GE Series 90-70 manual Configuration Guidelines, Specify the Number of I/O Link Modules

Page 33

4

Configuration Guidelines

To configure the I/O Link(s) in a PLC system, enter constant data values into the appropriate %P registers. These values determine:

HThe number of I/O Link Interface Modules in the PLC.

HThe rack and slot location of each I/O Link Interface Module.

HThe data length for each slave device (32 or 64 for a Power Mate).

HThe beginning address in PLC %I memory for input data.

HThe beginning address in PLC %Q memory for output data.

This must be done before the start command is issued to any I/O Link Interface Module (as explained later in this chapter).

Program references for the I/O Link Program Blocks are listed in the table opposite.

Specify the Number of I/O Link Modules

The total number of modules specified in %P must be compatible with the Program

Block being used:

A.for LINK73X, %P00001 must be 1

B.for LINK77X, %P00001 may be 1 or 2

C.for LINK78X, %P00001 may be 1 to 4

Configuring the I/O Link Module as a Master

If the I/O Link Interface Module is a master, specify a data length and references for each slave on the I/O Link. The data length (I/O count) for each device must be 0, 32, or 64. No other values are correct.

The starting %I and %Q addresses must be compatible with the Program Block being used:

A.for LINK73X, the range is (1 to 481) or (1 to 449)

B.for LINK77X, the range is (1 to 2017) or (1 to 1985)

C.for LINK78X, the range is (1 to 4065) or (1 to 4033)

Configure all devices to have consecutive numbers; do not leave any ªholesº in the configuration for a module. If a 0 is configured for a slave's data length, the data lengths of all subsequent slaves on the same link must also be 0.

Note

All %P references from %P0009 through %P0209 which are not used for the application must be set to 0 before the link is activated.

Configure all %I and %Q starting addresses at word boundaries.

Configuring the I/O Link Module as a Slave

If the module is a slave, configure it to be Device 0. Specify its data length (32 or 64) and references.

Assign a starting %I and %Q address for the module that is compatible with the

Program Block being used. The %I and %Q addresses must begin on word boundaries.

Set to 0 the unused %P references for devices 1 through 15. See ªConfiguring the I/O

Link Module as a Masterº, above.

GFK±0644

Chapter 4 Programming Guide

29

Image 33
Contents GE Fanuc Automation GFL±002 Content of this Manual Related PublicationsWe Welcome Your Comments and Suggestions Contents System Overview Chapter IntroductionMaster or Slave Operation Application Software LEDs Module DescriptionModule Specifications Reset PushbuttonSerial Ports CatalogNumber Cable Types for the I/O LinkCable Lengths on the I/O Link Optical Adapter Input and Output Data Operation of the I/O LinkData Returned by Slaves Data Sent by the MasterInputs and Outputs Hold Last State Faults on the I/O Link Link Control DiagnosticsInstall the module and complete the I/O Link Getting StartedComplete the program logic for the I/O Link Module Installing the I/O Link Interface Module in the Rack Chapter InstallationLED Name LED Status Indication Removing the I/O Link Interface Module from the RackConnecting the I/O Link Interface Module to Other Devices Ports on the I/O Link ModuleLink Module Used as a Master Serial Port Pin Assignments Link Module Used as a SlaveOrder of the Devices on the Link Cable Diagram, No Optical Adapter Optical Adapter Installation Cable Diagram, Electrical Cable to Optical AdapterCable Connections Configuration Steps Chapter Logicmaster 90-70 ConfigurationGFK-0644A Overview Chapter Programming GuideAdding the Program Block Logic to an Application Program Selecting a Program BlockUsing Multiple Calls to the Program Block Calling the Program BlockExample Call Instruction 3rdModule 4thModule Program %P References for the I/O Link Program BlocksGlobal %G References for the I/O Link Program Blocks Using Nicknames for the %P ReferencesConfiguration Logic, Example Configuring I/O LinksSpecify the Number of I/O Link Modules Configuration GuidelinesReset or Stop bit Set Master or Slave Mode bitControlling the I/O Link Module Start/Restart bitDisable or Enable the Output Update bit Disable or Enable the Input Update bitMonitoring Link Operation Monitor the Module bitMonitor Communications Status bit Monitor for Link Failure bit Monitor for an Invalid Configuration or Link Fault bitError Description RecommendedAction Code Error Codes TroubleshootingConfiguration Error Codes Index GFK-0644A Index