The I/O Link Module automatically resets control bit 13 to 0 to

 

 

acknowledge that it has received the command.

 

 

 

9

Invalid Number of

This code means that the number of I/O Link Interface Modules is not in the

 

I/OLinkModules

range of 0±2 or 0±4, as specified in program reference %P0001.

 

 

 

34

Series 90t-70 I/O Link Interface Module User's Manual ± February 1993

GFK-0644A

Image 38
Contents GE Fanuc Automation GFL±002 We Welcome Your Comments and Suggestions Content of this ManualRelated Publications Contents Chapter Introduction System OverviewMaster or Slave Operation Application Software Module Description LEDsSerial Ports Module SpecificationsReset Pushbutton Cable Types for the I/O Link CatalogNumberCable Lengths on the I/O Link Optical Adapter Operation of the I/O Link Input and Output DataData Sent by the Master Data Returned by SlavesInputs and Outputs Hold Last State Faults on the I/O Link Diagnostics Link ControlComplete the program logic for the I/O Link Module Install the module and complete the I/O LinkGetting Started Chapter Installation Installing the I/O Link Interface Module in the RackRemoving the I/O Link Interface Module from the Rack LED Name LED Status IndicationLink Module Used as a Master Connecting the I/O Link Interface Module to Other DevicesPorts on the I/O Link Module Order of the Devices on the Link Serial Port Pin AssignmentsLink Module Used as a Slave Cable Diagram, No Optical Adapter Cable Connections Optical Adapter InstallationCable Diagram, Electrical Cable to Optical Adapter Chapter Logicmaster 90-70 Configuration Configuration StepsGFK-0644A Chapter Programming Guide OverviewSelecting a Program Block Adding the Program Block Logic to an Application ProgramExample Call Instruction Using Multiple Calls to the Program BlockCalling the Program Block Program %P References for the I/O Link Program Blocks 3rdModule 4thModuleUsing Nicknames for the %P References Global %G References for the I/O Link Program BlocksConfiguring I/O Links Configuration Logic, ExampleConfiguration Guidelines Specify the Number of I/O Link ModulesControlling the I/O Link Module Set Master or Slave Mode bitReset or Stop bit Start/Restart bitDisable or Enable the Input Update bit Disable or Enable the Output Update bitMonitor Communications Status bit Monitoring Link OperationMonitor the Module bit Monitor for an Invalid Configuration or Link Fault bit Monitor for Link Failure bitError Codes Troubleshooting Error Description RecommendedAction CodeConfiguration Error Codes Index GFK-0644A Index